Installation Guide

 

IN-IC1-15

 

Title

:

 

Jace to i-Controller REV.200 MPU (575V 40–70 Ton) Conversion

 

 

Flō 

Tech Support 888-598-1198 

3

 

4-6DEC2021 

 

4.

 

Pulling Communications Cable 

A BacNet communications cable must be pulled to the 
unit for communication to the BMS system.  
 

5.

 

Install New Power Supply 

 

CAUTION:

  

Make sure the power to the 

Flō 

unit is turned 

off and internal electrical circuits are NOT 
energized.

 

 

5.1

 

Install New Transformers 

Using 5/16” screws, mount

 the 2 transformers in an area 

that has available space inside the controls cabinet.  
 
Using  the  sharpie,  mark  the  transformers  as  #1  and  #2. 
Transformer  1  will  be  dedicated  to  powering  the  i-
controller. Transformer 2 will be dedicated to powering all 
three expansion modules.  
 
Install the 

Flō 

provided fuses (Fuse Elec 10A/500V MIG) in 

each of the new transformers. 
 

NOTE:

  No  other  devices  will  be  connected  to  these 

transformers. 

 

5.2

 

Wire New Transformers 

Run the new transformers

 high voltage wires to 

Flō 

high 

voltage terminals L1 and L2.  
 

NOTE:

 Ensure the transformer tap correlates to the unit

’s

 

high voltage. 
 
Leave  the  new  transformer

s’

  low  voltage  wires 

disconnected. These will be terminated in the next steps. 

 

5.3

 

Prepare i-Controller for Installation  

Attach 10" lengths of Black 18 AWG wire to the following i-
Controller green plug connection points: 1, 7, 8, 25, 28 & 
61. See Figure 1. for plug orientation. 
 
Attach 10" lengths of Red 18 AWG wire to the following i-
Controller green plug connection points: 9, 15, 16, 29 & 71. 
See Figure 1. for plug orientation. 

 

Figure 1. Green Connector Reference 

Attach Red 18 AWG jumper wires between the following 
points on the i-Controller green plug connection points: 71 
to 80, 80 to 86, and 86 to 90.  
 
Attach  a  new  Black  18  AWG  wire  between  the 

Flō  unit’s 

CSTB1 24 VAC- (grounded side) and the Black 18 AWG wire 
coming from point 61 on the i-Controller. 
 
Attach  a  new  Red  18  AWG  wire  between  the 

Flō  unit’s 

CSTB1 24 VAC+ (hot side) and the Red 18 AWG wire coming 
from point 71 on the i-Controller. 

 

5.4

 

Prepare Expansion Module A for Installation 

Attach 10"  length of Black 18 AWG wire to the following 
Expansion green plug connection points: 1 & 15

**

.  

 

**NOTE:

 Only pigtail 15 if the unit has a CO2 or outdoor 

humidity sensor. 
 
Attach a 10" length of Red 18 AWG wire to the following 
Expansion green plug connection point: 9. 
 

5.5

 

Prepare Expansion Module B for Installation 

Attach 10" lengths of Black 18 AWG wire to the following 
Expansion green plug connection points: 1, 15 & 28

*

.  

 

*NOTE: 

Point 28 only gets a wire if either 2

nd

 space temp 

or 2

nd

 stage reheat/reclaim inlet probe. 

 
Attach a 10" length of Red 18 AWG wire to the following 
Expansion green plug connection point: 9 & 16. 
 

Содержание i-Controller

Страница 1: ...oat Switch 4 6 5 Install New CO2 Sensor 5 6 6 Install Space Temp RH Combo Sensor 5 7 Install The i Controller Components 6 7 1 Remove Existing Jenesys Controls 6 7 2 Install New i Controller and Expan...

Страница 2: ...rols Screwdriver Step Drill Bit for CO2 Sensor Probe Installation Refrigerant Tee with Schrader Depressor 2 Schrader Cores 4 Conductor Shielded Twisted Wire or Equivalent 5 Conductor Shielded Twisted...

Страница 3: ...gths of Black 18 AWG wire to the following i Controller green plug connection points 1 7 8 25 28 61 See Figure 1 for plug orientation Attach 10 lengths of Red 18 AWG wire to the following i Controller...

Страница 4: ...the 0 667 PSI Discharge transducers on the liquid lines of circuits 1 2 3 4 If there are spare service ports on the unit install the transducers on a spare service port If spare service ports are not...

Страница 5: ...w Figure 3 CO2 sensor location inside the unit Wire the new CO2 based on the following see Figure 4 24VAC Red wire 24VAC Black wire COM Green wire CO2 SIGNAL White wire NOTE Do not wire the CO2 sensor...

Страница 6: ...1 down 2 up 3 down 4 down NOTE The actual switch may be white but for illustrative purposes the switch is black in the Figure 6 below Figure 6 Fl i Controller Expansion Addressing Wire the 2 expansion...

Страница 7: ...Comp 1 SG WHT 12 Discharge Press Comp 1 0V BLK 8 Discharge Press Comp 1 Pwr RED 15 Suction Press Comp 2 SG WHT 13 Suction Press Comp 2 0V BLK 8 Suction Press Comp 2 Pwr RED 15 Discharge Press Comp 2...

Страница 8: ...Reheat Reclaim Inlet Probe 2 SG 29 Reheat Reclaim Inlet Probe 2 0V 28 This indicates that you will be attaching to a 10 wire not a pin This indicates that you will be attaching to the CSTB1 Table 3 In...

Страница 9: ...aim do not wire 24VAC to point 86 The dry common from the refrigeration rack reclaim control is connected to point 86 Existing Points Expansion Module A Expansion A Pin See Wiring Diagram in Unit ERV...

Страница 10: ...With a field highlighted press ENTER the value will begin blinking While the highlighted value is blinking use the and set the value Press ENTER a second time to accept changes The controller will au...

Страница 11: ...hen press ENTER Dehumidification mode is now turned OFF 9 6 Heating Test Mode From the Field Technician Options screen press T2 Test Modes Press T3 2 Operational Tests Use to navigate to the Heat Test...

Страница 12: ...ions button Using the to navigate to the value that you wish to change With a field highlighted press ENTER the value will begin blinking While the highlighted value is blinking use the set the value...

Страница 13: ...l Tech Support 888 598 1198 13 4 6DEC2021 11 Appendix 11 1 i Controller Layout 1 24VAC Power Point 9 and 1 2 Analog Inputs 3 Digital Inputs 4 Digital Outputs 5 Analog Outputs 11 2 Expansion Board Layo...

Отзывы: