Pulse-signal PNP / PNP-LP:
The F014-P is suitable for use with flowmeters which have a PNP output signal. For a reliable pulse
detection, the pulse amplitude has to go above 1.2V. Signal setting PNP-LP employs a low-pass
signal noise filter, which limits the maximum input frequency (read chapter 3.2.3).
A sensor supply voltage is offered with terminal 7.
Fig. 23: Terminal connections - PNP signal input.
Active signals:
Active signal selection may well be desired if an active signal is offered from the sensor.
Fig. 24: Terminal connections - Active signal input.
Reed-switch:
The F014-P is suitable for use with flowmeters which have a reed-switch. To avoid pulse bounce
from the reed-switch, it is advised to select REED LP - low-pass filter (read chapter 3.2.3).
Fig. 25: Terminal connections - Reed-switch signal input.