Recommendations and Warnings

Receiving inspection

Upon receiving the pump, it should 
be  inspected  for  damage  or 

shortages.  If  damage  has  occurred, 
file  a  claim  immediately  with  the

company that delivered the pump. If

the  manual  is  removed  from  the

packaging, do not lose or misplace.

Storage

Any  product  that  is  stored  for  a 

period  longer  than  six  (6)  months 
from the date of purchase should be 
bench  tested  prior  to  installation.  A 

bench test consists of, checking the 

impeller  to  assure  it  is  free  turning 

and  a  run  test  to  assure  the  motor 

(and  switch  if  provided)  operate 
properly.

Controls

Manual  models  require  a  separate 
approved  pump  control  device  or 
panel  for  automatic  operation.  Be 
sure the electrical specification of the 

control selected properly match the 

electrical specifications of the pump.

Submergence

The  pump  should  always  be 
operated 

in 

the 

submerged 

condition. The minimum sump liquid 
level should never be less than above 
the pump’s volute (See Figure 1).

Installation

These pumps are recommended for 
use  in  a  sump,  basin  or  lift  station. 

The  sump,  basin  or  lift  station  shall 
be sealed and vented in accordance 
with  local  plumbing  codes. 

This 

pump  is  designed  to  pump 
sewage,  effluent  or  wastewater, 
non-explosive  and  non-corrosive 
liquids and shall NOT be installed 

in locations classified as hazardous 
in  accordance  with  the  National 
Electrical  Code  (NEC)  ANSI/NFPA 
70 or Canadian Electric Code (CEC).

 

The pump should never be installed 
in a trench, ditch, or hole with a dirt 

bottom.  The  legs  will  sink  into  the 
dirt  and  the  suction  will  become 

plugged.

The  installation  should  be  at  a 

sufficient  depth  to  ensure  that  all 
plumbing  is  below  the  frost  line.  If 
this is not feasible, remove the check 
valve  and  size  the  basin  to 
accommodate 

the 

additional 

backflow volume.

Pumps are most commonly installed 
in  simplex  or  duplex  stations  or 

basins  with  a  slide  rail  system 
(Barmesa  SRC),  which  allows  the 

pump(s)  to  be  installed  or  removed 
without requiring personnel to enter 

the  station,  or  resting  on  the  basin 
floor.

Discharge Piping

Discharge piping should be as short 
as possible and sized no smaller than 
the pump discharge. 

Do not reduce 

the discharge pipe size below that 
which  is  provided  on  the  pump.

 

Both  a  check  valve  and  a  shut-off 

valve  are  recommended  for  each 

pump.  The  check  valve  is  used  to 

prevent backflow into the sump. The 
shut-off  valve  is  used  to  manually 
stop  system  low  during  pump 

servicing.

Liquid Level Controls

The  level  control(s)  should  be 

mounted on the discharge piping, a 

 

cable  rack or  l

 

f oat  pole.  The  level 

control  should  have  adequate 

clearance so it cannot hang up in it’s 

 

 

swing  and  that  the  pump is 

 

completely  submerged  when  the 

level control is in the "Off " mode. By 

adjusting the cord tether the control 

level  can  be  changed.  One  cycle  of 
operation  should  be  observed,  so 
that  any potential  problems  can  be 

 

corrected.

Electrical Connections

Power cable:

The  power  cable  mounted  to  the 
pump must  not  be  modi ied  in  any 

 

f

way  except for  shortening  to  a 

 

speci ic  application. Any  splice 

f

 

between  the  pump  and  the control 

 

panel  must  be  made  in accordance 

 

with  the  electric  codes.  It  is 
recommended that a junction box, if 
used, be mounted outside the sump 

 

or  be  of at  a  minimum  Nema  4 

 

construction iflocated within the wet 

 

well. 

DO  NOT  USE  THE  POWER 

CABLE TO LIFT PUMP.

It  is  recommended  that  the  level 
control l

 f oat should be set to insure 

that  the  liquid  in  the  sump  never 

drops  below  the  top  of the  motor 

 

housing  or  a  minimum  level  of 10 

 

inches above the basin  lfoor.

Always  rely  upon  a  C

ed 

ertifi

Electrician for installation.

Bottom of Feet

17"

Recommended

Submergence Level

Minimum

Submergence Level

Figure 1

Содержание 8FFSEHA Series

Страница 1: ...llation Operation Maintenance Manual Submersible Non Clog Sewage Pumps 8FFSEHA 30 40 50 60 75 1150 RPM 100 125 200 1750 RPM IMPORTANT Read all instructions in this manual before operating or servicing a pump ...

Страница 2: ...liftingdevice Sump and sewage pumps often handle materials which could cause illness or disease Wear adequate protective clothing when working on a used pump or piping Never enter a basin after it has been used WARNING Failure to permanently ground the pump motor and controls before connecting to power can cause shock DANGER burnsordeath These pumps are not to be installed in locations classified ...

Страница 3: ...A 48class30 WEARRING Bronze MOTORHOUSING CastironASTMA 48class30 SEALPLATE CastironASTMA 48class30 IMPELLER Castiron ASTM A 48class 3vanes closed withabronzewearringandvanesonbackside 30 SHAFT 416seriesstainlesssteel SQUARERINGS Buna N PAINT Airdryenamel waterbased SEAL Double mechanical oil filled chamber Ceramic stationary seat carbon ring and exclusion sealintherotatoryset Buna Nelastomerandsta...

Страница 4: ...he basin to accommodate the additional backflow volume Pumps are most commonly installed in simplex or duplex stations or basins with a slide rail system Barmesa SRC which allows the pump s to be installed or removed without requiring personnel to enter the station or resting on the basin floor Discharge Piping Discharge piping should be as short as possible and sized no smaller than the pump disc...

Страница 5: ...ise direction as viewed from motor end or opposite to impeller rotation Impeller rotation is counter clockwise as viewed from bottom of pump 3 Name Plate Record the information from the pump name plate to drawing in front of manual for future reference 4 Insulation Test An insulation megger test should be performed on the motor Before the pump is put into service The resistance values ohms as well...

Страница 6: ...r 2 on cap screws 2 and torque to 24 ft lbs Check for free rotation of motor and impeller Locate impeller washer 8 on shaft apply thread lock primer such as LOCTITE Primer T let set per manufacturer s directions to screw 10 threads thread screw 10 into shaft and torque to 35 ft lbs Rotate impeller to check for binding DO NOT disassemble the Reliance motor in any way except for outer seal as this w...

Страница 7: ...S 3 MOTOR GASKET 1 4 03020022 ADAPTER 1 5 91010396 SOCKET HD SCREW 5 8 x 1 STAINLESS 12 6 30400105 MOTOR ADAPTER 1 7 03140107 IMPELLER 1 8 30400415 IMPELLER WASHER 1 9 91010064 LOCKWASHER 3 4 STAINLESS 1 10 91010359 HEX HD SCREW 3 4 x 2 STAINLESS 1 11 92010170 VOLUTE GASKET 2 12 03090062 VOLUTE 1 13 30400301 WEAR RING 1 14 91010181 BOLT 1 4 x 1 STAINLESS 2 15 92010169 SUCTION FLANGE GASKET 1 16 03...

Страница 8: ...ee power supply leads to ensure proper impeller rotation 11 Repair fixturesasrequiredtoeliminateleakage 12 Check pump temperature limits and fluid temperature 13 Replace portion of discharge pipe with flexible connector or tighten existing piping 14 Turn to automatic position 15 Check for leaks around basin inlet and outlets Pump will not turn off 2a Float movement restricted 2b Switch will not ac...

Страница 9: ......

Отзывы: