3.INSTALLATION AND CONNECTION

11

3.4 Swimming Pool Heat Pumps Plumbing 

Location: Connect the unit in the pool pump discharge (return) line downstream of all filter 
and pool pumps, and upstream of any chlorinators, ozonators or chemical pumps.

Standard model have slip glue fittings which accept  32mm or 50 mm PVC pipe for 
connection to the pool or spa filtration piping. By using a 50 NB to 40NB you can plumb 40NB 

Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to allow 
easy draining of unit for winterizing and to provide easier access should servicing be 
required. 

Condensation: Since the Heat pump cools down the air about 4 -5 , water may condense on 
the fins of the horseshoe shaped evaporator. If the relative humidity is very high, this could 
be as much as several litres an hour. The water will run down the fins into the basepan and 
drain out through the barbed plastic condensation drain fitting on the side of the basepan. 
This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand 
and run to a suitable drain. It is easy to mistake the condensation for a water leak inside the 
unit. 

NB: A quick way to verify that the water is condensation is to shut off the unit  and keep the 
pool pump running. If the water stops running out of the basepan, it is condensation. AN 
EVEN QUICKER WAY IS to TEST THE DRAIN WATER FOR CHLORINE - if the is no chlorine 
present, then it's condensation. 

To  pool

From pump

PVC COUPLER
RECOMMENDED(Provided)

CONDENSATION
DRAIN
BARB FTG

The Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no 
special plumbing arrangements except bypass(please set the flow rate according to the 
nameplate). The water pressure drop is less than 10kPa  at max. Flow rate. Since there is no 
residual heat or flame Temperatures, The unit does not need copper heat sink piping. PVC  
pipe can be run straight into the unit.

IMPORTANT NOTE: 
A WATER BY-PASS MUST BE PLUMBED TO REGULATE WATER FLOW TO HEAT PUMP. 
FAILURE TO DO SO MAY RESULT IN POOR EFFICIENCY AND REDUCED HEATING OUTPUT.

Содержание ASTRALPOOL 78566

Страница 1: ...g children o persons without supervision Please ensure that Bolero ND Cleaner INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTIONS VIRON RANGE INVERTER HEAT PUMPS Installa...

Страница 2: ......

Страница 3: ...rical Wiring 3 6 Initial Start up of the Unit 4 Operation and Use 1 4 2 4 3 4 4 4 5 Maintenance and Inspection 6 Appendix Installation illustration Swimming Pool Heat Pumps Location Color screen wire...

Страница 4: ...type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Durable The heat exchanger is made of PVC Titanium tube which ca...

Страница 5: ...pliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Appliance sha...

Страница 6: ...eparately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs T...

Страница 7: ...wer Input COP Heating capacity 10 6 8 Heating Power Input COP Power Supply Compressor Quantity Compressor Fan Number Noise 1m Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimens...

Страница 8: ...ns L W H Net Weight Shipping Weight kW Btu h kW kW Btu h kW kW Btu h kW dB A mm 3 m h kPa mm mm kg kg 78575 4 6 19 5 15640 66300 0 37 3 94 12 43 4 95 3 84 15 4 13056 52360 0 6 3 81 6 4 4 04 3 38 14 4...

Страница 9: ...Ship Dimensions L W H Net Weight Shipping Weight kW Btu h kW kW Btu h kW kW Btu h kW dB A mm 3 m h kPa mm mm kg kg 78577 6 7 28 3 22780 96220 0 54 5 57 12 41 5 08 5 46 23 3 18564 79220 0 83 5 49 6 58...

Страница 10: ...Swimming Pool Heat Pump Unit UNIT 78572 78573 unit mm 2 SPECIFICATION 7 UNIT 78574 78575 unit mm Water inlet 48 3 Water outlet 48 3 465 7 9 5 2 6 8 790 470 1161 768 1046 615 435 Water inlet 48 3 Water...

Страница 11: ...2 SPECIFICATION 8 2 2 The dimensions for Swimming Pool Heat Pump Unit unit mm UNIT 78576 78577 4 7 2 1 1161 775 470 Water inlet 48 3 Water outlet 48 3 0 5 5 97...

Страница 12: ...ter 3 Close the valveand start theunit ATTN It is necessarythat the water inpipe is higherthan the poolsurface 3 INSTALLATION AND CONNECTION The schematicdiagram is forreference only Please checkthe w...

Страница 13: ...us source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool T...

Страница 14: ...tingon the sideof the basepan This fitting isdesigned to accept20mm clear vinyltubing which canbe pushed onby hand and run toa suitable drain It is easyto mistake thecondensation for awater leak insid...

Страница 15: ...our pool pump is running when the pool temperature drops more than 0 2 below set temperature Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect cont...

Страница 16: ...CLOCK Press to set the clock the timer on or timer off Fault display Click to view fault history Silent setting Click to turn on off silent function and to set timingLow speed function MODE Click to...

Страница 17: ...ode switch In the main interface click mode button or inlet water temperature setting button interface displays as follows 28 0 Click the refrigeration mode button automatic mode or heating mode butto...

Страница 18: ...ime Settings button interface displays as follows Click the value to set time directly the click confirm button to save the Settings For example setup time the 30 11 2016 16 00 00 input 30 11 16 16 00...

Страница 19: ...ton to start or end timing start setting function Timing on setting Click to set start time of the timing Timing end button Open red End gray Click this button to start or end tim ing end s etting fun...

Страница 20: ...the silent setting button and the interface displays as follows 2 4 1 The silent button Click the silent button the unit will enter the silent mode and interface displays as follows Click the silent...

Страница 21: ...t ime Click this button to set the timing silent start time Timing silent end time Click this button to set the timing silent end time Start time and end time setting value must be among the range of...

Страница 22: ...icon will flash between the the failure interface will record time code name of the fault After troubleshooting if you do not check the failure record the main interface willdisplay static if you chec...

Страница 23: ...recording curve is as follows 2 6 2 The average power curve Temperature curve automatically updates every one hour and the curve record can be stored for 60 days Start from the latest curve saved time...

Страница 24: ...heck or change the temp Sensor Check or change the temp Sensor Check or change the temp Sensor Check the pressure switch and cold circuit Check or change the temp Sensor Check the pressure switch and...

Страница 25: ...heckthe measuringvoltage check requencyconversion board hardware Checkwhether currentreturn wires connectedmotor Checkand adjustthe current measurement Checkthe input voltagemeasurement Checkthe input...

Страница 26: ...stable 12V power No use No use 485A 485B GND power Default 4 OPERATIONAND USE AC L OUT1 OUT2 OUT3 AC N OUT4 OUT5 Pc1004 GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND 0 10V OU...

Страница 27: ...output 220 230VAC Live wire input 220 230VAC Neutral wire input 220 230VAC Emergency switch input Water flow switch input System low pressure input System high pressure input Water output temperature...

Страница 28: ...25 4 OPERATION AND USE Controller interface diagram and definition...

Страница 29: ...26 4 OPERATION AND USE Controller interface diagram and definition...

Страница 30: ...27 4 OPERATIONAND USE Sign Meaning Number 22 23 Color line controller communication Main board of the input and output interface instructions below...

Страница 31: ...ge Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed Work procedure Work shal...

Страница 32: ...imes the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to install...

Страница 33: ...sphere from a leak Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into a...

Страница 34: ...e that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylin...

Страница 35: ...le before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is avai...

Страница 36: ...page protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm 2 mm 25 2 mm...

Страница 37: ...emperature R410A Pressure MPa Temperature R32 Temperature R410A Temperature R32 0 0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 51 3 20 9 4 11 19 24 31 35 39 52 5 20 9 3 5 10 18 23...

Страница 38: ...Note...

Страница 39: ......

Страница 40: ...Code 83900023...

Отзывы: