Getting Started
(continued)
Step Two
WEBCAL
®
VS. DISPLAY CONFIGURATION
EchoPod
®
can be configured using either the free WebCal
®
software and USB
®
Fob or with the internal display
module. Either method will accomplish the goal of sensor configuration. Changes to the configuration can be
made using the alternative method. Upon implementing one methodology, it is recommended to complete the
configuration before using the other methodology in making any adjustments.
EchoPod
®
can be configured before installation or after installation. The transmitter features non-volatile
memory, so any settings configured before installation will not be lost when the sensor is powered down. To
start, the following information is required:
Basic Tank Information
o
HEIGHT
(Sensor Height) – Distance from
the bottom of the tank to the bottom of the
sensor.
o
FILL-H
(Fill-Height) – Distance from the
bottom of the tank to the fill-height of the
liquid.
Power:
o
Provide input power to the EchoPod
®
Note: The HEIGHT and Fill-Height (FILL-H) settings also determine the 4 to 20 mA current span. The
HEIGHT setting determines the 4mA position and the FILL-H setting determines the 20 mA position.