![Fluidwell F112-P Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/fluidwell/f112-p/f112-p_manual_2309005045.webp)
FW_F112P_v1901_02_EN.docx
Page 45
Setup variables
PDU
ADDRESS
REGISTER
VARIABLE
TOTAL
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 32
[h] 0x020
40033
unit
1
R/W uint16 0=none
1=L
2= m
3
3=kg
4= lb
5=GAL
6= USGAL
7=bbl
[d] 33
[h] 0x021
40034
decimals
1
R/W uint16
0…3
[d] 34
[h] 0x022
40035
K-Factor
2
R/W uint32 1...9999999
Representation: 0.000010…9999999
depending on variable 37: decimals K-Factor.
[d] 37
[h] 0x025
40038
K-Factor decimals
1
R/W uint16
0…6
PDU
ADDRESS
REGISTER
VARIABLE
FLOW RATE
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 48
[h] 0x030
40049
unit
1
R/W uint16 0=mL
1=L
2= m
3
3=mg
4=g
5=kg
6=ton
7=GAL
8=bbl
9=lb
10=cf
11=rev
12=none
13=scf
14=NM
3
15=NL
16=p
[d] 49
[h] 0x031
40050
time unit
1
R/W uint16 0=/sec
1=/min
2=/hour 3=/day
[d] 50
[h] 0x032
40051
decimals
1
R/W uint16
0…3
[d] 51
[h] 0x033
40052
K-Factor
2
R/W uint32 1...9999999
Representation: 0.000010…9999999
depending on variable 54: decimals K-Factor.
[d] 54
[h] 0x036
40055
K-Factor decimals
1
R/W uint16
0…6
[d] 55
[h] 0x037
40056
number of pulses
1
R/W uint16 1...255
[d] 56
[h] 0x038
40057
cut-off time
1
R/W uint16 1...9999
Representation: 0.1
–
999.9 sec
PDU
ADDRESS
REGISTER
VARIABLE
DISPLAY
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 64
h; 0x040
40065
display function
1
R/W uint16 0=total
1=flow rate
d; 67
[h] 0x043
40068
backlight brightness
1
R/W uint16 0=off
1=20%
2=40%
3=60%
4=80%
5=100%
PDU
ADDRESS
REGISTER
VARIABLE
POWER MANAGEMENT
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 80
[h] 0x050
40081
LCD update time
1
r/w
uint16 0=fast
1=1sec
2=3sec
3=15sec
4=30sec
5=off
[d] 81
[h] 0x051
40082
power mode
1
r/w
uint16 0=operational
1=shelf
PDU
ADDRESS
REGISTER
VARIABLE
FLOWMETER
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 96
[h] 0x060
40097
flowmeter signal
1
R/W uint16 0=NPN
1=NPN LP
2=Reed
3=Reed LP
4=PNP
5=PNP LP
6=NAMUR
7=coil hi
8= coil lo
9=act 8.1V
10= act 12 V
11=act 24V