FlowLine AU23-4313 Скачать руководство пользователя страница 9

 

LM900006 Rev 0_3 

 9 

 

 

|

 

Getting Started (continued)

 Step 

Four 

  

 

GUIDE TO CONTROLS:

  

 
Below is a listing and the location of the different components for the controller: 

Standard Version (Non-CE) 
 

 

CE Version (ex. AZ23-4223-CE) 
 

 

 

1. 

Power indicator:

  This green LED lights when AC power is ON.   

2. 

Relay indicator:

  This red LED will light whenever the controller energizes the relay, in response to the 

proper condition at the sensor input(s) and after the time delay.   

3. 

AC Power terminals:

  Connection of 120 VAC power to the controller.  The setting may be changed to 

240 VAC if desired.  This requires changing internal jumpers; this is covered in the Installation section 
of the manual. Polarity (neutral and hot) does not matter. 

4. 

Relay terminals (NC, C, NO):

  Connect the device you wish to control (pump, alarm etc.) to these 

terminals: supply to the COM terminal, and the device to the NO or NC terminal as required.  The 
switched device should be a non inductive load of not more than 16 amps; for reactive loads the current 
must be derated or protection circuits used.  When the red LED is ON and the relay is in the energized 
state, the NO terminal will be closed and the NC terminal will be open. 

5. 

Invert switch:

  This DIP switch reverses the logic of the relay control in response to the sensor(s): 

conditions that used to energize the relay will make it turn off and vice versa. 

6. 

Latch switch:

  This DIP switch determines how the relay will be energized in response to the two 

sensor inputs.  When LATCH is OFF, the relay responds to sensor Input 1A only; when LATCH is ON, 
the relay will energize or de-energize only when both sensors (1Aand 1B) are in the same condition 
(wet or dry).  The relay will remain latched until both sensors change states.   

7. 

Time Delay:

  After the input(s) change(s) state, this control sets a delay from 0.15 to 60 seconds 

before the relay will respond.  

8. 

Input 1Aand 1B indicator:

  These amber LEDs will light immediately whenever the appropriate sensor 

attached to the terminals detects liquid, and will turn off when it is dry. 

9. Input 

terminals:

  Connect the wiring from the sensors to these terminals: A to the upper pair, B (LC11 

Series only) to the lower pair.  Note the polarity:  (+) is a 13.5 VDC, 27 mA power supply (to be 
connected to the red wire of a Flowline sensor), and (-) is the return path from the sensor (to be 
connected to the black wire of a Flowline sensor). If polarity is reversed, the sensors will not work.

 

 

 

Содержание AU23-4313

Страница 1: ...Flowline Inc 10500 Humbolt Street Los Alamitos CA 90720 p 562 598 3015 f 562 431 8507 w flowline com MN301410 Rev A Smart Trak With Compact Relay Controller AU23 AV23 AZ23 Series Manual ...

Страница 2: ...nsing technologies for broad application coverage ultrasonic vibration buoyancy Polypropylene enclosure rated NEMA 4X with swivel base for conduit alignment Easy setup with LED indicators for sensor s power and relay status Invert switch changes relay state from NO to NC without rewiring AC powered TABLE OF CONTENTS Specifications Dimensions 3 Parts Included 4 Configurations 5 Safety Precautions 6...

Страница 3: ... 80 Electronics temp F 40 to 158 C 40 to 70 Pressure Atmospheric Wetted material PP 20 glass filled Enclosure rating NEMA 4X IP65 Enclosure material PP U L 94 VO Process mount 2 NPT 2 G Enclosure rotation 300 swivel base Conduit entrance Single 1 2 NPT Installed height 5 7 14 4cm 7 4 18 8cm with strobe Classification General purpose Certificate number LR 79326 3 CE compliance EN 61326 EMC EN 61010...

Страница 4: ...iption AU23 4313 Add E Add CE NPT No Dual Level Switches Ultrasonic Gap Switch Technology AU23 4317 G AU23 4323 N A NPT Yes AU23 4327 G AV23 4313 Add CE NPT No Dual Level Switches Buoyancy Vertical Float Technology AV23 4317 G No AV23 4323 N A NPT Yes AV23 4327 G Yes AZ23 4313 Add CE NPT No Dual Level Switches Vibration Tuning Fork Technology Az23 4317 G No AZ23 4323 N A NPT Yes AZ23 4327 G Yes Ow...

Страница 5: ... x LM30 1001 1 x LC11 1051 STANDARD CONFIGURATION AU23 432_ AV23 432_ or AZ23 432_ Ultrasonic Buoyancy Vibration AU23 4323 2 x LU10 1305 1 x LM10 1_01 2 x LM30 1001 1 x LC11 1002 AU23 4327 2 x LU10 1305 1 x LM10 1_61 2 x LM30 1001 1 x LC11 1052 AV23 4323 2 x LV10 1301 1 x LM10 1_01 2 x LM30 1001 1 x LC11 1002 AV23 4327 2 x LV10 1301 1 x LM10 1_61 2 x LM30 1001 1 x LC11 1052 AZ23 4323 2 x LZ12 1405...

Страница 6: ...ession fitting thrust plate locking pin and 2 NPT fitting o Viton a fluorocarbon O ring o Neoprene w silicon gel for lubrication Wire gasket o Santoprene w silicon gel for lubrication Seal plug Make sure that the application liquids are compatible with the materials that will be wetted To determine the chemical compatibility between the components and its application liquids refer to the Compass C...

Страница 7: ...e controller that carry high voltage causing serious injury or death All power to the controller and the relay circuit s it controls should be turned OFF prior to working on the Smart Trak If it is necessary to make adjustments during powered operation use extreme caution and use only insulated tools Making adjustments to powered controllers is not recommended Wiring should be performed by qualifi...

Страница 8: ...o 60 seconds can be set delay occurs on both the make and break Typical applications are automatic filling starting fill pump at a low level and stopping pump at a high level or automatic emptying operations opening a drain valve at a high level and closing valve at low level FEATURES OF CONTROL LATCH OFF With the latch OFF the Smart Trak package is designed to receive a signal from a single liqui...

Страница 9: ...e the NO terminal will be closed and the NC terminal will be open 5 Invert switch This DIP switch reverses the logic of the relay control in response to the sensor s conditions that used to energize the relay will make it turn off and vice versa 6 Latch switch This DIP switch determines how the relay will be energized in response to the two sensor inputs When LATCH is OFF the relay responds to sen...

Страница 10: ...mpty In this application a pump or valve can be wired to either the Normally Open NO or Normally Closed NC side of the relay In the example below power to the Smart Trak is not shown STROBE ALERT OUTPUT The Smart Trak features a latching controller primarily designed for automatic filling or emptying of a tank or sump If the Strobe Alert was added to your package it can be wired to either indicate...

Страница 11: ...d turn OFF Latch In any two sensor control system LATCH must be ON Invert Referring to the logic chart in Step Nine we look for the setting that will de energize the relay start the pump when both inputs are wet Amber LEDs In this system Invert should be ON AUTOMATIC EMPTY Note that similar system logic can be used for an automatic empty operation simply by controlling a pump valve that takes flui...

Страница 12: ...T 1B are in the same condition The relay will not change its condition until both inputs reverse their state Invert Off Latch ON Input 1A Input 1B Relay ON OFF ON OFF ON ON OFF OFF ON No Change No Change OFF Invert ON Latch ON Input 1A Input 1B Relay ON OFF ON OFF ON ON OFF OFF OFF No Change No Change ON The example shown below has the Invert Off and the Latch ON With Invert ON follow the above le...

Страница 13: ...ors and also serve to contain the switch cable The bottom of the track is capped with an end cap RELAY CONTROLLER Both level switches are pre wired before shipment to the 4 pole terminal strip Input 1A Input 1B The switch technologies used to indicate level are either Ultrasonic Buoyancy or Vibration The Compact Relay Controller provides a 1 2 Conduit connection and 6 poles for wire termination of...

Страница 14: ...nsor to be moved slide the sensor along the track and then turn the nut back to lock into place NOTES No more than a to a turn to unlock and lock the nut is required The cable for the sensor is designed to be submersed is made of the same material as the sensor Sensors can easily be raised from their original position but may not be lowered because of pre cut cable lengths For systems ordered with...

Страница 15: ...ventory One Smart Trak kit LM10 1__1 includes the following parts 1 x Seal Plug 1 x Top compression fitting 1 x Wire gasket 1 x Thrust Plate 1 x Locking pin 1 x 2 NPT fitting 1 x Track 1 x End cap 2 x Wire retainer clips not shown Smart Trak Assembly Drawing Top View Seal Plug Assembly Drawing Side View ...

Страница 16: ...ide tension for the push and turn connection Switch Car Kit Assembly Drawing Side View Inventory One switch car kit LM30 1001 consists of the following parts 1 x Locking bolt 1 x Locking Nut 1 x Sensor car 1 x O ring 1 x Bayonet to 3 4 NPT adapter Switch Car Kit to Smart Trak Top View Switch Car Kit to Smart Trak Side View DETERMINE THE PROPER WIRE LENGTH Don t make the mistake of trimming the sen...

Страница 17: ...d directly to the side wall or lip of the tank Tank Adapter Flange Mounting Side Mount Bracket LM50 series Lip of Tank Side Wall SMART TRAK INSTALLATION The Smart Trak with Compact Junction Box assembly is designed to be installed through a 2 NPT 2 G thread The level switches will be staggered through the fitting for installation A key feature of Smart Trak is the adjustability of the level switch...

Страница 18: ...ontroller 2 Input LED s The input LED s on the controller will be Amber when the switch es is are wet and Off when the switch es is are dry Note see Step 5 regarding reed switches If the LED s are not switching the input LED test the level switch 3 Relays When both inputs are wet Amber LED s On the relay will be energized Red LED On After that if one switch becomes dry the relay will remain energi...

Страница 19: ...sure the input LEDs are both in the same state both ON or both OFF If not check wiring to each sensor Second check status of Relay LED If incorrect flip the Invert switch to change the relay state Pump or Valve is supposed to stop but it does not First check to make sure the input LEDs are both in the same state both ON or both OFF If not check wiring to each sensor Second check status of Relay LE...

Страница 20: ...ocedures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Flowline have attempted to repair 5 have been involved in accidents or natural disasters or 6 are damaged during return shipment to Flowline Flowline reserves the right to unilateral...

Отзывы: