![Flowserve MaxFlo4 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/flowserve/maxflo4/maxflo4_user-instructions_2308398006.webp)
After these requirements are confirmed, the valve can be installed and connected in the piping.
Table 2: Line flange bolting specifications
Valve
size
Pressure
rating
MaxFlo 4 flanged
MaxFlo 4
flangeless
Size X length Qty Size X length
Qty
1’’
DN25
ANSI 150
1/2 X 2.62
8
1/2 X 6.75
4
ANSI 300
5/8 X 3.12
8
5/8 X 6.88
4
ANSI 600
5/8 X 3.50
8
5/8 X 7.12
4
PN 16
M12 X 70
8
M12 X 175
4
PN 40
M12 X 70
8
M12 X 175
4
PN 63
M16 X 110
8
M16 X 210
4
1½’’
DN40
ANSI 150
1/2 X 2.88
8
1/2 X 7.50
4
ANSI 300
3/4 X 3.62
8
3/4 X 8.38
4
ANSI 600
3/4 X 4.25
8
3/4 X 8.75
4
PN 16
M16 X 80
8
M16 X 200
4
PN 40
M16 X 80
8
M16 X 200
4
PN 63
M20 X 120
8
M20 X 235
4
2’’
DN50
ANSI 150
5/8 X 3.25
8
5/8 X 8.38
4
ANSI 300
5/8 X 3.50
16
5/8 X 3.50
4
5/8 X 8.50
6
ANSI 600
5/8 X 4.25
16
5/8 X 4.25
8
5/8 X 9.13
4
PN 16
M16 X 85
8
M16 X 215
4
PN 40
M16 X 85
8
M16 X 215
4
PN 63
M20 X 120
8
M20 X 245
4
3’’
DN80
ANSI 150
5/8 X 3.62
8
5/8 X 10.5
4
ANSI 300
3/4 X 4.25
16
3/4 X 4.25
4
3/4 X 11.00
6
ANSI 600
3/4 X 5.00
16
3/4 X 5.00
8
3/4 X 11.50
4
PN 16
M16 X 85
16
M16 X 85
6
M16 X 255
5
PN 40
M16 X 95
16
M16 X 95
6
M16 X 265
5
PN 63
M20 X 125
16
M20 X 125
8
M20 X290
4
4’’
DN100
ANSI 150
5/8 X 3.62
16
5/8 X 3.62
4
5/8 X 11.5
6
ANSI 300
3/4 X 4.50
16
3/4 X 4.50
4
3/4 X 12.25
6
ANSI 600
7/8 X 5.75
7/8 X 5.75
8
7/8 X 13.38
4
PN 16
M16 X 85
16
M16 X 85
6
M16 X 285
5
PN 40
M20 X 100
16
M20 X 100
6
M20 X 300
5
PN 63
M24 X 135
16
M24 X 135
8
M24 X 330
4
1. Remove the protective flange covers and coating from
the control valve; clean the flange gasket surface.
Unsuitable cleaning agents can dam-
age and cause leakage in PTFE and
graphite gaskets. Consult a current chemical resis-
tance list before applying.
2. Whenever possible the valve should be installed so that
actuator is in an upright position. Vertical installation of
the actuator permits easier valve maintenance.
3. Install and connect the control valve to the pipeline. Locate
gaskets in the center of the body flanges and secure nuts and
bolts. Use the bolts indicated in the Table 2 for installing the
valve in the pipeline, and then tighten alternately according
to good practice. The user must in all cases confirm the
capacity of the bolts to ensure a sufficiently tight gasket seal
for the expected service.
4. Connect the power supply and instrument signal lines.
• Connect the air supply and instrument signal lines.
Valve
size
Pressure
rating
MaxFlo 4 flanged
MaxFlo 4
flangeless
Size X length Qty Size X length
Qty
6’’
DN150
ANSI 150
3/4 X 3.75
16
3/4 X 3.75
4
3/4 X 13.25
6
ANSI 300
3/4 X 4.88
24
3/4 X 4.88
8
3/4 X 14.00
8
ANSI 600
1 X 6.75
24
1 X 6.75
8
1 X 15.75
8
PN 16
M20 X 100
16
M20 X 100
4
M20 X 335
6
PN 40
M24 X 115
16
M24 X 115
4
M24 X 350
6
PN 63
M30 X 160
16
M30 X 160
8
M30 X 390
4
8’’
DN200
ANSI 150
3/4 X 4.25
16
3/4 X 4.25
8
ANSI 300
7/8 X 5.50
24
7/8 X 5.50
4
7/8 X 15.19
10
ANSI 600
1 1/8 X 7.50
24
1 1/8 X 7.50
8
1 1/8 X 17.00
8
PN 16
M20 X 100
24
M20 X 100
8
M20 X 350
8
PN 40
M27 X 135
24
M27 X 135
8
M27 X 385
8
PN 63
M33 X 180
24
M33 X 180
8
M33 X 420
8
10’’
DN250
ANSI 150
7/8 X 4.62
24
ANSI 300
1 X 6.25
32
ANSI 600
1 1/4 X 8.50
32
PN 16
M24 X 110
24
PN 40
M30 X 150
24
PN 63
M33 X 185
24
12’’
DN300
ANSI 150
7/8 X 4.75
24
ANSI 300
1 1/8 X 6.75 32
ANSI 600
1 1/4 X 8.75
40
PN 16
M24 X 115
24
PN 40
M30 X 160
32
PN 63
M33 X 200
32
NOTICE
MaxFlo 4 Control Valve FCD VLENIM0064-02-AQ – 09/16
6