10 |
www.flowair.com
Power supply 230V/50Hz (OMY 3x1,omm
2
)
Power supply 3x400V/50Hz:
EliS C-E-100 (5x2,5 mm
2
) Overcurrent breaker B16
ELiS C-E-150 (5x2,5 mm
2
) Overcurrent breaker B20
ELiS C-E-200 (5x4,0 mm
2
) Overcurrent breaker B25
Door contact DCet/DCm (door closed
–
opened contacts; door opened
–
closed contats).
Use DC jumper between connectors NC; NC (Elis C-W) if door contact not
used (OMY 2x1,0 mm
2
)
Air curtain step switch with thermostat TS (OMY 5x1,0 mm
2
)
FAN AUTO
–
Fan auto - fan operating depending on room thermostat signal
FAN CONT- fan operating continuously (deactivated thermostat signal)
HEAT
–
heating mode
FAN
–
room thermostat deactivated
COOL
–
cooling mode
In curtain connected with drivers, replace fuse on F6,3A
Zasilanie 230V/50Hz (OMY 3x1mm
2
)
–
obie kurtyny należy zasilić z tej
samej fazy
Zasilanie 3x400V/50Hz:
ELiS C-E-100 (5x2,5 mm
2
); wyłącznik naprądowy B16
ELiS C-E-150 (5x2,5 mm
2
) ; wyłącznik naprądowy B20
ELiS C-E-200 (5x4,0 mm
2
) ; wyłącznik naprądowy B25
czujnik drzwiowy DCet/DCm (drzwi zamknięte –
styki rozwarte; drzwi
otwarte
–
styki zwarte). W przypadku b
raku czujnika drzwiowego należy
wykonać zworkę pomiędzy złączami NC i NC.
3-
stopniowy regulator obrotów z termostatem TS (OMY
5x1,0mm
2
).
FAN AUTO
–
praca wentylatorów zależna od temp.
FAN CONT-
praca wentylatorów ciągła (niezależna od temp.)
HEAT
–
funkcja grzania
FAN
–
dla FAN CONT dezaktywacja pracy termostatu
COOL
–
odwrócenie logiki pracy termostatu
W kurtynie do której podłączone są sterowniki należy wymienić bezpiecznik
na F10A
Stroomvoorziening: 230 V/50 Hz (3-aderig, 3 x 1,0 mm
2
)
Stroomvoorziening 3x400V/50Hz:
ELiS C-E-100 (5x2,5 mm
2
) Overspanningsbeveiliging B16
ELiS C-E-150 (5x2,5 mm
2
) Overspanningsbeveiliging B20
ELiS C-E-200 (5x4,0 mm
2
) Overspanningsbeveiliging B25
Deurschakelaar DCet/DCm (deur gesloten - schakelaar geopend; deur
geopend - schakelaar gesloten).
Plaats een DC jumper tussen de connectoren NC en NC als
de deurschakelaar niet in gebruik is (2-aderig, 2 x 1,0 mm
2
)
Luchtgordijn te bedienen met TS thermostaat 3-standenregeling (5-aderig,
5 x 1,0 mm
2
)
FAN AUTO - ventilator auto - de werking van de ventilator wordt geregeld
door het signaal van de TS ruimtethermostaat
FAN CONT - ventilator is continu ingeschakeld (signaal van de thermostaat
gedeactiveerd)
HEAT - verwarmingsstand
FAN - ruimtethermostaat gedeactiveerd
COOL
–
koelingsstand ( n.v.t. )
Vervang de zekering op F6,3A in een gordijn dat is verbonden met
stuurprogramma's
Alimentare electrica 230V/50Hz (OMY 3x1,omm
2
)
Alimentare electrica 3x400V/50Hz:
EliS C-E-100 (5x2,5 mm
2
) B16
ELiS C-E-150 (5x2,5 mm
2
) Siguranta supracurent B20
ELiS C-E-200 (5x4,0 mm
2
) Siguranta supracurent B25
Contact usa DCet/DCm (contacte usa inchisa - deschisa; contacte usa
deschisa - inchisa).
Utilizati DC jumper intre conectorii NC; NC(ELiS C-W) daca nu se utilizeaza
senzorul de usa (OMY 2x1,0 mm
2
)
Termostat TS cu selector de viteza (OMY 5x1,0mm2)
FAN AUTO - Fan auto - Ventilatatorul functionaza dupa semnalul de la
termostatul de camera
FAN CONT - Ventilatorul functioneaza continuu (semnal de la termostat
dezactivat)
HEAT - mod incalzire
FAN - termostat camera dezactivat
COOL - mod racire
In perdea conectata cu driver,inlocuiti siguranta F6,3A
6.2. ELECTRIC SCHEME
–
CURTAIN CHAINING
6.2. STEROWANIE
–
ŁĄCZENIE KURTYN
6.2. AANSLUITSCHEMA
–
GORDIJNEN IN SERIE
6.2. CONECTAREA MAI MULTOR PERDELE
Single TS controller can run with up to 2 Elis C air curtains. Larger number of
Elis C-W air curtains need to be connected via RX splitter.
Możliwe jest podłączenie dwóch kurtyn do jednego regulatora TS. W przypadku
podłączenia większej ilości kurtyn
C-W
do jednego sterownika TS należy
wykorzystać rozdzielacz RX.
Een TS thermostaat kan maximaal 2 Elis C luchtgordijnen regelen. Een groter
aantal Elis C-W luchtgordijnen moet worden gekoppeld met behulp van een
RX splitter.
Un controller TS poate coordona maximum 2 unitati ELiS C. Pentru a coordona un
numar mai mare de unitati este nevoie de un spliter RX.
C-W
Single TS controller can run with up to 2 Elis C air curtains. Larger number
of Elis C-W air curtains need to be connected via RX splitter.
Możliwe jest podłączenie dwóch kurtyn do jednego regulatora TS. W przypadku
podłączenia większej ilości
kurtyn C-W
do jednego sterownika TS należy
wykorzystać rozdzielacz RX.
Een TS thermostaat kan maximaal 2 Elis C luchtgordijnen regelen. Een
groter aantal Elis C-W luchtgordijnen moet worden gekoppeld met behulp
van een RX splitter.
Можно подключить макс. 2 завесы к одному регулятору
TS
. Для того, чтобы
подключить больше завес к одному командоконтроллеру
TS
, следует
применить дополнительные распределители
RX.
C-