INTRODUCTION

TECHNOLOGY

Step Three

A. Application:

The general purpose ultrasonic switch provides

non-contact level detection up to 26’ or 8m with 3 relays. Each relay
can be configured on a single set point alarm, two latched set points
for automatic fill or empty, two set points for out of bounds alarms or
three set point (relays 1 and 2 only) alternation / duplexing . The
switch is well suited for a wide range of corrosive, waste and slurry
type media, and is broadly selected for atmospheric day tank, pump
lift station and waste sump applications. 

B. Part Number:

The part and serial numbers are located on the

wrench flat. Check the part number on the product label and confirm
which of the below model configurations you have purchased:

Part Number

Range

Supply

Mount

LU75-5005

4’ (1.2m)

95-250 VAC

1” NPT

LU75-5065

4’ (1.2m)

95-250 VAC

1” G

LU75-5805

4’ (1.2m)

12-28 VDC

1” NPT

LU75-5865

4’ (1.2m)

12-28 VDC

1” G

LU72-5005

9.8’ (3m)

95-250 VAC

1” NPT

LU72-5065

9.8’ (3m)

95-250 VAC

1” G

LU72-5805

9.8’ (3m)

12-28 VDC

1” NPT

LU72-5865

9.8’ (3m)

12-28 VDC

1” G

LU71-5005

16.4’ (5m)

95-250 VAC

1” NPT

LU71-5065

16.4’ (5m)

95-250 VAC

1” G

LU71-5805

16.4’ (5m)

12-28 VDC

1” NPT

LU71-5865

16.4’ (5m)

12-28 VDC

1” G

LU73-5005

26.2’ (8m)

95-250 VAC

2” NPT

LU73-5065

26.2’ (8m)

95-250 VAC

2” G

LU73-5805

26.2’ (8m)

12-28 VDC

2” NPT

LU73-5865

26.2’ (8m)

12-28 VDC

2” G

C. NEMA 4X Enclosure:

The enclosure has a flip cover with two

1/2” NPT female conduit ports and an internal terminal strip for

wiring. To open the enclosure, you will need a small insertion tool

such as a screwdriver. Insert the tool into the hole located at the

front of the enclosure and gently push on the latching mechanism

to release the cover. Rotate the hinged cover up for 135° access to

the faceplate and terminal strips. Before closing the enclosure,

make sure that the enclosure gasket is properly seated, and

that any conduit fittings, cable connectors or plugs are

installed correctly and sealed.

Step Two

About this Manual: 

PLEASE READ THE ENTIRE MANU-

AL PRIOR TO INSTALLING OR USING THIS PRODUCT.  This

manual includes information on the LU7_-5_ _5 Ultrasonic Level

Switch from FLOWLINE. Please refer to the part number located

on the switch label to verify the exact model configuration which

you have purchased.

User’s Responsibility for Safety: 

FLOWLINE manufac-

tures a broad range of level sensing technologies. While each of

these sensors is designed to operate in a wide variety of applica-

tions, it is the user’s responsibility to select a sensor model that is

appropriate for the application, install it properly, perform tests of

the installed system, and maintain all components. The failure to do

so could result in property damage or serious injury. 

Proper Installation and Handling: 

Only properly trained

staff should install and/or repair this product. Install the switch with

the included Viton gasket and never overtighten the switch within

the fitting. Always check for leaks prior to system start-up.

Wiring and Electrical: 

A supply voltage of 95-250 VAC is

used to power the LU7_-50 _5 switch, and a supply voltage of 12-

28 VDC is used to power the LU7_-58_5 switch. Electrical wiring

of the switch should be performed in accordance with all applica-

ble national, state, and local codes. 

Material Compatibility: 

The LU7_-5_ _5 enclosure is made

of a flame retardant Polycarbonate (PC/ABS FR). The transducer is

made of Polyvinylidene Fluoride (PVDF). Make sure that the

model which you have selected is chemically compatible with the

application media.

Enclosure: 

While the switch housing is liquid-resistant the

LU7_-5 _ _5 is not designed to be operational when immersed. It

should be mounted in such a way that the enclosure and transduc-

er do not come into contact with the application media under nor-

mal operational conditions.

Make a Fail-Safe System: 

Design a fail-safe system that

accommodates the possibility of switch and/or power failure.

FLOWLINE recommends the use of redundant backup systems

and alarms in addition to the primary system.

Flammable, Explosive or Hazardous Applications:

The LU7_-5_ _5 should not be used within classified hazardous

environments. 

Warning

Always use the Viton gasket when installing the LU7_-5_ _5
switch, and make sure that all electrical wiring of the switch
is in accordance with applicable codes.

LU7_-5_ _1

Shown

RELAY

1

RELAY

2

RELAY

3

L

1

 L

2

POWER

Cal.           Run

High

Low

Select

EchoSwitch

Содержание EchoSwitch LU71

Страница 1: ...se of any product returned to Flowline where a There is evidence of a potentially hazardous material present with product b The product has remained unclaimed at Flowline for longer than 30 days after...

Страница 2: ...safety De energizes during echo signal loss Process temp F 4 to 140 C 20 to 60 Temp comp Automatic Electronics temp F 40 to 160 C 40 to 71 Pressure 30 psi 2 bar 25 C derated 1 667 psi 113 bar per C ab...

Страница 3: ...l Switch from FLOWLINE Please refer to the part number located on the switch label to verify the exact model configuration which you have purchased User s Responsibility for Safety FLOWLINE manufac tu...

Страница 4: ...nergize set point both relays will energize until the level reaches the de energize set point Alternation will automati cally fill or empty the tank with two pumps switching after each cycle PREPARATI...

Страница 5: ...olid you may either re pro gram the channel with new set points or leave it inactive PROGRAMMING Set Point Calibration Box Insert Table Target Wall Tape Distance Set Point Cal Run High Low Select Echo...

Страница 6: ...Low Level Out of Bounds Alarm Programming High Set Point Distance Low Set Point Distance Energize Energize De energize Out of Bounds D Programming Automatic Fill After having powered the switch with...

Страница 7: ...Eleven PROGRAMMING Programming Duplexing Pump Control After having pow ered the switch with the appropriate supply voltage entered the CAL mode selected relay channel 1 and erased any previously inpu...

Страница 8: ...process conditions prior to system start up Gasket Flange on Riser Height Inner Diameter Riser Bracket Stand Pipe Dead Band Ventilation Hole Operational Range Highest Liquid Level Lowest Liquid Level...

Страница 9: ...acoustic signal strength Read the Maximum Applied Range Step 4 E and consider rein stalling the switch in a Stand Pipe Step 11 A 4 to dampen turbulence and or separate the point of measurement from s...

Страница 10: ...ackup Primary Stop Duplexing Control Operation Alternating Control Operation OPERATION Step Sixteen Relay X Energize De Energize Start Stop Automatic Empty Operation Automatic Fill Operation Out of Bo...