INSTALLATION (continued)
Step Seven
Fitting Selection:
Check the part number to determine the required fitting mount size and thread type.
EchoSonic® II is commonly installed in tank adapters, flanges, brackets or standpipes
.
Note:
Always include
the gasket when installing the EchoSonic® II.
1.
Tank Adapter:
Select a tank adapter fitting, such as the LM52‐1890 for the LU27 series or the LM52‐
2890 for the LU23, LU28 & LU29 series.
a.
For best results, select a 2” tank adapter and add a reducer bushing such as the LM52‐1400,
thread x thread, reducer bushing.
b.
Avoid tank adapter (thread x thread) styles and/or pipe stops forward of the installed
transducer.
c.
Always mount the tank adapter so the majority of fitting is outside the tank.
i.
Note:
Never mount the tank adapter upside down or where the bulk of the material is
inside the tank.
2” Tank Adapter
Slip x Thread
(LM52‐2890)
Tank Adapter
w/ 2” x 1” Reducer Bushing
LM52‐2890 w/LM52‐1800)
Tank Adapter
Thread x Thread
Do not use thread x thread
2.
Riser:
Installations with tall, narrow risers can impede the acoustic signal.
a.
Core‐Out Concrete:
Applications where tank with a concrete ceiling that has been cored out
can also be considered as a riser type application. In these applications follow a 2:1 ratio (Inner
Diameter to Core Height) for the diameter of the core.
a.
LU23, LU28 & LU29 Series:
2” (5 cm) diameter risers should be no taller than 4” (10 cm). Larger
diameter risers should be no taller than 12” (30.5 cm).
b.
LU27 Series:
Riser Specifications
Inner
Diameter
Maximum
Height
2” (5cm)
4” (10cm)
6” (15cm)
4” (10cm)
8” (20cm)
12” (30cm)
Note:
Do not exceed the dimensions listed above.
Note:
If attempting to raise the
sensor above the top of the tank
to allow for a higher fill capacity,
avoid the use of tall and narrow
risers. The example to the left
exceeds the dimensions listed in
the
Riser Specifications
chart.
Use a larger tank adapter which
takes into account the
Riser
Specifications
.