1 - DISPLAY (CONTINUED) 

OFFSET  
14 

The unit need to know the value at minimum signal. 
The following range can be programmed: 
 
 

-99,999 to + 199,999 

 
The 

minus

 for a 

negative

 value can selected by pressing the centre and 

right button simultaneously. 

SPAN  
15 

With the span, the sensor signal is converted to a certain value.  
The 

span 

is determined on the basis of the 

selected measurement and 

time unit

 at 20mA.  

The more accurate the span, the more accurate the functioning of the 
system will be. The following range can be programmed: 
 
 

0.00001 to + 199,999 

 

Example 1  

Calculating the span for a level measurement  

 

   

application: 
Let us assume that the sensor generates 20mA at a level 
of 2,481.3 Liters, the selected unit is "Liters" and one 
decimal.  
The span is 2481.3 
Enter: 
SETUP 11: “L” 
SETUP 12: “1111.1” 
SETUP 13: "2481.3 
SETUP 14 "0.00". 

 

Example 2  

Calculating the span for a level measurement  

 

   

Application with an offset: 
Let us assume that the sensor generates 4mA at a level 
of 200.00 USGAL and 20mA at a level of 652.31 USGAL, 
the selected unit is “USG” and two decimals. 
The span is 652.31-200=452.31.  
Enter: 
SETUP 11: “USG” 
SETUP 12: “222.22” 
SETUP 13: "452.31 
SETUP 14 "200.00". 

DIRECTION 
16 

If the display is required to increase in value as the input current 
increases, select the scale direction 

“normal”.  

Alternatively, select “reverse” if the display is required to decrease as the 
input current rises. 

CURRENT 
17 

Do select “ON” if you want the actual current value to be displayed for the 
operator. 

PERCENTAGE 
18 

Do 

select “ON” if you want to display the 0% value (value at minimum 

sensor signal) and 100% (value at maximum sensor signal). 

BARGRAPH  
19 

The bargraph (piegraph) displayed at operator level is percentage-wise 
related to the input signal: minimum signal is 0% (setup 33) and maximum 
signal is 100% (setup 34).  
With this function, the bargraph can be enabled / disabled. 
Following selections are available: 
 
 

 

OFF - ON 

 

 
 

 

Содержание F090-A-PL

Страница 1: ...nput sensor 4 20mA Options Intrinsically Safe F Series Field mounted indicators for safe and hazardous areas More info www fluidwell com fseries F Series Field mounted indicators for safe and hazardous areas More info www fluidwell com fseries ...

Страница 2: ...isposed of according to local regulations regarding waste electronic equipment If a battery is present in this product it should be disposed of separately The separate collection and recycling of your waste equipment will help to conserve natural resources and ensure that it is recycled in a manner that protects the environment SAFETY RULES AND PRECAUTIONARY MEASURES The manufacturer accepts no re...

Страница 3: ...r procedures which if not performed correctly may lead to personal injury a safety hazard or damage of the F090 A PL or connected instruments A caution indicates actions or procedures which if not performed correctly may lead to personal injury or incorrect functioning of the F090 A PL or connected instruments A note indicates actions or procedures which if not performed correctly may indirectly a...

Страница 4: ...s 2 About the operation manual 3 Contents manual 4 1 Introduction 5 3 Configuration 8 4 Installation 15 5 Intrinsically safe applications 19 6 Maintenance 23 Appendix A Technical specification 24 Appendix B Problem solving 26 Appendix C Declaration of Conformity 27 Appendix D Control Drawing 28 Index of this manual 29 Notes 30 ...

Страница 5: ...nd does not require any additional external power supply Fig 1 Application example of the F090 A PL Configuration of the unit The F090 A PL has been designed to be implemented in many types of applications For that reason a SETUP level is available to configure your F090 A PL according to your specific requirements It includes several important features such as Span measurement units display optio...

Страница 6: ...instruction is meant for users operators 2 2 CONTROL PANEL The following keys are available Fig 2 Control Panel Functions of the keys This key is used to program and save new values or settings It is also used to gain access to SETUP level please read chapter 3 This key is used to SELECT actual mA value 0 and 100 value The arrow key is used to increase a value after PROG has been pressed or to con...

Страница 7: ... this main display automatically Display actual mA value if activated After pressing SELECT the actual input current mA will be displayed Display 0 100 if activated After pressing SELECT a few times the 0 value 4mA and 100 value 20mA will be displayed Under range over range If the input current is in between 3 5mA and 3 75mA low range will be displayed If the input current is in between 3 75mA and...

Страница 8: ...nual are to be observed Ensure that the measuring system is correctly wired up according to the wiring diagrams The housing may only be opened by trained personnel Take careful notice of the Safety rules instructions and precautionary measures in the front of this manual 3 2 PROGRAMMING SETUP LEVEL 3 2 1 GENERAL Configuration of the F090 A PL is done at SETUP level SETUP level is reached by pressi...

Страница 9: ...has a unique number which is displayed below the word SETUP at the bottom of the display The number is a combination of two figures The first figure indicates the function group and the second figure the sub function Additionally each function is expressed with a keyword After selecting a sub function the next main function is selected by scrolling through all active sub functions e g 1 11 12 13 1...

Страница 10: ...When data is altered but ENTER is not pressed then the alteration can still be cancelled by waiting for 20 seconds or by pressing ENTER for three seconds the PROG procedure will be left automatically and the former value reinstated Note alterations will only be set after ENTER has been pressed To return to OPERATOR level In order to return to the operator level PROG will have to be pressed for thr...

Страница 11: ...HERS 41 MODEL F090 A 42 SOFTWARE VERSION 03 03 xx 43 SERIAL NO 44 PASSWORD 0000 9999 45 TAGNUMBER 0000000 9999999 3 2 3 EXPLANATION OF SETUP FUNCTIONS 1 DISPLAY UNIT 11 SETUP 21 determines the measurement unit to be displayed The following units can be selected mL L nL M3 nM3 mg g kg ton gal sgal igal lb bbl cf scf p rev C F K m mm cm mtr inch ft psi mbar bar barg mmwk mmwc cmwk cmwc mwk mwc inwc ...

Страница 12: ...ample 2 Calculating the span for a level measurement Application with an offset Let us assume that the sensor generates 4mA at a level of 200 00 USGAL and 20mA at a level of 652 31 USGAL the selected unit is USG and two decimals The span is 652 31 200 452 31 Enter SETUP 11 USG SETUP 12 222 22 SETUP 13 452 31 SETUP 14 200 00 DIRECTION 16 If the display is required to increase in value as the input ...

Страница 13: ...The value measured is a snap shot of the real signal as it will be fluctuating With the help of this digital filter a stable and accurate reading can be obtained while the filter level can be set to a desired value The filter principal is based on three input values the filter level 01 99 the last measured analogue value and the last average value The higher the filter level the longer the respons...

Страница 14: ...ibrated with the actual 20mA value After pressing enter TUNED will be displayed as soon as the calibration is completed From that moment the analog value must be less than the calibrated value for a reliable measurement DFLT with this setting the manufactures value is re installed SET to select the last calibrated value Remark the analog input value can be programmed up side down if desired so 20m...

Страница 15: ...Take the relevant IP classification of the enclosure into account see identification plate Even an enclosure rated for IP67 TYPE 4 X should NEVER be exposed to strongly varying weather conditions When panel mounted the front panel of the F Series is rated for IP65 TYPE 4 X When used in very cold surroundings or varying climatic conditions inside the instrument case take the necessary precautions a...

Страница 16: ...0 60 mm 2 36 120 mm 4 72 M20 x 1 5 PG9 PG9 30mm 30mm 22 5mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30mm 30mm 22 50mm M20 x 1 5 22 5mm M20 x 1 5 M20 x 1 5 25mm 25mm 22 5mm 1 2 NPT 0 9 3x 1 2 NPT 0 12 0 12 0 9 HA HM HN HO HP HT HU 6 x M12 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 115 mm 4 53 98 mm 3 86 HB 29 1 mm 1 15 31 mm 1 22 HZ 4x M20 x 1 5 15 15 15 HV 23 23 16 mm ...

Страница 17: ... 40 60 mm 2 36 120 mm 4 72 HD HK HK back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 20mm D 20mm D 16mm HC 75 mm 2 95 118 mm 4 65 104 mm 4 09 HJ 0 9 0 12 0 12 3x D 22mm 0 866 115 mm 4 53 98 mm 3 86 29 1 mm 1 15 31 mm 1 22 ...

Страница 18: ...propriate to the application 4 4 2 TERMINAL CONNECTORS For Intrinsically Safe applications read chapter 5 The following terminal connectors are available Fig 6 Overview of terminal connectors standard configuration F090 A PL and options REMARKS TERMINAL CONNECTORS Terminals 1 2 sensor INPUT LOOP POWERED 4 20mA type A PL Model F090 A PL is powered from the 4 20mA sensor signal The unit will process...

Страница 19: ...ct certificate KEMA 05ATEX1168 X For installation under IECEx scheme this intrinsically safe device must be installed in accordance the product certificate IECEx KEM 08 0006X For installation under CSA this intrinsically safe device must be installed in accordance with the product certificate CSA 08 2059461 X For installation under FM this intrinsically safe device must be installed in accordance ...

Страница 20: ...or Class I II III Div 1 Grps A B C D E F G Temp class T4 Class I Zone 0 AEx ia IIC T4 For installation and entity evaluation refer to control drawing no FWCD 0002 CSA Certificate nr CSA 08 2059461 FM Project ID 3033306 Made in Veghel The Netherlands by Fluidwell bv MODEL F0xx A PL XI Signal input 4 20mA loop powered Intrinsically Safe Possible static hazard Do not rub KEMA 05ATEX1168 X Tamb IP67 I...

Страница 21: ...US AREA SAFE AREA Power supply For example MTL5025 max 30 V max 200 mA max 0 75 W Uo Io Po Note above values are safety values Consult the technical specification for operational values Power supply For example MTL5025 max 30 V max 93 mA max 0 92 W Uo Io Po I S sensor input type A PL 4 20mA input loop powered Backlight option type ZB Sensor supply is not available unit is input loop powered type P...

Страница 22: ...battery with the utmost care to prevent a short circuit and damage 4 Do not recharge crush disassemble incinerate heat above its rated temperature or expose the contents to water 5 Dispose of the battery in accordance with the inter national the manufacturer s and the plant owner s standards and regulations 6 Read and understand the instructions 7 Get approval from the safety officer to do the wor...

Страница 23: ... A PL does not require special maintenance unless it is used in low temperature applications or surroundings with high humidity above 90 annual mean It is the users responsibility to take all precautions to dehumidify the internal atmosphere of the F090 A PL in such a way that no condensation will occur for example by placing dry silica gel sachet in the casing just before closing it Furthermore i...

Страница 24: ...nclosure Field wall mount enclosures Classification Aluminum enclosures Type HA Type HM Type HN Type HO Type HP Type HT Type HU Type HV Type HZ GRP enclosures Type HD Type HE Type HF Type HG Type HJ Type HH Type HK Dimensions 130 x 120 x 75mm 5 10 x 4 72 x 2 95 LxHxD IP67 NEMA4X Drilling 2x PG9 1x M20 Drilling 2x M16 1x M20 Drilling 1x M20 Drilling 2x M20 Drilling 6x M12 Drilling 1x NPT Drilling 3...

Страница 25: ...n Operator functions Displayed functions top line main display value bottom line measuring unit and messages bottom line actual percentage in relation to it s measuring range can be enabled disabled piegraph 10 segment display related to the input signal can be enabled disabled actual sensor input value in mA can be enabled disabled displayed value at 0 of the input signal can be enabled disabled ...

Страница 26: ...one possibility left call your supplier ALARM When the alarm flag starts to blink an internal alarm condition has occurred Press the select button several times to display the 5 digit error code The codes are 0001 irrecoverable display data error data on the display might be corrupted 0002 irrecoverable data storage error the programming cycle might have gone wrong check programmed values 0003 err...

Страница 27: ...FW F090 A PL M_v0403_07_EN docx Page 27 APPENDIX C DECLARATION OF CONFORMITY ...

Страница 28: ...FW F090 A PL M_v0403_07_EN docx Page 28 APPENDIX D CONTROL DRAWING ...

Страница 29: ...ecimals 11 12 measuring unit 11 Span 12 time unit 11 functional description 5 hardware version 3 input loop powered 18 Installation 15 intrinsic safety 19 Intrinsic safety 19 keys 6 loop powered 18 main function 9 maintenance 23 manual version 3 model 14 Operator level 7 pass code 14 26 Piegraph 12 problem solving 26 rate Total 7 repair 23 sensor 13 serial number 14 SETUP level 8 software version ...

Страница 30: ...FW F090 A PL M_v0403_07_EN docx Page 30 NOTES ...

Страница 31: ...FW F090 A PL M_v0403_07_EN docx Page 31 NOTES ...

Страница 32: ...rmula interpol 32 filter 01 off 33 calibrat low 4mA default 34 calibrat high 20mA default 4 OTHERS 41 model F090 A F090 A F090 A 42 software version 03 ____ ____ 03 ____ ____ 03 ____ ____ 43 serial number _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 44 pass code 0000 45 tagnumber 0000000 Fluidwell bv PO box 6 Voltaweg 23 Website www fluidwell com 5460 AA Veghel 5466 AZ Veghel Find your nearest repres...

Отзывы: