2 - BACKLIGHT
The functions below will only effect the optional LED-backlight.
BACKLIGHT
(OPTION)
21
If a LED backlight has been supplied, the color can be selected.
Following selections are available:
OFF - GREEN - AMBER
BRIGHTNESS
(OPTION)
22
The density of the backlight can be set in following range:
1 - 5
One is minimum and five is maximum brightness.
3 - SENSOR
FORMULA
31
The F090-A-PL can process the 4-20mA signal in two ways:
▪
Interpolation: the signal is processed linear
V = S x I
▪
Square root: for differential pressure
V = S
√
I
where:
V = Value: the calculated value
S = Span: the value at maximum signal (Span). The Span is
programmed with setting 14.
I = Input: the scaled analogue input value; in these formulas value 0
(zero) for (0)4mA and value 1 (one) for 20mA.
FILTER
32
The analogue output signal of a sensor does mirror a value. This value is
measured several times a second by the F090-A-PL. The value measured
is a "snap-shot" of the real signal as it will be fluctuating. With the help of
this digital filter a stable and accurate reading can be obtained while the
filter level can be set to a desired value.
The filter principal is based on three input values: the filter level (01-99),
the last measured analogue value and the last average value. The higher
the filter level, the longer the response time on a value change will be.
Below, several filter levels with there response times are indicated:
F
ILTER VALUE
R
ESPONSE TIME ON STEP CHANGE OF ANALOG VALUE
.
T
IME IN SECONDS
50%
INFLUENCE
75%
INFLUENCE
90%
INFLUENCE
99%
INFLUENCE
01
filter disabled
filter disabled
filter disabled
filter disabled
02
0.3 seconds
0.5 seconds
1.0 seconds
1.8 seconds
03
0.5 seconds
1.0 seconds
1.5 seconds
3 seconds
05
1.0 seconds
1.8 seconds
2.8 seconds
5.3 seconds
10
1.8 seconds
3.5 seconds
5.6 seconds
11 seconds
20
3.5 seconds
7.0 seconds
11 seconds
23 seconds
50
8.8 seconds
17 seconds
29 seconds
57 seconds
75
13 seconds
26 seconds
43 seconds
86 seconds
99
17 seconds
34 seconds
57 seconds
114 seconds
Continued next page >>>
Содержание F090-A-PL
Страница 27: ...FW F090 A PL M_v0403_07_EN docx Page 27 APPENDIX C DECLARATION OF CONFORMITY ...
Страница 28: ...FW F090 A PL M_v0403_07_EN docx Page 28 APPENDIX D CONTROL DRAWING ...
Страница 30: ...FW F090 A PL M_v0403_07_EN docx Page 30 NOTES ...
Страница 31: ...FW F090 A PL M_v0403_07_EN docx Page 31 NOTES ...