fluidra ASTRALPOOL 78566 Скачать руководство пользователя страница 25

22

4.OPERATION AND USE

Drv1 MOP alarm

Inverter offline

IPM protection

Comp. Driver Failure

DC Fan Fault

IPM Overcurrent

Inv. DC Overvoltage 

Inv. DC Lessvoltage

Inv. Input Lessvolt.

Inv. Input Overvolt.

Inv. Sampling Volt.

Comm. Err DSP-PFC

Input Over Cur.

PFC fault

IPM Over heating

Weak Magnetic Warn

Inv. Input Out Phase

IPM Sampling Cur.

Inv. Temp. Probe Fail  

Inverter Overheating

Inv. Overheating Warn

Comp. OverCur. Warn

Input Over Cur. Warn

EEPROM Error Warn

Protection/fault

Frequency conversion board fault table:

F01

F02

F03

F04

F05

F06

F07

F08

F09

F10

F11

F12

F26

F27

F15

F16

F17

F18

F19

F20

F22

F23

F24

F25

 

 

 

MOP drive alarm

Frequency conversion board and main

 

 

 

 

 

 

 

 

board communication failure

IPM modular protection 

Lack of phase, step or drive hardware

   

 

 

 

 

 

 

damag

Motor current feedback open circuit or

 

 

 

 

 

 

 

 

short circuit

IPM Input current is large   

DC bus voltage>Dc bus over-voltage

 

 

 

 

 

 

 

protection value

DC bus voltage<Dc bus over-voltage

 

 

 

 

 

 

protection value

The input voltage is low, causing the

 

 

   

 

 

 

 

   

inputcurrent is high

The input voltage is too high, more than

 

   

 

 

 

 

 

 

 

 

 outage protection current RMS

 

 

 

 

 

The input voltage sampling fault

 

 

 

 

 

DSP and PFC connect fault

 

  

 

   

 

 

The equipment load is too large

The PFC circuit protection

 

 

   

 

The IPM module is overheat

 

 

   

 

Compressor magnetic force is not

enough

 

 

 

 

 

Recoveryafter the 150s

 

 

 

 

Checkthe communicationconnection

 

 

 

 

Recoveryafter the 150s

Checkthe measuringvoltage check

 

 

 

 

 

 

requencyconversion board hardware

Checkwhether currentreturn wires

 

 

 

 

 

 

connectedmotor

Checkand adjustthe current

 

 

 

 

 

 

measurement

 

 

 

 

 

Checkthe input voltagemeasurement

 

 

 

 

 

Checkthe input voltagemeasurement

 

 

 

 

 

Checkthe input voltagemeasurement

 

 

 

 

Checkthe input voltagemeasurement

 

 

 

 

 

 

Checkand adjustthe current

measurement

 

 

 

Checkthe communicationconnection

Che ck th

  e PF C swit ch tub

  e sho rt circu

 it 

or not

Checkand adjustthe current

 

 

 

 

 

 

measurement

Checkand measurethe voltage

 

 

 

 

 

adjustment

Checkand adjustthe current

 

 

 

 

 

measurement

 

 

 

 

Inspectand replacethe sensor

Checkand adjustthe current

 

 

 

 

 

 

measurement

Checkand adjustthe current

 

 

 

 

 

 

measurement

The compressorover-current

 

 

 

protection

Checkand adjustthe current

 

 

 

 

 

 

measurement

Checkwhether the chip is damaged

 

 

 

   

 

 

 

Replacethe chip

Fault

 display

Reason

Elimination methods

 

 

 

 

The input voltage lost phase

 

 

   

 

IPM sampling electricity is fault

   

 

 

 

 

 

Sensor is short circuit or open circuit

 

   

 

The transducer is overheat

 

   

 

Transducer temperature is too high

 

   

 

Compressor electricity is large

 

   

 

 

Input current is too large

 

 

MCU error

F28

V15V over/undervoltage fault

The V15V is overload or undervoltage 

Check the V15V input voltage in range

 13.5v~16.5v or not

E081

F032

Communication Fault
(speed control module)

Fan Motor2 Fault

Speed control module and main 
board communication fail

 

 

 

 

Checkthe communication connection

1. Motor is in locked-rotor state
2.The wire connection between 
DC-fan motor module and fan 
motor is in bad contact

1.Change a new fan motor
2.Check the wire connection and make sure 
they are in good contact

Содержание ASTRALPOOL 78566

Страница 1: ...g children o persons without supervision Please ensure that Bolero ND Cleaner INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTIONS VIRON RANGE INVERTER HEAT PUMPS Installa...

Страница 2: ......

Страница 3: ...rical Wiring 3 6 Initial Start up of the Unit 4 Operation and Use 1 4 2 4 3 4 4 4 5 Maintenance and Inspection 6 Appendix Installation illustration Swimming Pool Heat Pumps Location Color screen wire...

Страница 4: ...type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Durable The heat exchanger is made of PVC Titanium tube which ca...

Страница 5: ...pliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Appliance sha...

Страница 6: ...eparately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs T...

Страница 7: ...wer Input COP Heating capacity 10 6 8 Heating Power Input COP Power Supply Compressor Quantity Compressor Fan Number Noise 1m Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimens...

Страница 8: ...ns L W H Net Weight Shipping Weight kW Btu h kW kW Btu h kW kW Btu h kW dB A mm 3 m h kPa mm mm kg kg 78575 4 6 19 5 15640 66300 0 37 3 94 12 43 4 95 3 84 15 4 13056 52360 0 6 3 81 6 4 4 04 3 38 14 4...

Страница 9: ...Ship Dimensions L W H Net Weight Shipping Weight kW Btu h kW kW Btu h kW kW Btu h kW dB A mm 3 m h kPa mm mm kg kg 78577 6 7 28 3 22780 96220 0 54 5 57 12 41 5 08 5 46 23 3 18564 79220 0 83 5 49 6 58...

Страница 10: ...Swimming Pool Heat Pump Unit UNIT 78572 78573 unit mm 2 SPECIFICATION 7 UNIT 78574 78575 unit mm Water inlet 48 3 Water outlet 48 3 465 7 9 5 2 6 8 790 470 1161 768 1046 615 435 Water inlet 48 3 Water...

Страница 11: ...2 SPECIFICATION 8 2 2 The dimensions for Swimming Pool Heat Pump Unit unit mm UNIT 78576 78577 4 7 2 1 1161 775 470 Water inlet 48 3 Water outlet 48 3 0 5 5 97...

Страница 12: ...ter 3 Close the valveand start theunit ATTN It is necessarythat the water inpipe is higherthan the poolsurface 3 INSTALLATION AND CONNECTION The schematicdiagram is forreference only Please checkthe w...

Страница 13: ...us source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool T...

Страница 14: ...tingon the sideof the basepan This fitting isdesigned to accept20mm clear vinyltubing which canbe pushed onby hand and run toa suitable drain It is easyto mistake thecondensation for awater leak insid...

Страница 15: ...our pool pump is running when the pool temperature drops more than 0 2 below set temperature Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect cont...

Страница 16: ...CLOCK Press to set the clock the timer on or timer off Fault display Click to view fault history Silent setting Click to turn on off silent function and to set timingLow speed function MODE Click to...

Страница 17: ...ode switch In the main interface click mode button or inlet water temperature setting button interface displays as follows 28 0 Click the refrigeration mode button automatic mode or heating mode butto...

Страница 18: ...ime Settings button interface displays as follows Click the value to set time directly the click confirm button to save the Settings For example setup time the 30 11 2016 16 00 00 input 30 11 16 16 00...

Страница 19: ...ton to start or end timing start setting function Timing on setting Click to set start time of the timing Timing end button Open red End gray Click this button to start or end tim ing end s etting fun...

Страница 20: ...the silent setting button and the interface displays as follows 2 4 1 The silent button Click the silent button the unit will enter the silent mode and interface displays as follows Click the silent...

Страница 21: ...t ime Click this button to set the timing silent start time Timing silent end time Click this button to set the timing silent end time Start time and end time setting value must be among the range of...

Страница 22: ...icon will flash between the the failure interface will record time code name of the fault After troubleshooting if you do not check the failure record the main interface willdisplay static if you chec...

Страница 23: ...recording curve is as follows 2 6 2 The average power curve Temperature curve automatically updates every one hour and the curve record can be stored for 60 days Start from the latest curve saved time...

Страница 24: ...heck or change the temp Sensor Check or change the temp Sensor Check or change the temp Sensor Check the pressure switch and cold circuit Check or change the temp Sensor Check the pressure switch and...

Страница 25: ...heckthe measuringvoltage check requencyconversion board hardware Checkwhether currentreturn wires connectedmotor Checkand adjustthe current measurement Checkthe input voltagemeasurement Checkthe input...

Страница 26: ...stable 12V power No use No use 485A 485B GND power Default 4 OPERATIONAND USE AC L OUT1 OUT2 OUT3 AC N OUT4 OUT5 Pc1004 GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND 0 10V OU...

Страница 27: ...output 220 230VAC Live wire input 220 230VAC Neutral wire input 220 230VAC Emergency switch input Water flow switch input System low pressure input System high pressure input Water output temperature...

Страница 28: ...25 4 OPERATION AND USE Controller interface diagram and definition...

Страница 29: ...26 4 OPERATION AND USE Controller interface diagram and definition...

Страница 30: ...27 4 OPERATIONAND USE Sign Meaning Number 22 23 Color line controller communication Main board of the input and output interface instructions below...

Страница 31: ...ge Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed Work procedure Work shal...

Страница 32: ...imes the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to install...

Страница 33: ...sphere from a leak Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into a...

Страница 34: ...e that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylin...

Страница 35: ...le before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is avai...

Страница 36: ...page protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm 2 mm 25 2 mm...

Страница 37: ...emperature R410A Pressure MPa Temperature R32 Temperature R410A Temperature R32 0 0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 51 3 20 9 4 11 19 24 31 35 39 52 5 20 9 3 5 10 18 23...

Страница 38: ...Note...

Страница 39: ......

Страница 40: ...Code 83900023...

Отзывы: