QSI3 WIRING
QSI VERSION 3 – PC BOARD
4-20mA
Figure 8
QSI VERSION 3 - WIRING DIAGRAM
Customer Equipment with Built-in Power Supply
Inputs: Standard Remote Sensor (Variable Reluctance Pickup Coil)
Outputs: Customer Equipment, 4-20mA Sensing, Built-in Loop Power Supply
Minimum signal amplitude required for
normal operation is approximately 15mV P-P.
Recommended cable type - twisted pair with
shield. Recommended maximum cable length
is 20ft.
CAUTION:
When reassembling the cover plate, make sure the enclosure seal is not crimped or twisted.
Do not over-tighten screws (hand-tighten only).
Figure 9