FW_F115P_v1702_02_EN
Page 18
WIDTH
92
The pulse width determines the time that the output will be active; in other words
the pulse duration. Value “zero” will disable the pulse output.
The pulse signal always has a 50% duty cycle, hence the minimum time between
the pulses is equal to the pulse width setting. If the frequency should go out of
range – when the flow rate increases for example – an internal buffer will be used
to “store the missed pulses”: As soon as the flow rate slows down, the buffer will
be “emptied”.
It might be that pulses will be missed due to a buffer-overflow, so it is advised to
program this setting within its range!
DECIMALS
93
This setting is used to set the amount of digits behind the decimal point for the
amount.
AMOUNT
94
A pulse will be generated every time a certain quantity is added to the total. Enter
this quantity here while taking the decimals for pulse into account.
3.1.11
EXPLANATION OF SETUP-MENU A - COMMUNICATION (OPTION)
This product is designed for the connection to a communication network. Products with a
communication option do not include cyber security functions. Fluidwell cannot take any
responsibility for the cyber security, omissions or errors in the communication safety. To maintain a
secure operation, automation and control, it is the sole responsibility of the owner to install and
manage the appropriate safety measures to protect the network, the product and the communication
against any kind of security breaches.
The functions described below deal with hardware that is not part of the standard delivery.
Programming of these functions does not have any effect if this hardware has not been installed.
Consult Appendix C and the Modbus communication protocol description for a detailed explanation.
SPEED
A1
This setting is used to set the Baudrate.
9600 is a low power setting, 9600HP is a high power setting (Modbus compliant).
ADDRESS
A2
This setting is used to set the communication address for the F115-P.
MODE
A3
This setting is used to set the Modbus transmission mode. Select OFF to disable
the communication.
DATABITS
A4
This setting determines for communication the number of data bits.
Select 8 bit for BUS-RTU and 7 bits for BUS-ASC.
PARITY
A5
As demanded by the connected equipment, select a parity bit (odd, even or none).
3.1.12
EXPLANATION OF SETUP-MENU B - OTHERS
For support and maintenance it is important to have information about the characteristics of the F115-P. Your
supplier will ask for this information when support is required.
MODEL
B1
This setting shows the model name.
SOFTWARE VERSION
B2
This setting shows the version number of the firmware (software).
SERIAL NO.
B3
This setting shows the serial number.
PASSWORD
B4
This setting is used to set a password (pin code) to limit the access for the setup
menu. Only persons who know the pin code can access the setup menu. The pin
code 0000 disables the pin code to allow for access by any person.
TAG-NR
B5
This setting is used to set a tag number for the F115-P.