FloPlast AF110 Скачать руководство пользователя страница 8

8

Figure 5

 

Examples of drain ventilation provisions

6.3

 To prevent self-siphonage a connection to the AF32 or AFE32 valve is required within 1500mm of the trap (see 

Figure 4).

6.4

 To prevent induced siphonage in a row of wash-basins, a AF32 or AFE32 valve can be fitted between 

the two wash-basins furthest from the discharge stack (see Figure 4).

6.5

 Air admittance valves should not be used as the only ventilation to septic tanks or cesspools.

6.6

 The valve should be installed within the building where it is easily accessible but not subject to  inter-

ference from vandals. 

6.7

 If the valve is to be installed in, or in close proximity to, an habitable space where noise of operation may cause a 

nusiance, then consideration must be given to the use of a suitable form of sound insulation.

6.8

 In addition, other than those shown in Figure 5, stacks should not be fitted with the valves when the connecting 

drain(s) are subject to periodic surcharging or are fitted with intercepting traps. An open-topped discharge stack or 

ventilating stack should be used in such cases.

Up to four dwellings fitted with

FloPlast AVE110, AF110 or

AX110 valves 

Index

C  -  Conventional vent stack

G - Gully

F  -  FloPlast 110mm or 82mm AAV

A - Access 

Single multi-storey building with

FloPlast AVE110, AF110 or

AX110 valves 

More than one multi-storey building 

with FloPlast AVE110, AF110 or

AX110 valves 

Row of 20 dwellings with 

FloPlast AVE100, AV110, AF110 or AX110 valves

11 to 20 vent at head and mid point

5 to 10 vent to head

up to 4th

non conventional

vent stack

A

A

F

G

F

G

A

A

A

A

A

G

C

A

A

C

G

G

F

F

G

F

G

A

A

A

A

20th

13th

12th

11th

10th

9th

8th

3rd

2nd

1st

head of

drain

A

A

F

G

A

A

F

F

F

G

G

G

A

A

C

F

F

A

A

A

C

A

A

A

A

F

A

A

F

Содержание AF110

Страница 1: ...itish Standards Kitemark KM512474 and CE mark as having met the performance requirements of BS EN 12380 2002 and have been designated with an A1 rating FloPlast s Air Admittance Valves provide a means...

Страница 2: ...the installation part of this document Building standards applicable to construction Wastewater drainage The valves can meet the relevent requirements of this Standard with reference to clauses 3 7 7...

Страница 3: ...also be installed directly into 100mm or 110mm European designated pipe with the use of an EPDM finned seal this product is designated AFE110 FloPlast s AF110 Air Admittance Valve as seen on the fron...

Страница 4: ...socket 82 82 0 82 3 BS EN1329 1 BS 4514 PVC AF110 AX110 Push Fit 110 110 0 110 3 BS EN 1329 1 BS EN 1455 1 BS EN 1565 1 BS EN 1566 1 BS 4514 BS5255 Multi AV110 Solvent Weld 110 110 0 110 3 BS EN1329 1...

Страница 5: ...on instructions are supplied in cardboard boxes and polyethylene bags to limit the risk of contamination or damage All valves must be stored upright in their boxes until required for use 3 2 The legen...

Страница 6: ...wellings a ventilated by FloPlast AVE100 AV110 AF110 or AX110 FloPlast AVE100 AV110 AF110 or AX110 FloPlast AF32 or AFE32 Minimum 200mm Greater than 4 metres b unventilated Up to 4 metres NOTES The ma...

Страница 7: ...le 3 and Figure 5 Table 3 Air admittance valve disposition Number of Dwellings Up to three stories in height Multi storey domestic dwelling and non domestic buildings 1 4 Additional drain and venting...

Страница 8: ...suitable form of sound insulation 6 8 In addition other than those shown in Figure 5 stacks should not be fitted with the valves when the connecting drain s are subject to periodic surcharging or are...

Страница 9: ...ied out in accordance with these instructions 11 2 FloPlast AF110 AX110 valves are supplied with a synthetic rubber connector enabling a push fit into 100mm and 110mm as indicated in Table 1 Additiona...

Страница 10: ...ecification BS 5255 1989 Specification for thermoplastics waste pipe and fittings BS EN 1329 1 2014 Plastics piping systems for soil and waste discharge low and high temperature within the building st...

Страница 11: ...c Are reviewed by the BSI as and when it considers appropriate 15 4 In issuing this document FloPlast is not responsible for a the right of the document holder to market supply install or maintain th...

Отзывы: