and the negative pump lead to the terminal labeled 

Pump ‘–’. 

 

NOTICE:

 If the leads are reversed, the pump will run 

backward and not pump water.

 

3.

 

The float switch leads are not polarity sensitive; connect 
t

he float switch leads to the ‘Float Switch’ tabs on the 

charger/controller. 

 

4.

 

Test the float and the pump by lifting and holding the 

float. The ‘PUMP STATUS’ LED will light continuously and 

the buzzer will beep steadily. The 

 

Figure 5: The battery input is inside the battery case.  

Support the case when opening it. The support must be 
at least 4” thick.

 

pump should start after 3 seconds. If the pump does 

not run, check all the connections and remake them as 
necessary.

 

5.

 

To stop the pump, lower the float; after 25 seconds the 

pump should stop, the ‘PUMP STATUS’ LED should 

flash, and the buzzer should beep. 

 

6.

 

With the pump operating, test the ‘SILENCED ALARM’ 
button; hold for one second; release. The ‘SILENCED 

AUDIBLE ALA

RM’ LED should illuminate and the buzzer 

should stop sounding. To reset the buzzer (allow it to 

sound) and extinguish the ‘SILENCED AUDIBLE ALARM’ 
LED, press the ‘SILENCE ALARM’ button again for one 

second.

 

Depress the ‘SYSTEM TEST’ button; hold it for one

 

second; release. The ‘PUMP STATUS’ LED should stop 

flashing.

 

Wiring 

 Setup  

NOTICE: 

During normal operation, the flashing ‘PUMP 

STATUS’ LED indicates that the pump has run in your 

absence.

 

7.

 

Press and hold ‘SYSTEM TEST’ button. All LEDs will light up, 

pump will run and buzzer will sound. Release the button 
and LEDs should go off, pump should stop, buzzer should 
stop.

 

8.

 

The ‘BATTERY STATUS’ LED indicates the battery capacity 

when the A.C. power is off.

 

A. Continuously ON - the battery voltage is above 

 

10.9 Volts Direct Current (10.9VDC) and  

4. capacity is 

above 20%.

 

B. Slow Beep/Slow LED Flash - 

the battery’s  

capacity is between 0 and 20%.

 

LED Display and Control Buttons

 

C. Fast Beep/Fast LED Flash - the battery is severely 

discharged. The battery will continue to charge (as 
long as the 115V AC power to the charger is on) at 

the rate of .5 AH until the battery’s charge is above 

20%.

 

When the first warning occurs (slow beep/slow flash), 

you will have approximately 2 hours (or less) of pump 
operation left. The actual time of operation will depend 
on the condition of the battery and may be as little as 
15 minutes.

 

Connect the Power Supply cable (supplied) to the 

Charger/Controller’s Power Input jack.

 

Содержание BDWWHU

Страница 1: ...OWNER S MANUAL BDWWHU Backup System...

Страница 2: ...fting by the cord can damage the cord Pump clear water only with this pump Pump is permanently lubricated at the factory Do not try to lubricate it Keep battery charger and battery box off of the floo...

Страница 3: ...rectly outdoors separate discharge pipe from the primary sump pump discharge pipe If this is not a practical option see the Common Discharge Figure 3 Page 4 option NOTICE For ALL installations once th...

Страница 4: ...tallation if the Primary Sump Pump PSP does not have a check valve installed below the wye you MUST install a check valve for the PSP as shown This prevents backflow of water into the sump from the Ba...

Страница 5: ...charge pipes Figure 3 Typical installation with common discharge pipe INSTALLATION Typical Separate Discharge Risk of electrical shock Can shock burn or kill Unplug the primary sump pump before beginn...

Страница 6: ...Leave the hose clamps loose and slide the Assembly down below the top of the riser pipe 9 Determine where you want the discharge to exit the basement At that point drill the necessary holes large enou...

Страница 7: ...he discharge pipe install one now 9 Cut a length of discharge pipe for the PSP to fit between the check valve and a 45 slip wye Be sure to allow for the overlap needed for gluing joints 10 Install the...

Страница 8: ...case from chipping and gouging do not let the battery sit on a concrete floor Install the battery on a shelf or protective pad plywood 2x4s etc Always install the battery in a dry location that is pro...

Страница 9: ...ions for maintenance and safe use of the battery 1 Connect the positive charger controller lead wire red to the positive battery terminal red Connect the negative charger controller lead wire black to...

Страница 10: ...e SILENCE ALARM button again for one second Depress the SYSTEM TEST button hold it for one second release The PUMP STATUS LED should stop flashing Wiring Setup NOTICE During normal operation the flash...

Страница 11: ...when it first receives power from the battery the BATTERY STATUS LED will flash for 3 seconds NOTICE To activate any Control Button press and hold it for 1 second LED Display TABLE II Operating Code...

Страница 12: ...he LED Charging Indicates that the battery is charging see Table II above Battery Status A Continuous ON the battery voltage is above 10 9 Volts DC and capacity is above 20 B Slow Beep Slow LED Flash...

Страница 13: ...S LED When pushed with the SILENCE ALARM button the Charger Controller microprocessor resets and error code resets Silence Alarm Toggle Prevents the audible alarm sounding Press and release to reset L...

Страница 14: ...primary pump discharge and the Battery Backup wye Check for an obstruction in the discharge pipe The discharge pipe length and or height exceeds the capacity of the pump See Table VI Page 11 for pump...

Страница 15: ...012 3 Float Switch PS17 2003 4 Charger Controller PS217 1521 5 Battery Case Complete PS17 1512 6 AC Adaptor PS17 2008 7 11 x 14 Plastic Cable Tie Purchase separately If pump fails replace entire syste...

Страница 16: ......

Страница 17: ...15...

Отзывы: