3.2.4 

RETURNING TO OPERATOR-LEVEL 

When all settings are configured correctly, the unit can be returned to OPERATE-level. 
Please keep a record of all settings for later reference. 
 

Use the control panel to return to OPERATE-level 

 

SELECT

-key 

In order to return to the operator level, press the SELECT-key for three seconds.  
When no keys are pressed for 2 minutes, SETUP-level will be left automatically. 
The display will deactivate the 

SETUP

 indicator and activate the 

RUN

 indicator. 

 

3.3 

CONFIGURATION SETTINGS 

All settings of the B-SMART can be set via the control panel and the SETUP-menu. Additionally, 
configuration of the B-SMART can be done using a PC with our free of charge Remote Configuration 
Tool, which allows you to setup the configuration as desired, up- or download the settings to the 
device and print a hardcopy for each product.  

The connection between the B-SMART and the PC is made by means of the service port and a 
special communications cable that can be ordered separately. This is described in section 
4.7.4: Service-port. 

The Remote Configuration Tool software package can be downloaded from our website at 
www.fluidwell.com/software and installed on a Microsoft Windows PC using the installation program. 
The installation also contains a Quickstart manual which gives detailed instructions on how to 
achieve a successful connection between PC and device. 

 

3.3.1 

OVERVIEW FUNCTIONS SETUP-LEVEL 

TOTAL 

 

1.1 

UNIT 

 m3 

 kg 

 lb 

 GAL 

 USGAL 

 bbl 

 (no unit) 

1.2 

DECIMALS 

 0.1 

 0.02 

 0.003 

1.3 

K-FACTOR 

0.000010 

 9999999 

1.4 

K-FACTOR DECIMALS 

 0.1 

 0.02 

 0.003 

 0.003 

 0.0004 

 0.00005 

 0.000006 

RATE (flowrate) 

 

2.1 

UNIT 

mL 

 L 

 m3 

 g 

 kg 

 ton 

 GAL 

 bbl 

 lb 

 cf 

 (no unit) 

2.2 

TIME 

/sec 

 /min 

 /hour 

 /day 

2.3 

DECIMALS 

 0.1 

 0.02 

 0.003 

2.4 

K-FACTOR 

0.000010 

 9999999 

2.5 

K-FACTOR DECIMALS 

 0.1 

 0.02 

 0.003 

 0.003 

 0.0004 

 0.00005 

 0.000006 

METER (flowmeter) 

 

3.1 

SIGNAL 

COIL 

 REED 

 NPN 

 PNP 

 NAMUR 

A-OUT (analog output) 

 

4.1 

OUTPUT 

enable 

 disable 

4.2 

RATE-MIN (4mA) 

0.000 

 9999999 

4.3 

RATE-MAX (20mA) 

0.000 

 9999999 

4.4 

TUNE-MIN (4mA) 

0000 

 9999 

4.5 

TUNE-MAX (20mA) 

0000 

 9999 

D-OUT (digital or pulse output) 

 

5.1 

MODE 

off 

 long 

 inter 

 short  

5.2 

DECIMALS 

 0.1 

 0.02 

 0.003 

5.3 

AMOUNT 

0.000 

 9999999 

OTHER 

 

6.1 

MODEL 

BASIC71 

6.2 

SOFTWARE VERSION 

03.06.xx 

6.3 

SERIAL NO 

xxxxxxx 

6.4 

PIN 

0000 

 9999 

6.5 

BL BACKLIGHT 

off 

 on  

Содержание B-BASIC

Страница 1: ...MART FLOWRATE INDICATOR TOTALIZER Signal input flowmeter pulse NAMUR and coil Signal outputs Analog referenced flowrate and scaled pulse referenced total B Series Basic indicators for ordinary locatio...

Страница 2: ...e natural resources and ensure that it is recycled in a manner that protects the environment SAFETY RULES AND PRECAUTIONARY MEASURES The manufacturer accepts no responsibility whatsoever if the follow...

Страница 3: ...connected instruments A caution indicates actions or procedures which if not performed correctly may lead to personal injury or incorrect functioning of the B SMART or connected instruments A note ind...

Страница 4: ...Meter flowmeter 13 3 3 5 Menu 4 A OUT analog output 13 3 3 6 Menu 5 D OUT digital or pulse output 14 3 3 7 Menu 6 Other 14 4 INSTALLATION 15 4 1 General directions 15 4 2 Installation surrounding con...

Страница 5: ...and aggravation Good readings in full sunlight and darkness through a bright backlight Mounting flexibility with a compact and durable IP65 enclosure for field wall or meter mounting Ability to proces...

Страница 6: ...e implemented in many types of applications For that reason a SETUP level is available to configure your B SMART according to your specific requirements It includes several important features such as...

Страница 7: ...Control panel Functions of the keys SELECT key This key is used to SELECT the displayed information like accumulated total and flowrate gain access to SETUP level please read chapter 3 CLEAR key This...

Страница 8: ...p to 9 999 999 before rolling over to zero The unit and number of decimals are displayed according to the configuration settings for Total Clear total The value for Total can be cleared and reset to z...

Страница 9: ...vice even when SETUP level is still active Make sure that the unit is not being used for any application when altering the settings 3 2 1 ENTERING SETUP LEVEL Configuration of the B SMART is done at S...

Страница 10: ...ng new values alterations will only be set after the SELECT and CLEAR keys have been pressed simultaneously to confirm the new value STEP 3 Step 1 Starting the programming sequence SELECT CLEAR key Wh...

Страница 11: ...4 7 4 Service port The Remote Configuration Tool software package can be downloaded from our website at www fluidwell com software and installed on a Microsoft Windows PC using the installation progr...

Страница 12: ...curate the Total K Factor the more accurate the functioning of the system will be 1 4 K FACTOR DECIMALS This decimal point determines for K Factor SETUP 1 3 the number of digits following the decimal...

Страница 13: ...it can be disabled to minimize power consumption to safe battery life When the output is disabled the current will be less than 3 4mA and the unit can still be supplied from this signal provided a po...

Страница 14: ...utput is switched off Long represents a pulse length of 100ms max 5Hz Inter represents a pulse length of 15ms max 33Hz Short represents a pulse length of 5ms max 100Hz 5 2 DECIMALS The decimal point d...

Страница 15: ...ck The housing may only be opened by trained personnel Take careful notice of the Safety rules instructions and precautionary measures at the front of this manual 4 2 INSTALLATION SURROUNDING CONDITIO...

Страница 16: ...d on the outside of the unit Fig 6 Example external label with general data Installation label A second label is located on the inside and shows additional installation data Fig 7 Example internal lab...

Страница 17: ...Page 17 FW_B SMART_v0306 01_EN docx 4 4 MECHANICAL INSTALLATION 4 4 1 DIMENSIONS ENCLOSURE Fig 8 Dimensions enclosure...

Страница 18: ...er maximum 5mm 0 2 Shaft length minimum 50mm 2 Use the correct plugs if applicable Note The rear enclosure part can be rotated in steps of 90 enabling cable entry from any side Fig 9 Installation Wall...

Страница 19: ...um rating of 0 5A e g fuse or circuit breaker must be inserted in the positive supply line in safe area The external power supply must be an approved ELV source insulated from AC mains by double reinf...

Страница 20: ...e or sine wave coil The screen of the signal wire must be connected to the common ground terminal unless earthed at the sensor itself The sensor output of the flowmeter should match with the selected...

Страница 21: ...ut Pulse signal PNP The B SMART is suitable for use with flowmeters which have a PNP output signal 3 0V is offered on terminal 3 which has to be switched by the sensor to terminal 2 SIGNAL For reliabl...

Страница 22: ...sure the contact resistance of the reed switch is less than 10k Ohm Fig 15 Terminal connections Reed switch signal input NAMUR signal The B SMART is suitable for flowmeters with a NAMUR signal The B...

Страница 23: ...ted from the internal electronics If the unit is only powered by the loop the backlight will not be activated Fig 17 Terminal connections 4 20mA analog output 4 7 3 TERMINAL 7 8 DIGITAL OUTPUT The fun...

Страница 24: ...e g a laptop The port does not use the standard type connectors but the connections are made with a special service port communications cable which is available through your supplier or our website a...

Страница 25: ...unction is disabled if not in use as this has a major influence on the battery life time Low temperatures the available power will be less due to battery chemistry NPN and PNP inputs consume more ener...

Страница 26: ...ery with the utmost care to prevent a short circuit and damage 5 Do not recharge crush disassemble incinerate heat above its rated temperature or expose the contents to water 6 Dispose of the battery...

Страница 27: ...consumption 25mA The power supply will also supply the backlight and the 8 2V DC sensor supply Battery Primary non rechargeable Lithium metal Thionyl Chloride Li SOCl2 1x3 6V 2 4Ah AA size IEC R6 ANS...

Страница 28: ...eneral Transmitting flow rate Type Loop powered 4 20mA output not isolated Supply voltage 12V lift off voltage 30V DC Max load 600 Ohm 24V DC 24V 12V 20mA Accuracy 10 bit Error 0 5 20 C Typical 45ppm...

Страница 29: ...tput does not function properly Check SETUP 4 1 is the function enabled SETUP 4 2 4 3 are the flow levels programmed correctly SETUP 4 4 4 5 are the 4mA and 20mA tuned correctly Connection of the exte...

Страница 30: ...erlands luidwell is I certified by A ertification eander Arnhem he etherlands eghel ebruary 2022 We luidwell B declare under our sole responsibility that the B Series indicators are designed and will...

Страница 31: ...technical specfication 27 terminal connectors 20 total accumulated 8 clear 8 decimals 12 display 8 K factor 12 K factor decimals 12 unit 12 LIST OF FIGURES Fig 1 Typical application for the B SMART 5...

Страница 32: ...L coil 4 A OUT 4 1 OUTPUT disable 4 2 RATE MIN 4mA 0 L 4 3 RATE MAX 20mA 99999 L 4 4 TUNE MIN 4mA 1368 4 5 TUNE MAX 20mA 5466 5 D OUT 5 1 MODE Off 5 2 DECIMALS 0 5 3 AMOUNT 0 L 6 OTHERS 6 1 MODEL BASI...

Отзывы: