No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing 
any pipe work that contains or has contained flammable refrigerant shall use any sources 
of ignition in such a manner that it may lead to the risk of fire or explosion. All possible 
ignition sources, including cigarette smoking, should be kept sufficiently far away from the 
site of installation, repairing, removing and disposal, during which flammable refrigerant 
can possibly be released to the surrounding space. Prior to work taking place, the area 
around the equipment is to be surveyed to make sure that there are no flammable hazards 
or ignition risks. 

No Smoking

 signs shall be displayed.

Ventilated area 
Ensure that the area is in the open or that it is adequately ventilated before breaking into 
the system or conducting any hot work. A degree of ventilation shall continue during the 
period that the work is carried out. The ventilation should safely disperse any released 
refrigerant and preferably expel it externally into the atmosphere. prolonged period of no 
usage.

5. MAINTENANCE AND INSPECTION

Checks to the area 
Prior to beginning work on systems containing flammable refrigerants, safety checks are 
necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating 
system, the following precautions shall be complied with prior to conducting work on the 
system. prolonged period of no usage.

Checks to the refrigeration equipment 
Where electrical components are being changed, they shall be fit for the purpose and to the 
correct specification. At all times the manufacturer's maintenance and service guidelines 
shall be followed. If in doubt consult the manufacturer's technical department for 
assistance. 
The following checks shall be applied to installations using flammable refrigerants: 
 The charge size is in accordance with the room size within which the refrigerant containing 
parts are installed; 
 The ventilation machinery and outlets are operating adequately and are not obstructed; 
 If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for 
the presence of refrigerant; 
 Marking to the equipment continues to be visible and legible. Markings and signs that are 
illegible shall be corrected; 
 Refrigeration pipe or components are installed in a position where they are unlikely to be 
exposed to any substance which may corrode refrigerant containing components, unless 
the components are constructed of materials which are inherently resistant to being 
corroded or are suitably protected against being so corroded. 

Checks to electrical devices 
Repair and maintenance to electrical components shall include initial safety checks and 
component inspection procedures. If a fault exists that could compromise safety, then no 
electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the 
fault cannot be corrected immediately but it is necessary to continue operation, an 
adequate temporary solution shall be used. This shall be reported to the owner of the 
equipment so all parties are advised. 
Initial safety checks shall include: 
. That capacitors are discharged: this shall be done in a safe manner to avoid possibility of 
sparking; 
. That there no live electrical components and wiring are exposed while charging, 
recovering or purging the system; 
. That there is continuity of earth bonding. 

Содержание ASTRALPOOL 78566

Страница 1: ...g children o persons without supervision Please ensure that Bolero ND Cleaner INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTIONS VIRON RANGE INVERTER HEAT PUMPS Installa...

Страница 2: ......

Страница 3: ...rical Wiring 3 6 Initial Start up of the Unit 4 Operation and Use 1 4 2 4 3 4 4 4 5 Maintenance and Inspection 6 Appendix Installation illustration Swimming Pool Heat Pumps Location Color screen wire...

Страница 4: ...type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Durable The heat exchanger is made of PVC Titanium tube which ca...

Страница 5: ...pliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Appliance sha...

Страница 6: ...eparately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs T...

Страница 7: ...wer Input COP Heating capacity 10 6 8 Heating Power Input COP Power Supply Compressor Quantity Compressor Fan Number Noise 1m Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimens...

Страница 8: ...ns L W H Net Weight Shipping Weight kW Btu h kW kW Btu h kW kW Btu h kW dB A mm 3 m h kPa mm mm kg kg 78575 4 6 19 5 15640 66300 0 37 3 94 12 43 4 95 3 84 15 4 13056 52360 0 6 3 81 6 4 4 04 3 38 14 4...

Страница 9: ...Ship Dimensions L W H Net Weight Shipping Weight kW Btu h kW kW Btu h kW kW Btu h kW dB A mm 3 m h kPa mm mm kg kg 78577 6 7 28 3 22780 96220 0 54 5 57 12 41 5 08 5 46 23 3 18564 79220 0 83 5 49 6 58...

Страница 10: ...Swimming Pool Heat Pump Unit UNIT 78572 78573 unit mm 2 SPECIFICATION 7 UNIT 78574 78575 unit mm Water inlet 48 3 Water outlet 48 3 465 7 9 5 2 6 8 790 470 1161 768 1046 615 435 Water inlet 48 3 Water...

Страница 11: ...2 SPECIFICATION 8 2 2 The dimensions for Swimming Pool Heat Pump Unit unit mm UNIT 78576 78577 4 7 2 1 1161 775 470 Water inlet 48 3 Water outlet 48 3 0 5 5 97...

Страница 12: ...ter 3 Close the valveand start theunit ATTN It is necessarythat the water inpipe is higherthan the poolsurface 3 INSTALLATION AND CONNECTION The schematicdiagram is forreference only Please checkthe w...

Страница 13: ...us source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool T...

Страница 14: ...tingon the sideof the basepan This fitting isdesigned to accept20mm clear vinyltubing which canbe pushed onby hand and run toa suitable drain It is easyto mistake thecondensation for awater leak insid...

Страница 15: ...our pool pump is running when the pool temperature drops more than 0 2 below set temperature Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect cont...

Страница 16: ...CLOCK Press to set the clock the timer on or timer off Fault display Click to view fault history Silent setting Click to turn on off silent function and to set timingLow speed function MODE Click to...

Страница 17: ...ode switch In the main interface click mode button or inlet water temperature setting button interface displays as follows 28 0 Click the refrigeration mode button automatic mode or heating mode butto...

Страница 18: ...ime Settings button interface displays as follows Click the value to set time directly the click confirm button to save the Settings For example setup time the 30 11 2016 16 00 00 input 30 11 16 16 00...

Страница 19: ...ton to start or end timing start setting function Timing on setting Click to set start time of the timing Timing end button Open red End gray Click this button to start or end tim ing end s etting fun...

Страница 20: ...the silent setting button and the interface displays as follows 2 4 1 The silent button Click the silent button the unit will enter the silent mode and interface displays as follows Click the silent...

Страница 21: ...t ime Click this button to set the timing silent start time Timing silent end time Click this button to set the timing silent end time Start time and end time setting value must be among the range of...

Страница 22: ...icon will flash between the the failure interface will record time code name of the fault After troubleshooting if you do not check the failure record the main interface willdisplay static if you chec...

Страница 23: ...recording curve is as follows 2 6 2 The average power curve Temperature curve automatically updates every one hour and the curve record can be stored for 60 days Start from the latest curve saved time...

Страница 24: ...heck or change the temp Sensor Check or change the temp Sensor Check or change the temp Sensor Check the pressure switch and cold circuit Check or change the temp Sensor Check the pressure switch and...

Страница 25: ...heckthe measuringvoltage check requencyconversion board hardware Checkwhether currentreturn wires connectedmotor Checkand adjustthe current measurement Checkthe input voltagemeasurement Checkthe input...

Страница 26: ...stable 12V power No use No use 485A 485B GND power Default 4 OPERATIONAND USE AC L OUT1 OUT2 OUT3 AC N OUT4 OUT5 Pc1004 GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND 0 10V OU...

Страница 27: ...output 220 230VAC Live wire input 220 230VAC Neutral wire input 220 230VAC Emergency switch input Water flow switch input System low pressure input System high pressure input Water output temperature...

Страница 28: ...25 4 OPERATION AND USE Controller interface diagram and definition...

Страница 29: ...26 4 OPERATION AND USE Controller interface diagram and definition...

Страница 30: ...27 4 OPERATIONAND USE Sign Meaning Number 22 23 Color line controller communication Main board of the input and output interface instructions below...

Страница 31: ...ge Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed Work procedure Work shal...

Страница 32: ...imes the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to install...

Страница 33: ...sphere from a leak Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into a...

Страница 34: ...e that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylin...

Страница 35: ...le before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is avai...

Страница 36: ...page protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm 2 mm 25 2 mm...

Страница 37: ...emperature R410A Pressure MPa Temperature R32 Temperature R410A Temperature R32 0 0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 51 3 20 9 4 11 19 24 31 35 39 52 5 20 9 3 5 10 18 23...

Страница 38: ...Note...

Страница 39: ......

Страница 40: ...Code 83900023...

Отзывы: