FlowLine EchoPod UG01-03 Скачать руководство пользователя страница 29

 

MN310140 Rev A2 

29   

|

 

Installation 

(continued)

 

Step Five 

  

 

FITTING SELECTION 

Check the part number to determine the required fitting mount size and thread type.  EchoPod

®

 is commonly 

installed in tank adapters, flanges, brackets or standpipes.  

Note: Always include the gasket when installing 

the “G” threaded EchoPod

®

 

1. 

Tank Adapter:

  Select a tank adapter fitting, such as the LM52-2890 tank adapter for 2” sensors or the 

LM52-3890 for 3” sensors.   

a. 

For best results, select a 3” tank adapter and add a reducer bushing such as the LM52-2400, 
thread x thread, reducer bushing.

   

b.  Avoid tank adapter (thread x thread) styles and/or pipe stops forward of the installed transducer. 
c.  Always mount the tank adapter so the majority of fitting is outside the tank. 

i. Note: Never mount the tank adapter upside down or where the bulk of the material is 

inside the tank. 

2” Tank Adapter 
Socket x Thread 

(LM52-2890) 

Tank Adapter 

w/ 3”x2” Reducer Bushing 

(LM52-3890 w/LM52-2400) 

Tank Adapter 

Thread x Thread 

 

 

 

Do not use thread x thread 

2. 

Riser: 

 Installations with tall, narrow risers can impede the acoustic signal.  

a. 

Core Out Concrete:

  Applications where a tank with a concrete ceiling that has been cored out 

can also be considered as a riser type application.  In these applications follow a 2:1 ratio (Inner 
Diameter to Core Height) for the diameter of the core. 

a.  2” (5 cm) diameter risers should be no taller than 4” (10.0 cm).  Larger diameter risers should be 

no taller than 12” (30.5 cm).                  

 

Riser Specifications 

Inner 

Diameter 

Maximum 

Height 

2” (5cm) 

4” (10cm) 

6” (15cm) 

4” (10cm) 

8” (20cm) 

12” (30cm) 

Note: Do not exceed the dimensions listed above. 

 

 

Note: If attempting to raise the 
sensor above the top of the tank 
to allow for a higher fill capacity, 
avoid the use of tall and narrow 
risers.  The example to the left 
exceeds the dimensions listed in 
the  Riser Specifications chart.  
Use a larger tank adapter which 
takes into account the Riser 
Specifications
.  

 

 

Содержание EchoPod UG01-03

Страница 1: ...Flowline Inc 10500 Humbolt Street Los Alamitos CA 90720 p 562 598 3015 f 562 431 8507 w flowline com MN310140 Rev A2 UG06 UG12 Series Manual EchoPod Ultrasonic Level Transmitter...

Страница 2: ...TABLE OF CONTENTS Introduction 2 Specifications 4 Dimensions 5 Reflective Technology 6 About this manual 7 Getting Started 8 Setup Overview 8 Components 9 WebCal vs Display Configuration 10 Understand...

Страница 3: ...ys Controllers PLCs 35 36 Voltage Output 37 WebCal Appendix 38 Sensor Configuration 38 39 Volumetric Configuration 40 42 Tank Level Confirmation 43 Write to Unit 44 Display Appendix 45 Air Gap vs Liqu...

Страница 4: ...PVDF with Viton A gasket Process Mount UG06 2 NPT or 2 G UG12 3 NPT or 3 G Gasket Viton A G thread only Electrical Connections Power Return 2 pin removable terminal block Display Connect 4 pin removab...

Страница 5: ...MN310140 Rev A2 5 Introduction continued Step One DIMENSIONS Dimensions for UG06 Series Dimensions for UG12 Series...

Страница 6: ...reducing their measurement reliability At the core of Reflective Technology is a simple fact Unlike flat horizontal surfaces significant water droplets cannot adhere to smooth vertical surfaces By ori...

Страница 7: ...selected is chemically compatible with the application media Enclosure While the sensor housing is liquid resistant the EchoPod is not designed to be operational when immersed It should be mounted in...

Страница 8: ...ontains information on using the WebCal configuration software 4 Configure Sensor with Push Button Section Four a Section 4 contains information on using the Push Button Display to configure the senso...

Страница 9: ...0001 00 19 7 6m 8 20cm 2 NPT Not Included 4 20 mA Display with Push Button or WebCal UG06 0001 01 Included UG06 0011 00 2 G Not Included UG06 0011 01 Included UG12 0001 00 39 4 12m 18 45 7cm 2 NPT No...

Страница 10: ...can be configured before installation or after installation The transmitter features non volatile memory so any settings configured before installation will not be lost when the sensor is powered down...

Страница 11: ...of the tank and any risers fittings structures or extensions associated with the tank or the installation see examples below The reference point for definition of the Sensor Height is always the botto...

Страница 12: ...e top of the tank Note The ratio of height to diameter of the riser must be no greater than 2 1 Any higher and the sensor will target the inside wall of the riser Example 2 Dome Top Tanks Tank C has a...

Страница 13: ...lation of the sensor Be sure to understand the geometry directly underneath the sensor Cone or rounded bottom tanks will provide off angled surfaces that can reflect the ultrasonic sound energy away f...

Страница 14: ...units i e inches feet gallons meters liters etc Tank A Tank B Tank C In the Tank A example the Sensor Height sets the 4mA to the bottom of the tank Fill Height sets the 20mA to the top of the straigh...

Страница 15: ...measurement 3 Sensor Configuration a Configures Loop Fail Safe Output at Empty Startup Condition for the sensor 4 Dimensional Entry a Distance Mode default i Basic information for operation Sensor He...

Страница 16: ...download and install WebCal prior to plugging in the USB Fob LI99 2001 Please go to flowline com webcal software and select your language version WEBCAL SYSTEM REQUIREMENTS Windows 2000 XP Vista 7 8 1...

Страница 17: ...The maximum cable distance between the computer and EchoPod is 15 This only applies for configuring the EchoPod Once EchoPod is configured and prior to installation isolate the white and green termin...

Страница 18: ...er hand sensors installed in risers nozzles will result in a higher HEIGHT value The basic measurements Height and Fill H for configuration are described below 1 HEIGHT Sensor Height Distance from the...

Страница 19: ...the WebCal manual located at flowline com webcal software STEP 3 SENSOR CONFIGURATION Configures the Loop Fail Safe Output at Empty and Startup Condition for the sensor Note When connecting the senso...

Страница 20: ...uts refer to VOLUMETRIC CONFIGURATION on page 40 The two values Sensor Height and Fill Height below set the 4 20 mA current span for the sensor Both values will be set in the units shown under Height...

Страница 21: ...EP 6 WRITE TO UNIT This WebCal operation uploads configuration into the sensor Other features in the section include providing a custom wiring diagram specific to the signal output and saving the conf...

Страница 22: ...eering units of length including Feet Inches Centimeters or Meters 3 Set the Sensor Height HEIGHT a This is the empty setting 4mA for the tank 4 Set the Fill Height FILL H a This is the full setting 2...

Страница 23: ...er hand sensors installed in risers nozzles will result in a higher HEIGHT value The basic measurements Height and Fill H for configuration are described below 1 HEIGHT Sensor Height Distance from the...

Страница 24: ...display 3 Use OK to choose a MENU item How to exit the TOP LEVEL MENU In TOP LEVEL MENU press OK when RUN appears STEP 2 SETTING THE UNITS OF MEASUREMENT UNITS 1 In the TOP LEVEL MENU mode select UNI...

Страница 25: ...to the bottom of the tank 4 To enter the value press and hold OK for 5 seconds and release SAVED will display 5 Select EXIT to return to TOP LEVEL MENU Note The HEIGHT setting also determines the 4 m...

Страница 26: ...quid to the bottom of the tank 4 To enter the value press and hold OK for 5 seconds and release SAVED will display 5 Select EXIT to return to TOP LEVEL MENU Note The Fill Height FILL H setting determi...

Страница 27: ...urrent Output or LOST setting can be set to output a current of 4mA 20mA 21mA 22mA or Hold last known value During fail safe the display will read LOST 2 In TOP LEVEL MENU mode select OUTPUT 3 Select...

Страница 28: ...3 from the side wall 4 Do not mount where obstacles will intrude on sensor s beam width a mount at least 3 from the side wall 5 Do not mount in a vacuum 6 Do not mount in the center of a dome top tan...

Страница 29: ...Adapter Socket x Thread LM52 2890 Tank Adapter w 3 x2 Reducer Bushing LM52 3890 w LM52 2400 Tank Adapter Thread x Thread Do not use thread x thread 2 Riser Installations with tall narrow risers can im...

Страница 30: ...to 2 reducer bushing to complete the installation 2 Flange LM52 2850 3 Flange w Reducer Bushing LM52 3800 4 Side Mount Bracket For installations in open tanks and sumps use the LM50 1001 series side...

Страница 31: ...m of the pipe should remain submerged at all times to prevent foam from entering the pipe e Cut a 45 notch at the bottom of the pipe Drill a 1 4 pressure equalization hole in the dead band f The pumps...

Страница 32: ...h WebCal and use the wiring diagram button to view the appropriate diagram Each configuration will have its own unique diagram The diagram shown above is only a sample and should not be used as a wiri...

Страница 33: ...ies GENERAL NOTES FOR ELECTRICAL CONNECTIONS USAGE AND SAFETY Where personal safety or significant property damage can occur due to a spill the installation must have a redundant backup safety system...

Страница 34: ...al with a sampling resistor as shown in the following diagram The cabling should be a shielded twisted pair to minimize EMI interference Typically 20 to 24 gauge wire is used in this application To ac...

Страница 35: ...Below is a quick review of wiring the EchoPod to common display controllers and PLC s DataView LI55 Series Level Controller Commander LI90 Series Multi Tank Level Controller DataLoop LI23 Series Level...

Страница 36: ...CONTINUED DataPoint LC52 Series Level Controller JWA mode Factory Setting DataPoint LC52 Series Level Controller JWB mode Generic Loop Powered Display Generic PLC Refer to the DataPoint LC52 Series Le...

Страница 37: ...to 5 VDC or 0 to 10 VDC output A resistor will need to be added to the circuit to enable a voltage output refer to the wiring diagram below 0 5 VDC output o Add a 250 Ohm resistor o Actual output wil...

Страница 38: ...sensor will output 20 mA during a fail safe condition Full The output will revert to the current value for a full condition When 4 mA at Bottom is selected the sensor will output 20 mA during a fail...

Страница 39: ...output will revert to the selected current value for an empty condition o 4 mA at Bottom The sensor will output 4 mA while the sensor powers up o 20 mA at Bottom The sensor will output 20 mA while the...

Страница 40: ...not the height of the tank This means that the current output will track the volume of the tank in gallons or liters Depending on the shape of the tank the values may be a linear or non linear scale...

Страница 41: ...ts as Distance or Volume After choosing the Sensor Output Units select the units of measurement in the pull down to the left Units of Measurement Distance Volume Inches Cm Feet Meters Gallons Liters D...

Страница 42: ...e tank to the top of the straight side wall Diameter Distance of the inside tank diameter Volume Tank Capacity Vertical Cylinder Example After entering the dimensions press the Capacity button to show...

Страница 43: ...to the bottom of the sensor Fill Height Distance from the bottom of the tank to the operational full level of liquid 20mA This setting defines the location of full current output and is the top of th...

Страница 44: ...ature setting designed to help solve performance or operational issues for specific applications Changing these setting will alter the factory default performance or operation of your sensor Increase...

Страница 45: ...the tank LIQUID mode or the amount of air in the tank AIR mode This function does not influence the current output just the display on the sensor 1 In TOP LEVEL MENU mode select DISPLAY 2 Select LIQUI...

Страница 46: ...top then use the REV MA setting to reverse the current output With REV MA set to NORM factory default 4mA will be at the bottom and 20 mA at the top of the tank With REV MA set to REV 20mA will be at...

Страница 47: ...quires the level reading the output current can be preset in order to avoid any false alarms during this window The options for start up are 4mA 12mA 20mA or 22mA 1 In TOP LEVEL MENU mode select OUTPU...

Страница 48: ...lect SETUP 3 Setup will list the following information a HEIGHT b FILL H 4 Select EXIT to return to TOP LEVEL MENU DIAGNOSTIC DIAG PARAMETERS This mode runs diagnostic tests that confirm operation of...

Страница 49: ...Eight RESET EchoPod enables the end user to reset the entire configuration back to the original factory settings 1 In TOP LEVEL MENU mode select VALUES 2 Select RESET 3 Select YES a To cancel the rese...

Страница 50: ...d Green are securely attached to the Fob Check Device Manager and confirm that both drivers WebCal Configuration EchoFob are present If the above do not work reinstall the WebCal software while the co...

Страница 51: ...0 mA Check the wiring for an open circuit An open circuit is the most common issue with a 0 mA signal Transmitter jumps to a current reading between 19 and 20 mA Check the installation of the transmi...

Страница 52: ...edures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personne...

Отзывы: