3.3.3
EXPLANATION OF SETUP-MENU 2 - ALARM
SETUP
FUNCTIONS
AND
VARIABLES
2
ALARM
2.1
ALARM VALUE LOW
TEMPERATURE
The low alarm is set with this setting. An alarm will be generated as
long as the temperature is lower than this value.
With value 0.0 this function is disabled.
2.2
ALARM VALUE HIGH
TEMPERATURE
The high alarm is set with this setting. An alarm will be generated as
long as the temperature is higher than this value.
With value 0.0 this function is disabled.
2.3
DELAY TIME ALARM
LOW TEMPERATURE
An alarm generated by SETUP 2.1
“low” can be ignored during X-time
period. If the actual temperature is still incorrect after this delay time,
then an alarm will be generated.
2.4
DELAY TIME ALARM
HIGH TEMPERATURE
An alarm generated by SETUP 2.2
“high” can be ignored during X-
time period. If the actual temperature is still incorrect after this delay
time, then an alarm will be generated.
2.5
ALARM OUTPUT
TRANSISTOR /RELAY
One transistor or relay output is available to transmit the alarm
condition. Assign with this function the type of alarm to be transmitted:
low temperature alarm, high temperature alarm or both alarms.
3.3.4
EXPLANATION OF SETUP-MENU 3 - DISPLAY
SETUP
FUNCTIONS
AND
VARIABLES
3
DISPLAY
3.1
SET ALARM
This function determines if the temperature alarm values can be set at
both Operator level and SETUP-level or SETUP-level only.
If SETUP has been selected, the alarm values are still visible for the
Operator but cannot be changed.
The functions below will only affect the optional LED-backlight.
3.2
BACKLIGHT (optional)
If a LED backlight has been supplied, it can be turned on or off.
3.3
BACKLIGHT ALARM
(optional)
In case the F043-T generates a temperature alarm, the backlight can
be set to change to red. Following selections are available:
OFF:
during temperature alarm display is according to SETUP 3.2
ON:
during temperature alarm the color is red.
FLASH: during temperature alarm the color flashes red.
3.4
BL. BRIGHTNESS
(optional)
The backlight brightness is adjustable. The following can be selected:
1
– 5 (where 1 is minimum and 5 is maximum brightness)
3.3.5
EXPLANATION OF SETUP-MENU 4 - POWER MANAGEMENT
When used with the internal battery option, the user can expect reliable measurement over a long
period of time. The F043-T has several smart power management functions to extend the battery life
time significantly. Two of these functions are available.
SETUP
FUNCTIONS
AND
VARIABLES
4
POWER MANAGEMENT
4.1
LCD NEW
The calculation of the display-information influences the power
consumption significantly. When the application does not require a
fast display update, it is
strongly advised
to select a slow refresh
rate. Please understand that NO information will be lost; every pulse
will be counted and the output signal will be generated in the normal
way. The following can be selected:
Fast - 1 sec - 3 sec - 15 sec - off.
Example battery life-time:
•
FAST update: about 3 years.
•
1 sec update: about 5 years.
After a button has been pressed by the operator - the display refresh
rate will always switch to FAST for 30 seconds. When "OFF" is
selected, the display will be switched off after 30 seconds and will be
switched on as soon as a button has been pressed.