FlowLine EchoPod DX10 Series Скачать руководство пользователя страница 5

 

We do Your Level Best

 

We do Your Level Best

 

Configuration Settings 

 

 

 

 

 

Mounting the EchoPod

®

 

The EchoPod

®

 should always be mounted perpendicular to the liquid surface and 

installed using the provided Viton

®

 mounting gasket. Always use  fittings, with thin 

wall mounting structures that isolate the transducer. This will provide the best 

performance over the lifetime of the product. 

The preferred mounting fitting for the EchoPod

®

 DX10 is the Reducer Bushing LM52-

1400 (2” thread x 1” thread). Further mounting products and solutions can be found 

on the Flowline website at  

www.flowline.com/fittings.php

. An instructional video on 

mounting ultrasonic level measurement technology is also available on the website. 

For installations in existing 2” fittings: 

1)  Use LM52-1400 2” thread x 1” thread adapter (An 

adapter with an air gap around the 1 inch threads as 
shown is recommended). 

For installations in plastic tanks: 

1)  Use a Bulkhead fitting LM52-1890 1” Bulkhead fitting, 

2)  Use a Bulkhead fitting LM52-2890 in combination with 

LM52-1400 or, 

3)  Weld a plastic 1” half coupler to tank top. 

 

For installations in metal tanks: 

1)  Use the recommended bulkhead fittings as shown 

above or a LM52-1850 1” Flange.  The flange fitting 

must have a riser for the threaded section. Drilling and 

tapping a blind flange is not recommended.   

2)  While installations directly into a 1”metal fitting are not 

 recommended, acceptable results may be obtained if 

 the 1” fitting is a half coupling in form and the outer 

diameter of the coupler is tightly wrapped in vinyl tape  

to dampen vibrations.  

 

For installations in open tanks and sumps: 

1)  Use Flowline's LM50-1001-1 side mount bracket, 

which includes a 2" x 1" thread reducer bushing. 

Using the drop-down menus on the left of the WebCal screen, set the configuration 

for your application requirements. When a selection does not apply to your 

application, “Not Applicable” will appear in the drop-down. Make sure all drop-downs 
are set appropriately for your application before moving to the Tank Level section. 

 

 

 

 

 

 

 

 

 

NOTE

: If you would like to start over, click the                                                                           

Clear Screen

 button on the right. 

 

Enter the appropriate tank level set points for your application. 

 

 

 

 

 

 

 

 

Tank Level Settings 

 

Units

. Display measurements in inches 

or centimeters. 

 

Sensor Height

. Distance measured from 

the bottom of the empty tank to the 

bottom of the transducer. Under factory 

configuration, this becomes the 4 mA set 

point. 

 

Fill Height

. Distance measured from the 

bottom of the empty tank to the maximum 

fill height within the tank. Under factory 

configuration, this becomes the 20 mA 

set point. 

 

 

 

Select Output

. The Output can be 

displayed in terms of either Voltage or 

Frequency. As shown later in the Wiring 

section, this relates to the connections 

through the blue and brown wires. 

 

Maximum Output 

and

 Minimum 

Output

. Sets the tank full and tank empty 

output levels, respectively. 

 

Fail Safe Output

. Use this setting to 

choose the output level when the sensor 

loses the echo return. 

 

Startup Condition

. During the 15-20 

seconds during which the EchoPod starts 

up, this describes the level at which it will 

begin searching for the contents of the 

tank

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Содержание EchoPod DX10 Series

Страница 1: ...ligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Flowline have attempted to repair 5 have been involved in accidents or natural disasters or 6 are damaged during return shipment to Flowline Flowline reserves the right to unilaterally waive this warranty and dispose of any product returned to Flowline where 1 there is evidence of a potentially hazardous...

Страница 2: ...llation must have a redundant backup safety system installed Wiring should always be completed by a licensed electrician Supply voltage should never exceed 28 VDC Protect the sensor from excessive electrical spikes by isolating the power whenever possible The sensor materials must be chemically compatible with the liquids to be measured Design a fail safe system for possible sensor and or power fa...

Страница 3: ...your EchoPod should be performed prior to mounting since it requires connection to your PC Step 1 Install the WebCal Software Download WebCal from www flowline com onto a PC with the following minimum specifications Windows 2000 XP Vista 7 10 MB storage space 256 MB RAM 1 USB 2 0 port Double click the WebCal icon to install before proceeding to Step 2 You must have an active Internet connection to...

Страница 4: ...y vapor Select a 3 pipe a 2 pipe is usable but the minimum and attach the EchoPod with a coupling and reducer bushing The pipe length should run the measurement span and the bottom of the pipe should remain submerged at all times to prevent foam from entering the pipe Cut the bottom end of the pipe at 45 and drill a 1 4 pressure equalization hole high in the dead band The pumps should not drive li...

Страница 5: ... vinyl tape to dampen vibrations For installations in open tanks and sumps 1 Use Flowline s LM50 1001 1 side mount bracket which includes a 2 x 1 thread reducer bushing Using the drop down menus on the left of the WebCal screen set the configuration for your application requirements When a selection does not apply to your application Not Applicable will appear in the drop down Make sure all drop d...

Страница 6: ...guration file and click Save Config File Configuration is now complete Disconnect the USB Fob before continuing to the next step Mounting the EchoPod For updates to WebCal or to make sure you re using the most up to date version available click the Update tab on the top of the WebCal screen Write to Unit Send your configuration into EchoPod Wiring Diagram Open PDF wiring schematic of your configur...

Отзывы: