FW_F115P_v1702_02_EN
Page 46
PDU
ADDRESS
REGISTER VARIABLE
FLOW RATE B
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 67
[h] 0x043
40068
Backlight brightness
1
r/w uint16 0=0% (off)
1=20%
2=40%
3=60%
4=80%
5=100% (full)
PDU
ADDRESS
REGISTER VARIABLE
POWER MANAGEMENT
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 80
[h] 0x050
40081
LCD update time
1
r/w uint16 0=fast
1=1sec
2=3sec
3=15sec
4=30sec
5=off
[d] 81
[h] 0x051
40082
power mode
1
r/w uint16 0=operational
1=shelf
PDU
ADDRESS
REGISTER
VARIABLE
FLOWMETER
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 96
[h] 0x060
40097
flowmeter signal A
1
r/w
uint16 0=NPN
1=NPN LP
2=Reed
3=Reed LP
4=PNP
5=PNP LP
6=NAMUR
7=coil hi
8= coil lo
9=act 8.1V
10= act 12 V
11=act 24V
[d] 97
[h] 0x061
40098
flowmeter signal B
1
r/w
uint16 0=NPN
1=NPN LP
2=Reed
3=Reed LP
4=PNP
5=PNP LP
6=NAMUR
7=coil hi
8= coil lo
9=act 8.1V
10= act 12 V
11=act 24V
[d] 252
[h] 0x0FC
40253
bidirectional
1
r/w
uint16 0=disable
1=enable
[d] 253
[h] 0x0FD
40254
phase
1
r/w
uint16 0=90 degrees
1=270 degrees
[d] 73
[h] 0x049
40074
count negative
1
r/w
uint16 0=disable
1=enable
[d] 254
[h] 0x0FE
40255
K-factor
1
r/w
uint16 0=Single
1=Dual
[d] 140
[h] 0x08C
40141
calculate
1
r/w
uint16 0=diff
1=add
PDU
ADDRESS
REGISTER
VARIABLE
ANALOG
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 112
[h] 0x070
40113
output
1
R/W
uint16
0=disable
1=enable
[d] 113
[h] 0x071
40114
rate-min
2
R/W
uint32
0…9999999
Representation: unit, time, decimals
depending on variables 48, 49, 50
[d] 125
[h] 0x07D
40126
rate-min, sign
1
R/W
uint16
0=positive (+)
1=negative (-)
[d] 116
[h] 0x074
40117
rate-max
2
R/W
uint32
0…9999999
Representation: unit, time, decimals
depending on variables 48, 49, 50
[d] 126
[h] 0x07E
40127
rate-max, sign
1
R/W
uint16
0=positive (+)
1=negative (-)
[d] 124
[h] 0x07C
40125
rate-sel
1
r/w
uint8
0=
signed
1=absolute
2=rate A
3=rate B
[d] 119
[h] 0x077
40120
cut off
1
R/W
uint16
0...99
Representation: 0.0 – 9.9%
[d] 120
[h] 0x078
40121
tune-min
1
R/W
uint16
0...9999
[d] 122
[h] 0x07A
40123
tune-max
1
R/W
uInt16
0...9999
[d] 127
[h] 0x07F
40128
filter
1
R/W
uint16
1...99
PDU
ADDRESS
REGISTER
VARIABLE
PULSE
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 135
[h] 0x087
40136
mode
1
R/W
uint16
0=not negative 1=separated 2=signed
[d] 128
[h] 0x080
40129
width
1
R/W
uint16
0…9999
Representation: 0.001 – 9.999 sec
[d] 133
[h] 0x085
40134
decimals
1
R/W
uint16
0…3
[d] 130
[h] 0x082
40131
amount
2
R/W
uint32
1...9999999
Representation: 0.001 – 9999999
depending on variable 133