Sensor excitation
Type PB / PC / PX
3V DC for low power pulse signals and 1.2V DC for coil pick-up.
Type PD
1.2; 3; 8.2; 12; 24V DC - max. 50mA@24V DC
Type PD-XI
Intrinsically safe: Pulse signals: 1.2; 3; 8.2 - max. [email protected] DC.
Type PF / PM
1.2; 3; 8.2; 12; 24V DC - max. 400mA@24V DC.
Terminal connections
Type
Removable plug-in terminal strip. Wire max. 1.5mm
2
and 2.5mm
2
Data protection
Type
EEPROM backup of all settings.
Backup of running totals every minute. Data retention at least 10 years.
Password
Configuration settings can be Password protected.
Hazardous area
Intrinsically safe
Type XI
ATEX approval :
II 1 G Ex ia IIB/IIC T4 Ga
II 1 D Ex ia IIIC T100°C Da
IECEx approval :
Ex ia IIB/IIC T4 Ga
Ex ia IIIC T100°C Da
Explosion proof
Type XF
ATEX approval ref: II 2 EEx d IIB T5. Weight appr. 15kg.
Dimensions of enclosure: 350 x 250 x 200mm (13.7” x 9.9” x 7.9”) LxHxD.
Directives and Standards
EMC
EN 61326-1; FCC 47 CFR part 15
LVD
EN/IEC 61010-1
ATEX / IECEx
EN/IEC 60079-0; EN/IEC 60079-11
RoHS
EN 50581
IP & NEMA
EN 60529; NEMA 250
Inputs
Flowmeter
Type P
npn; npn-lp; reed; reed-lp; pnp; pnp-lp; namur; coil-hi; coil-lo; 8-1 DC; 12 DC; 24 DC
Frequency Minimum 0 Hz – maximum 7 kHz for total and flow rate.
Maximum frequency depends on signal type and internal low-pass filter.
E.g. Reed switch with low-pass filter: max. frequency 120 Hz.
K-Factor 0.000010 - 9999999 with variable decimal position.
Low-pass filter
npn-lp; reed-lp; pnp-lp
Temperature
Type TP
2 or 3 wire PT100.
Standard range -100°C to +200°C (-148°F to 392°F) – accuracy 0.1 °C (0.18°F).
Extended range (ZV) -200°C to +800°C (-328°F to 1832°F) - accuracy 0.5 °C (0.9°F).
Update time four times a second.
The linearity is internally compensated.
Type TA
(0)4-20mA - with signal calibration feature at any current within the range.
Type TU
0-10 V - with signal calibration feature at any voltage within the range.
Accuracy Resolution: 14 bit.. Error < 0.025mA / ±0.125% FS. Low level cut-off programmable.
Span 0.000010 - 9999999 with variable decimal position.
Update time Four times a second.
Voltage drop, Type TA 2.5 Volt @ 20mA.
Load impedance, Type TU 3kOhm
For signal type TA and TU: external power to sensor required; e.g. Type PD.