Page 25
FW-F011-P-M_v0404_01_EN.docx
4.6
TERMINAL CONNECTORS SAFE AREA APPLICATIONS
– TYPE PB / PX / PD
Take careful notice of all safety and precautionary measures indicated in paragraph
4.5: Electrical Installation and review paragraph 4.5.3 and 4.5.4 before applying any
field or power supply wiring.
For Intrinsically Safe applications: read chapter 5.
Following terminal connectors are available on the F011-P when supplied with Type PB / PX / PD:
Fig. 14: Overview of terminal connectors F011-P
– type PB / PD / PX
4.6.1
TERMINALS 1-3: FLOWMETER INPUT
Three basic types of flowmeter signals can be connected to the F011-P: pulse, active pulse or coil.
The screen of the signal wire can be connected to the common ground terminal. See paragraph 4.5.
The input signal type has to be selected with the correct SETUP-function (read chapter 3.3).
On terminal 3 and 6, an internal and external sensor supply is available. To configure the sensor
supply, see paragraph 4.5.5: Sensor supply for details.
Coil
The F011-P is suitable for use with flowmeters which have a coil output signal.
Two sensitivity levels can be selected with the SETUP-function:
•
COIL LO: sensitivity from about 90mVp-p.
•
COIL HI: sensitivity from about 20mVp-p.
•
Type ZF (option): offers for setting COIL HI : sensitivity from about 10mVp-p.
•
Type ZG (option): offers for setting COIL HI : sensitivity from about 5mVp-p.
Fig. 15: Terminal connections - Coil signal input.