Page 13
FW-F011-P-M_v0404_01_EN.docx
3.3.4
EXPLANATION OF SETUP-MENU 3 - POWER MANAGEMENT
When used with the internal battery option, the user can expect reliable measurement over a long
period of time. The F011-P has several smart power management functions to extend the battery life
time significantly. Two of these functions are available.
SETUP
FUNCTIONS
AND
VARIABLES
3
POWER MANAGEMENT
3.1
LCD NEW
The calculation of the display-information influences the power
consumption significantly. When the application does not require a
fast display update, it is
strongly advised
to select a slow refresh
rate. Please understand that NO information will be lost; every pulse
will be counted and the output signal will be generated in the normal
way. The following can be selected:
Fast - 1 sec - 3 sec - 15 sec - 30 sec - off.
Example battery life-time with a coil pick-up:
•
1kHz pulse and FAST update: about 2 years.
•
1kHz pulse and 1 sec update: about 5 years.
After a button has been pressed by the operator - the display refresh
rate will always switch to FAST for 30 seconds. When "OFF" is
selected, the display will be switched off after 30 seconds and will be
switched on as soon as a button has been pressed.
3.2
BATTERY MODE
The F011-P has two modes: operational or shelf.
After "shelf" has been selected, the F011-P can be stored for several
years; it will not process the sensor signal; the display is switched off
but all settings and totals are stored. In this mode, power consumption
is extremely low.
To wake up the F011-P again, press the SELECT/
key twice.
3.3.5
EXPLANATION OF SETUP-MENU 4 - FLOWMETER
The F011-P is able to handle several types of input signal. The type of flowmeter pickup / signal is
selected with SETUP 4.1. Read also paragraph 4.6.1 Terminals 1-3: Flowmeter input.
SETUP
FUNCTIONS
AND
VARIABLES
4
FLOWMETER
4.1
SIGNAL
TYPE OF SIGNAL
EXPLANATION
RESISTANCE
FREQ. / mV
REMARK
NPN
NPN input
100
kΩ pull
-up
6 kHz.
(open collector)
NPN - LP
NPN input with
low pass filter
100
kΩ pull
-up
1.2 kHz.
(open collector)
less sensitive
REED
Reed-switch input
1
mΩ pull
-up
600 Hz.
REED - LP
Reed-switch input
with low pass
filter
1
mΩ pull
-up
120 Hz.
Less sensitive
PNP
PNP input
47
kΩ pull
-down
6 kHz.
PNP - LP
PNP input with
low pass filter
100
kΩ pull
-down
1.2 kHz.
Less sensitive
NAMUR
Namur input
820
Ω pull
-down
4 kHz.
External power
required
COIL HI
High sensitive coil
input
-
20 mV p.t.p.
Sensitive for
disturbance!
COIL LO
Low sensitive coil
input
-
90 mV p.t.p.
Normal sensitivity
ACTIVE
Active pulse input
detection level
1.2V DC
47
kΩ
10 kHz.
External power
required
Содержание F011-P