A. Fitting Selection:

Check the switch part number

to determine the required fitting mount size and
thread type. The switch is commonly installed in
tank adapters, flanges, brackets or stand pipes. 

1. Adapter:

Select a tank adapter fitting with

minimal height so as to ensure that the
installed transducer will not be substantially
elevated into the fitting. Avoid tank adapter
styles with threads and/or pipe stops forward
of the installed transducer. 

2. Flange:

Tall flanges with narrow risers

impede the acoustic signal. Select a fitting
with the right riser height versus inner diame-
ter geometry. The switch may be elevated up
to 12” (30 cm) in a 6” (15 cm) riser, 8” (20
cm) in a 4” (10 cm) riser and 3” (7.6 cm) in a
2” (5 cm) riser.

3. Bracket:

The LM50 bracket or equivalent can

be used for open tank top installations against
the side wall.

4. Stand Pipe:

A stand pipe may be

used to dampen turbulence or separate
surface foam. Select a 2” or larger
pipe for models LU75-5_ _ 5 and
LU72-5_ _ 5. Select a 3” or larger pipe
for models LU71-5_ _5 and LU73-5_
_5. The pipe length should run the
measurement span. Cut a 45° notch at
the bottom of the pipe and drill a 1/4”
pressure equalization hole high in the
dead band.

Step Thirteen

INSTALLATION

Adapter

VACUUM

Do not install at

angle relative 

to the liquid

Do not install with-

in 3” of 

tank side wall

Do not install 

with objects 

in the beam

Do not install 

in applications 

with vacuum 

Warning

Install the appropriate installation fitting. Make sure that
the fitting and switch threads are not damaged or worn.
Install the switch with the included Viton mounting gasket.
Hand tighten the switch within the fitting. Perform an
installed leak test under normal process conditions prior to
system start up.

Gasket

Flange

on Riser

Height

Inner Diameter

Riser

Bracket

Stand Pipe

Dead Band

Ventilation
Hole

Operational Range

Highest
Liquid Level

Lowest
Liquid Level

2"/3" Minimum
Diameter

Step Twelve

PROGRAMMING

12. Press the HIGH button for the first key-stroke and the Relay LED

will blink once. 

13. Press the HIGH button again for the second key-stroke and the

Relay LED will blink twice. 

14. The Power LED will flash from AMBER to GREEN when the set

point has been accepted into memory.

15. Press the SELECT switch repeatedly until BOTH LEDs for Relay

1 and Relay 2 are ON (after Relay 3).

16. Press the HIGH button for the first key-stroke and Relay LED will

blink once. 

17. Press the HIGH button again for the second key-stroke and Relay

LED will blink twice. 

18. Press SELECT to program the next relay channel or slide the

RUN/CAL switch RIGHT to exit the CAL mode.

Note: The duplexing mode can be disabled by repeating Steps #15-18
and pressing the LOW button instead of the HIGH button in the
HIGH/HIGH combination.

Programming Alternating Control Only:

1. To program the switch for alternating

control only without the lead-lag func-
tion, follow the instructions for
Programming Duplexing Pump Control
(Steps 11 and 12).  The difference
between Duplexing and Alternation is
the location of the Relay 2 set point.  Set
Relay 2 close to the deadband without
crossing into the deadband and above
the highest level of expected liquid.

Note: The alternation mode can be disabled
by repeating Steps #15-18 and pressing the
LOW button instead of the HIGH button in the HIGH/HIGH combi-
nation.

Duplex Programming

(Backup)

Box

Insert

Table

Target

Wall

Tape

Distance

Set Point

De-energize (All) Low

Energize

High

High High

Alternating

11

Alternating Programming

(Backup)

Box

Insert

Table

Target

Wall

Tape

Distance

Set Point

2

Programming Duplex Pump Control (continued):

Содержание EchoSwitch LU71

Страница 1: ...se of any product returned to Flowline where a There is evidence of a potentially hazardous material present with product b The product has remained unclaimed at Flowline for longer than 30 days after...

Страница 2: ...safety De energizes during echo signal loss Process temp F 4 to 140 C 20 to 60 Temp comp Automatic Electronics temp F 40 to 160 C 40 to 71 Pressure 30 psi 2 bar 25 C derated 1 667 psi 113 bar per C ab...

Страница 3: ...l Switch from FLOWLINE Please refer to the part number located on the switch label to verify the exact model configuration which you have purchased User s Responsibility for Safety FLOWLINE manufac tu...

Страница 4: ...nergize set point both relays will energize until the level reaches the de energize set point Alternation will automati cally fill or empty the tank with two pumps switching after each cycle PREPARATI...

Страница 5: ...olid you may either re pro gram the channel with new set points or leave it inactive PROGRAMMING Set Point Calibration Box Insert Table Target Wall Tape Distance Set Point Cal Run High Low Select Echo...

Страница 6: ...Low Level Out of Bounds Alarm Programming High Set Point Distance Low Set Point Distance Energize Energize De energize Out of Bounds D Programming Automatic Fill After having powered the switch with...

Страница 7: ...Eleven PROGRAMMING Programming Duplexing Pump Control After having pow ered the switch with the appropriate supply voltage entered the CAL mode selected relay channel 1 and erased any previously inpu...

Страница 8: ...process conditions prior to system start up Gasket Flange on Riser Height Inner Diameter Riser Bracket Stand Pipe Dead Band Ventilation Hole Operational Range Highest Liquid Level Lowest Liquid Level...

Страница 9: ...acoustic signal strength Read the Maximum Applied Range Step 4 E and consider rein stalling the switch in a Stand Pipe Step 11 A 4 to dampen turbulence and or separate the point of measurement from s...

Страница 10: ...ackup Primary Stop Duplexing Control Operation Alternating Control Operation OPERATION Step Sixteen Relay X Energize De Energize Start Stop Automatic Empty Operation Automatic Fill Operation Out of Bo...

Отзывы: