background image

Installation  

6

 

NOTICE:

 Allow for overlap when cutting piping and run a trial 

(dry) fitting before you glue.

 

1.

 

Use PTFE pipe thread sealant tape on male ends of 
discharge pipe. Thread the 1-

1/4” x 1

-

1/2” elbow (supplied) 

onto the discharge. When tight, the elbow must point up. 

 

2.

 

If possible, install the Battery Backup Unit (BBU) on the 
floor of the sump; be sure that the two pumps do not touch 
each other and do not interfere with switch operation. 

 

NOTICE:

 If debris or gravel is present in the bottom of the 

sump pit that could get sucked up into the pump, set both 
the primary sump pump and the BBU up on bricks or cinder 
blocks to prevent clogging.

 

3.

 

If the sump is too small to allow both pumps to sit on the 
bottom of the sump, install an angle bracket on the primary 

sump pump’s disch

arge pipe with stainless steel hose 

clamps. Mount the backup pump on the angle bracket. See 

Figure 1, “Separate Discharge”.

 

4.

 

Cut a piece of 1-

1/2” PVC pipe to reach from the backup 

pump discharge elbow to about one (1) foot above the 
basement floor. This is the lower discharge pipe. 

 

5.

 

To prevent airlocking the pump during operation, drill a 

1/8” hole in the lower discharge pipe about 2” above the 

bottom of the pipe (below floor level). 

 

6.

 

Install FP0026-10 check valve (purchase separately) on the 
upper end of the pipe. Tighten the hose clamps securely. 
BE SURE that the flow arrows point UP (away from the 
BBU). If they point down, the valve will not pass water and 
the pump will not work.

 

7.

 

Cut a short length of 1-

1/2” PVC pipe for a riser pipe and 

clamp it into the top of the check valve.

 

8.

 

Install a U74-68 Hose and Clamp Assembly on the top of 
the riser pipe. For 1-

1/2” pipe, remove and discard the 

short piece of 1-

1/4” hose in the Hose and Clamp 

Assembly. Leave the hose clamps loose and slide the 
Assembly down below the top of the riser pipe. 

 

9.

 

Determine where you want the discharge to exit the 
basement. At that point, drill the necessary holes (large  
enough to have clearance for a 1-

1/2” pipe) to allow you to 

run the discharge pipe from above the sump to the 
outdoors.

 

10.

 

Install the horizontal discharge pipe. Install a 90° elbow on 
the inside end but do not glue. 

 

11.

 

Cut another short piece of 1-

1/2” PVC for the Upper 

Discharge Pipe to run from the top of the riser pipe up to 
the 90° elbow. Be sure to allow enough overlap for the glue 
joint in the elbow.

 

12.

 

Do a trial fit with NO GLUE, installing the 1-

1/2” upper 

discharge pipe in the 90° elbow and the upper discharge 
pipe in the vertical end of the 90° elbow. The upper 
discharge pipe should just fit between the riser pipe and 
the elbow. 

 

13.

 

 Risk of fire and chemical inhalation.

 

Whenever using PVC primer and PVC cement, follow the 

glue manufacturer’s instructions.

 

14.

 

Make sure that the BBU will clear the primary sump pump 

and its switch. If there isn’t room for both pumps to sit on

 

the floor of the sump, the BBU will have to be raised 
(depending on your particular situation).

 

15.

 

Clean, prime and glue the upper discharge pipe into the 

 

90º elbow. When the glue has set, slide the Hose and 

Clamp Assembly up to cover the joint and tighten all the 
hose clamps.

 

16.

 

Install the Battery Backup Switch as shown, 1” above start 

water level of primary pump. Fasten it to the pipe with 
cable ties. 

 

17.

 

Tape the pump cord to the riser pipe so that the plug 
cannot fall into the sump.

 

18.

 

Go to “BBU WIRING AND SETUP” (Page 8) for wirin

instructions. 

 

19.

 

Once all wiring is complete, fill your pit with water and 

verify that the PSP removes the water and the BBU doesn’t 

run. Then, unplug your PSP and refill your pit with water. 
Verify that the BBU pump removes the water.

 

20.

 

Make sure that the power is on to both pumps, and your 
system is ready to use.

 

 

Содержание BDWWHU

Страница 1: ...OWNER S MANUAL BDWWHU Backup System...

Страница 2: ...fting by the cord can damage the cord Pump clear water only with this pump Pump is permanently lubricated at the factory Do not try to lubricate it Keep battery charger and battery box off of the floo...

Страница 3: ...rectly outdoors separate discharge pipe from the primary sump pump discharge pipe If this is not a practical option see the Common Discharge Figure 3 Page 4 option NOTICE For ALL installations once th...

Страница 4: ...tallation if the Primary Sump Pump PSP does not have a check valve installed below the wye you MUST install a check valve for the PSP as shown This prevents backflow of water into the sump from the Ba...

Страница 5: ...charge pipes Figure 3 Typical installation with common discharge pipe INSTALLATION Typical Separate Discharge Risk of electrical shock Can shock burn or kill Unplug the primary sump pump before beginn...

Страница 6: ...Leave the hose clamps loose and slide the Assembly down below the top of the riser pipe 9 Determine where you want the discharge to exit the basement At that point drill the necessary holes large enou...

Страница 7: ...he discharge pipe install one now 9 Cut a length of discharge pipe for the PSP to fit between the check valve and a 45 slip wye Be sure to allow for the overlap needed for gluing joints 10 Install the...

Страница 8: ...case from chipping and gouging do not let the battery sit on a concrete floor Install the battery on a shelf or protective pad plywood 2x4s etc Always install the battery in a dry location that is pro...

Страница 9: ...ions for maintenance and safe use of the battery 1 Connect the positive charger controller lead wire red to the positive battery terminal red Connect the negative charger controller lead wire black to...

Страница 10: ...e SILENCE ALARM button again for one second Depress the SYSTEM TEST button hold it for one second release The PUMP STATUS LED should stop flashing Wiring Setup NOTICE During normal operation the flash...

Страница 11: ...when it first receives power from the battery the BATTERY STATUS LED will flash for 3 seconds NOTICE To activate any Control Button press and hold it for 1 second LED Display TABLE II Operating Code...

Страница 12: ...he LED Charging Indicates that the battery is charging see Table II above Battery Status A Continuous ON the battery voltage is above 10 9 Volts DC and capacity is above 20 B Slow Beep Slow LED Flash...

Страница 13: ...S LED When pushed with the SILENCE ALARM button the Charger Controller microprocessor resets and error code resets Silence Alarm Toggle Prevents the audible alarm sounding Press and release to reset L...

Страница 14: ...primary pump discharge and the Battery Backup wye Check for an obstruction in the discharge pipe The discharge pipe length and or height exceeds the capacity of the pump See Table VI Page 11 for pump...

Страница 15: ...012 3 Float Switch PS17 2003 4 Charger Controller PS217 1521 5 Battery Case Complete PS17 1512 6 AC Adaptor PS17 2008 7 11 x 14 Plastic Cable Tie Purchase separately If pump fails replace entire syste...

Страница 16: ......

Страница 17: ...15...

Отзывы: