DANGER
Personnel working on pipes are exposed to
safety risks and may suffer severe injuries,
poisoning or even loss of life.
Make sure that no hot or hazardous
fluid is in the equipment or the pipes.
Make sure that the pipes upstream
and downstream of the equipment are
depressurised.
Make sure that the installation is
switched off and protected against
unauthorised or unintended activation.
Make sure that the equipment and the
pipes have cooled down to room
temperatures.
Wear protective clothing that is
suitable for the fluid and, if necessary,
wear protective gear.
For more information on suitable safety clothing and
safety gear refer to the safety data sheet of the fluid
in question.
Drain pipes until they are empty.
Switch the installation off and protect it against
unauthorised or unintended re-activation.
Connecting the equipment
DANGER
Incorrectly connected equipment can
cause fatal accidents or severe injuries.
Make sure that only qualified skilled
personnel connect the equipment to
pipes.
Make sure that the flow arrow on the
equipment body matches the direction
of flow in the pipe.
Specialist personnel must be highly qualified and
fully experienced in making pipe connections for the
respective type of end connection.
Attention!
Equipment will be damaged if the end
connections are undersized.
Make sure that the connections are
strong and rigid enough to support the
weight of the equipment and to
withstand the forces that occur during
operation.
Make sure that the pipe system of the plant is
clean.
Make sure that the equipment is free from
foreign matter.
Attention!
Damage due to steam leakage may occur
if the equipment is installed with the
handwheel upside down.
Install the equipment with the
handwheel on top.
Furthermore, if the equipment is installed with the
handwheel upside down, dirt can accumulate in the
bellows.
When mounting the equipment make sure that
the handwheel is on top!
Make sure that the flow arrow matches the
direction of the fluid flow in the pipe.
Contact the manufacturer if you want to mount
the equipment in a different position of
installation.
Connect the equipment to the pipes.
Make sure that the equipment is safely mounted