  5. MAINTENANCE AND INSPECTION 

 

 

 

Removal and evacuation

 

When breaking into the refrigerant circuit to make repairs or for any other purpose

 

conventional procedures shall be used. However, it is important that best practice is

 

followed since flammability is a consideration. The following procedure shall be adhered to:

 

. Remove refrigerant;

 

. Purge the circuit with inert gas;

 

. Evacuate;

 

. Purge again with inert gas;

 

. Open the circuit by cutting or brazing.

 

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be 
"flushed" with OFN to render the unit safe. This process may need to be repeated several times. 
Compressed air or oxygen shall not be used for this task.

 

Flushing  shall  be  achieved  by  breaking  the  vacuum  in  the  system  with  OFN  and  continuing  to  fill 
until  the  working  pressure  is  achieved,  then  venting  to  atmosphere,  and  finally  pulling  down  to  a 
vacuum. This process shall be repeated until no refrigerant is within the system.

 

When the final OFN charge is used, the system shall be vented down to atmospheric 
pressure to enable work to take place. This operation is absolutely vital if brazing

 

operations on the pipe-work are to take place.

 

Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 
ventilation available. working on them.

 

 

Labelling

 

Equipment shall be labelled stating that it has been de-commissioned and emptied of 
refrigerant. The label shall be dated and signed. Ensure that there are labels on the

 

equipment stating the equipment contains flammable refrigerant.

 

 

Recovery

 

When removing refrigerant from a system, either for servicing or decommissioning, it is 
recommended good practice that all refrigerants are removed safely.

 

When transferring refrigerant into cylinders, ensure that only appropriate refrigerant

 

recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total 
system charge is available. All cylinders to be used are designated for the

 

recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of 
refrigerant). Cylinders shall be complete with pressure relief valve and associated shut- off valves in 
good working order. Empty recovery cylinders are evacuated and, if possible,

 

cooled before recovery occurs.

 

The recovery equipment shall be in good working order with a set of instructions 
concerning the equipment that is at hand and shall be suitable for the recovery of

 

flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in 
good working order. Hoses shall be complete with leak-free disconnect couplings and in good 
condition. Before using the recovery machine, check that it is in satisfactory working order, has 
been properly maintained and that any associated electrical

 

components are sealed to prevent ignition in the event of a refrigerant release. Consult 
manufacturer if in doubt.

 

The recovered refrigerant shall be returned to the refrigerant supplier in the correct

 

recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in 
recovery units and especially not in cylinders.

 

If compressors or compressor oils are to be removed, ensure that they have been

 

evacuated to an acceptable level to make certain that flammable refrigerant does not

 

remain within the lubricant. The evacuation process shall be carried out prior to returning the 
compressor to the suppliers. Only electric heating to the compressor body shall be

 

employed to accelerate this process. When oil is drained from a system, it shall be carried out 
safely.

 

Содержание 78568

Страница 1: ...intended for use by young children 3 08 2017 ECO RANGE INVERTER HEAT PUMPS Installation Instruction manual INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTIONS Eco Range...

Страница 2: ......

Страница 3: ...ool Heat Pumps Electrical Wiring 10 3 6 Initial Start up of the Unit 10 4 Use and Operation Instruction 11 4 1 Interface display 11 4 2 Key and icon function instruction 11 4 3 Startup shutdown 13 4 4...

Страница 4: ...t type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Durable The heat exchanger is made of PVC Titanium tube which c...

Страница 5: ...liance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Appliance shal...

Страница 6: ...ful life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 D...

Страница 7: ...g Power Input kW 0 2 1 25 0 27 1 72 COP 4 5 3 2 4 5 3 2 Power Supply 220 240V 50Hz 220 240V 50Hz Compressor Quantity 1 1 Compressor rotary rotary Fan Number 1 1 Noise dB A 38 50 39 51 Water Connection...

Страница 8: ...3 2 18 COP 4 8 3 3 Power Supply 220 240V 50Hz Compressor Quantity 1 Compressor rotary Fan Number 1 Noise dB A 42 53 Water Connection mm 48 3 Water Flow Volume m3 h 3 5 Water Pressure Drop max kPa 4 Un...

Страница 9: ...6 545 2 SPECIFICATION 2 2 The dimensions for Swimming Pool Heat Pump Unit UNIT 78566 78567 78568 unit mm 1000 Water outlet 48 3 Water inlet 48 3 418 350 97 605...

Страница 10: ...pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary that the water in pipe is higher than the pool surface The schematic diagram is forreference only Please che...

Страница 11: ...inlet These locations deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 3 How Close To Your Pool Normally the pool heat pump is ins...

Страница 12: ...to provide easier access should servicing be required To pool PVC COUPLER RECOMMENDED Provided From pump CONDENSATION DRAIN BARB FTG Condensation Since the Heat pump cools down the air about 4 5 wate...

Страница 13: ...nitial startup of the Unit NOTE In order for the unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation is com...

Страница 14: ...effective and used to enter and exit the mute mode with one click Mode key It is used to switch the unit mode temperature setting and parameter setting On off key It is used to carry out startup shutd...

Страница 15: ...sh Or else it is off Timing symbol It will display after the user sets the timing and multiple timing intervals can be set Water outlet symbol When the axillary display area displays the water outlet...

Страница 16: ...rface When it displays with half screen off or full screen off click any key for returning to ON OFF main interface When the unit is started under the control of wire controller if using the emergency...

Страница 17: ...g During the defrosting mode switch is available And when switching the mode the unit won t work under a new mode until defrosting is completed 4 5 Temperature setting Notes Under the temperature sett...

Страница 18: ...lay among timer ON1 OFF1 ON2 and OFF2 4 Use andOperation Instruction 4 6 Clock setting 6 1 System time setting Notes Under the clock setting interface if there is no operation for 20 s the system will...

Страница 19: ...lay among timer ON1 OFF1 ON2 and OFF2 4 Use andOperation Instruction 4 6 Clock setting 6 1 System time setting Notes Under the clock setting interface if there is no operation for 20 s the system will...

Страница 20: ...2 1 cancel the Timer ON OFF as below Take ON1 for example 2 To cancel the first stage timing switch cancel both ON and To cancel the second stage timing switch cancel both ON2 and To cancel the two st...

Страница 21: ...silent Keep long press of fo r 2 s Short press or 4 Use andOperation Instruction 4 7 Silent setting 7 1 One click silent function Notes 1 If one click silent and timming silentaare stared at the same...

Страница 22: ...em Check the pipe water flow and water pump Anti freezing Prot E07 Water flow is not enough Checkth ep ipew aterfl owa ndw hether waters ystemi sja mmedo rn ot Winter Primary Anti freezing Prot E19 Th...

Страница 23: ...nput voltagemeasurement Inv Sampling Volt F11 The input voltage sampling fault Checkand adjustthe current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Checkthe communicationconnection In...

Страница 24: ...Default 27 27 27 Remarks Adjustable Adjustable Adjustable 4 Use and Operation Instruction 10 2 Parameter list Meaning 21...

Страница 25: ...4 Use and Operation Instruction 4 11 Main board 22...

Страница 26: ...23 4 Use and Operation Instruction Main board of the input and output interface instructions below Number Sign Meaning 22 23 Color line controller communication...

Страница 27: ...ge Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed Work procedure Work shal...

Страница 28: ...times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to instal...

Страница 29: ...only with parts specified by the manufacturer Other parts may result in the ignition of refrigerant in the atmosphere from a leak Cabling Check that cabling will not be subject to wear corrosion exces...

Страница 30: ...igerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders for holdin...

Страница 31: ...e in accordance with manufacturer s instructions h Do not overfill cylinders No more than 80 volume liquid charge i Do not exceed the maximum working pressure of the cylinder even temporarily j When t...

Страница 32: ...0A 30mA less than 0 1 sec 186 224A 2 95mm2 95mm2 280A 30mA less than 0 1 sec 2 Three phase unit Nameplate maximum current Phase line Earth line MCB Creepage protector Signal line No more than 10A 3 1...

Страница 33: ...0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 Temperature R410A 51 3 20 9 4 11 19 24 31 35 39 Temperature R32 52 5 20 9 3 5 10 18 23 29 5 33 3 38 7 Pressure MPa 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 Temperature R410A 4...

Страница 34: ...Note...

Страница 35: ...Note...

Страница 36: ......

Отзывы: