Installation Guide

 

IN-IC1-15

 

Title

:

 

Jace to i-Controller REV.200 MPU (575V 40–70 Ton) Conversion

 

 

Flō 

Tech Support 888-598-1198 

2

 

4-6DEC2021 

 

1.

 

Overview  

This document describes the steps required to replace the 
Jace2  controller  with  an  i-Controller  in  a  40-70  ton  MPU 
unit. 
 
Below is a brief summary of an i-Controller upgrade. 
 

 

Power supply replacement. 

 

CO2 sensor replacement. 

 

Pressure transducer installation. 

 

Reheat/reclaim inlet sensor replacement. 

 

Space temp/RH sensor replacement. 

 

Controller replacement. 

 

Perform operational tests. 
 

2.

 

Contractor Tools & Materials 

In addition to a standard toolset, having the items in Table 
1 are required during the installation.  

ADDITIONAL TOOLS & MATERIALS 

Cordless Drill 

Drill Bit Set 

Multi-Meter 

Adjustable Wrench 

Wire Strippers 

Wire Crimpers 

Temperature Gauge 

Psychrometer 

Socket Set 

 Standard 

Cell Phone 

Red Fork Wire Connectors 

Fine Point Sharpie Marker 

5/16” Self

-Tapping Sheetmetal Screws 

18AWG Stranded Insulated Wire (Red, Black & White) 

Blue, Orange & Yellow Wire Nuts 

Red Insulated Female Spade Connectors 

Micro Control Screwdriver Set (Eye Glass Repair Size) 

Controls Screwdriver 

½” Step Drill Bit 

for CO2 Sensor Probe Installation 

¼” Refrigerant Tee 

with Schrader Depressor & 2 Schrader 

Cores 

4-Conductor Shielded Twisted Wire or Equivalent 

5-Conductor Shielded Twisted Wire or Equivalent 

BacNet Compliant Cable 

Table 1. Additional Tools & Materials 

3.

 

Flō 

Supplied Parts 

The  parts  contained  in  the 

Flō 

supplied  parts  kit  are 

provided specifically for the 

Flō 

unit at this site.  

Part Description

 

Part Number

 

Qty

 

i-Controller Unit Controller 

PTCS8188101 

i-Controller Expansion Module 

PTCS8187001 

DIN-Rail 

PTCSP91730 

DIN-Rail End Cap 

PTCSV66150 

i-Controller Visograph 

PTCS8189002 

Visograph/CO2 Sensor 
Mounting Bracket 

PTCS184068001 

24VAC Isolated Transformer 

PTCSP47700 

Fuse Elec 10A/500V MIG 

PTCSP63180 

4-Wire Duct CO2 Sensor (with 
Tubing and Duct Probe) 

PTCSV57760 

Pressure Transducer (0-500psi)  

PTCSV67380 

Transducer Whip (Blue) 

PTCSV42220 

Pressure Transducer (0-667psi)  

PTCSV67390 

Transducer Whip (Yellow) 

PTCSV42100 

Temperature/Humidity Combo 
Sensor 

**

 

PTCS2035752 

Reheat/Reclaim Coil Surface 
Mount Temp Sensor 

PTCS5011125 

Float Switch Kit 

PTCSS25801 

Digital Phase Monitor 

PTCSV26350 

Upgrade Document 

IN-IC1-15 

Table 2. 

Flō 

Supplied Parts List 

**NOTE: 

PTCS2035752 may be substituted for a RH 

Sensor (PTCS2035751) and a Temp Probe (PTCS5011121). 
 

 

Содержание i-Controller

Страница 1: ...oat Switch 4 6 5 Install New CO2 Sensor 5 6 6 Install Space Temp RH Combo Sensor 5 7 Install The i Controller Components 6 7 1 Remove Existing Jenesys Controls 6 7 2 Install New i Controller and Expan...

Страница 2: ...rols Screwdriver Step Drill Bit for CO2 Sensor Probe Installation Refrigerant Tee with Schrader Depressor 2 Schrader Cores 4 Conductor Shielded Twisted Wire or Equivalent 5 Conductor Shielded Twisted...

Страница 3: ...gths of Black 18 AWG wire to the following i Controller green plug connection points 1 7 8 25 28 61 See Figure 1 for plug orientation Attach 10 lengths of Red 18 AWG wire to the following i Controller...

Страница 4: ...the 0 667 PSI Discharge transducers on the liquid lines of circuits 1 2 3 4 If there are spare service ports on the unit install the transducers on a spare service port If spare service ports are not...

Страница 5: ...w Figure 3 CO2 sensor location inside the unit Wire the new CO2 based on the following see Figure 4 24VAC Red wire 24VAC Black wire COM Green wire CO2 SIGNAL White wire NOTE Do not wire the CO2 sensor...

Страница 6: ...1 down 2 up 3 down 4 down NOTE The actual switch may be white but for illustrative purposes the switch is black in the Figure 6 below Figure 6 Fl i Controller Expansion Addressing Wire the 2 expansion...

Страница 7: ...Comp 1 SG WHT 12 Discharge Press Comp 1 0V BLK 8 Discharge Press Comp 1 Pwr RED 15 Suction Press Comp 2 SG WHT 13 Suction Press Comp 2 0V BLK 8 Suction Press Comp 2 Pwr RED 15 Discharge Press Comp 2...

Страница 8: ...Reheat Reclaim Inlet Probe 2 SG 29 Reheat Reclaim Inlet Probe 2 0V 28 This indicates that you will be attaching to a 10 wire not a pin This indicates that you will be attaching to the CSTB1 Table 3 In...

Страница 9: ...aim do not wire 24VAC to point 86 The dry common from the refrigeration rack reclaim control is connected to point 86 Existing Points Expansion Module A Expansion A Pin See Wiring Diagram in Unit ERV...

Страница 10: ...With a field highlighted press ENTER the value will begin blinking While the highlighted value is blinking use the and set the value Press ENTER a second time to accept changes The controller will au...

Страница 11: ...hen press ENTER Dehumidification mode is now turned OFF 9 6 Heating Test Mode From the Field Technician Options screen press T2 Test Modes Press T3 2 Operational Tests Use to navigate to the Heat Test...

Страница 12: ...ions button Using the to navigate to the value that you wish to change With a field highlighted press ENTER the value will begin blinking While the highlighted value is blinking use the set the value...

Страница 13: ...l Tech Support 888 598 1198 13 4 6DEC2021 11 Appendix 11 1 i Controller Layout 1 24VAC Power Point 9 and 1 2 Analog Inputs 3 Digital Inputs 4 Digital Outputs 5 Analog Outputs 11 2 Expansion Board Layo...

Отзывы: