background image

 

24 

 

GATEWAY SPECIFICATION - WebdynPulse

 

WebdynPulse – Gateway specification - Version 2.0 

 

The WebdynPulse always carries out the same tasks, regardless of the type of connection requested: 

 

NTP synchronization  

 

Connection to the remote FTP server 

o

 

Alarm management 

o

 

Command file management 

o

 

Data management 

 

Upload of input/output data files 

 

Upload of electric meter files 

o

 

Configuration file management 

o

 

Definition file management 

o

 

Log management 

o

 

Firmware update management 

 

6.4.1  Manual connection 

 

Connection by pressing the push-button: 

You can force a connection manually by using a tool to press and hold the push-button labelled 

“INSTALL” until the “SERVICES” LED begins to flash rapidly. 

 

Connection via the built-in Web server: 

You can force a connection manually via the built-in Web interface by going to the 

“Install/Connection” menu and clicking on the “Connect” button.   

 

                                 

         

 

 

Connection via SMS: 

 

Send the SMS “

connect”

 to the WebdynPulse to force immediate connection. 

 

6.4.2  Periodic automatic connection 

Periodic automatic connection consists of providing the WebdynSun with a period for connection to 

the remote server. This period is expressed in hours and is repeated every day. 

This is done by using the variables “Connection_Period”, “Connection_Hour” and 

“Connection_Minute” in the configuration file 

prefixID

_var.ini. 

 

 

Содержание WebdynPulse WG0510-A01

Страница 1: ...WebdynPulse The monitoring gateway for your electric meters Gateway specification...

Страница 2: ...NTP server 11 5 3 Connation via GPRS or Ethernet 11 5 3 1 Ethernet connection 12 5 3 2 GPRS connection 12 5 3 3 Managing the PIN code for the SIM card 12 6 Configuring the unit 12 6 1 Roles of the We...

Страница 3: ...f the alarms file name 35 7 7 2 Format of alarm file 35 7 7 3 Example of an alarm on a digital input 35 8 Upgrading the unit 35 8 1 Upgrading via the Web server 36 8 2 Upgrading remotely via the FTP s...

Страница 4: ...urope for rack mounted industrial control equipment TCP Transmission Control Protocol A connection oriented protocol for the Internet which provides data segmentation into packets that are transmitted...

Страница 5: ...the health safety of personnel Electrical connections All wiring must be carried out only by a specialized qualified electrician Prior to installation all equipment connected to the corresponding com...

Страница 6: ...lse Gateway specification Version 2 0 3 1 Overview diagram of a comprehensive monitoring solution FTP Server HTTP Server Web Services Electric meters Local PC configuration Users Operation Electric in...

Страница 7: ...compressed data Dimensions Size 157mm 86mm 58 5mm Environmental conditions Operational temperature range 10 C to 55 C Storage temperature for a period of less than one month 20 C to 45 C Storage temp...

Страница 8: ...modules please check the output tension adjustment value In addition check the power consumption of all remotely powered modules Characteristics OUTPUT DC VOLTAGE 24V RATED CURRENT 0 63A CURRENT RANG...

Страница 9: ...EFFICIENT 0 03 0 50 C VIBRATION 10 500Hz 2G 10min 1cycle period for 60min each along X Y Z axes Mounting Compliance to IEC60068 2 6 SAFETY EMC SAFETY STANDARDS UL60950 1 TUV EN60950 1 approved design...

Страница 10: ...vailable on a remote FTP server Consequently it is vitally important that the WebdynPulse gateway should have access to an FTP server for downloading and or uploading its configuration and definition...

Страница 11: ...oad of data files This directory contains four subdirectories o IO Analogue and digital input output data and index entries ALARM Contains the alarm files CMD Contains the command and acknowledgement...

Страница 12: ...e gateway If the PIN code is activated and equal to 0000 when the gateway is fired up for the first time a new PIN code is attributed to the SIM card This PIN code is defined on the basis of the ICCID...

Страница 13: ...e files on the FTP server it creates them from its current configuration Furthermore at every connection to the server the gateway checks the modification dates and sizes of the files in order to dete...

Страница 14: ...ask Communication via Ethernet up to 15 characters 255 255 255 0 X LAN_Gateway Address of the gateway router on the LAN Communication via Ethernet up to 15 characters 0 0 0 0 X LAN_DNS Address of the...

Страница 15: ...remote FTP server up to 29 characters empty X X FTP_Password Password for connation to remote FTP server up to 29 characters empty X X FTP_Port Port used for connation to remote FTP server 21 X X FTP...

Страница 16: ...ote server To ensure consistency between the server and the unit it is advisable to delete the unit s configuration file prefixID_config ini from the remote server as soon as any local modification is...

Страница 17: ...ore connecting the WebdynPulse gateway up to your network Connecting to the built in Web interface 1 Once your computer has been correctly configured 2 Launch your Web browser Internet Explorer Firefo...

Страница 18: ...ng home page is displayed If the gateway is not yet operating the following message is displayed General configuration The Configuration page allows you to Choose the Web interface language Configure...

Страница 19: ...ateway when interacting with the FTP server The names of the files available on the server will be prefixed with the value of this variable so as to link them to the gateway i e the site concerned The...

Страница 20: ...he IP address IP of the device that establishes the connation to the Internet In general the address entered here is that of the router or ADSL modem DNS enter the address of the DNS server The DNS Do...

Страница 21: ...ame of the directory for downloading new firmware default BIN Allow configuration files to be replaced on FTP server if this box is checked the local gateway configuration takes precedence over the re...

Страница 22: ...pn apn_name usr user_name pwd password Where apn_name Name of the APN user_name User ID for access to the APN password Password for access to the APN SMS to configure the remote FTP server Send the fo...

Страница 23: ...r2 IP address for the backup NTP server up to 29 characters empty An option to force NTP resynchronization after a restart following a power failure is enabled by setting to 1 the variable NTP_SyncPow...

Страница 24: ...connection manually by using a tool to press and hold the push button labelled INSTALL until the SERVICES LED begins to flash rapidly Connection via the built in Web server You can force a connection...

Страница 25: ...The variable Connection_Minute is used to specify the minute number within the hour for the connection If 0 connection every day at the time specified by the variables Connection_Hour and Connection_...

Страница 26: ...to the parameters for connecting periodically or at fixed times as shown in the foregoing chapters Example Configuration Connection_OnDataAcquisition 1 Connection_Period 0 Connection_Hour 23 Connectio...

Страница 27: ...he gateway can be programmed not to analyses the configuration and definition directories on every connection Where the variable Connection_Period is zero the time for the analysis is defined by the v...

Страница 28: ...7 1 Wiring The WebdynPulse has 3 index inputs for pulse counting or relay switching detection The gateway manages Class A and B pulse outputs according to IEC 62053 31 1998 standard To avoid damage t...

Страница 29: ...s must be declared in the configuration file prefixID_daq ini This can be done automatically on generation of the file prefixID_daq ini It can also be modified manually by altering the fields listed b...

Страница 30: ...me_IO_N coeffA_N coeffB_N actionN Variable Definition Comments Default value DAQ_Period Collection interval in minutes common to all data sources Inverters TIC I O Modbus Possible value from 0 to 59 m...

Страница 31: ...N Type of input output 1 analogue input 0 10 V or 4 20 mA 2 bang bang input 3 switching relay output 4 pulse counting input name_IO_N Name of the input output coeffA_N and coeffB_N Physical conversion...

Страница 32: ...y It is advisable to check that input ports are operating correctly after they have been installed and configured This can be done via the built in Web server by going to the Control Input Output menu...

Страница 33: ...format year month day hour minute second 7 6 2 Format of input data The file format is as follows fields in green are optional data that can be enabled or disabled in IDSite_daq ini TypeIO fileDefini...

Страница 34: ...s B pulse meter connected to the input 3 TypeIO WD004DC2_IO ini 19 11 13 17 20 00 0 10 46 With the definition file prefixID_IO ini 1 1 2 PULSE1 1 0 4 2 2 5 PULSE2 1 0 4 3 3 6 PULSE3 1 0 4 On the serve...

Страница 35: ...mp when the alarm was triggered in the format YY MM DD hh mm ss AlarmSourceN source that triggered the alarm here I O fileDefinitionName_N name of the definition file associated with the trigger typeI...

Страница 36: ...llowing message is displayed 4 Click on OK and wait until the file download onto the gateway is complete 5 Once the download has finished the following page is displayed 1 Click on Restart 2 The gatew...

Страница 37: ...m the front end application that an action has been performed on the FTP server such as upload or download of files These calls are optional 9 1 Enabling and configuring The use of Web Services can be...

Страница 38: ...on php MAC ADR MAC address Automatic attribution of the site number MAC address format XX XX XX XX XX XX HTTP response ReturnCode IDsite The return codes of the responses from the HTTP server may be 0...

Страница 39: ...that the file INV ini has been uploaded to the FTP server confirm php NSITE IDsite ACTION CMD RC 0 RC COMP Informs the HTTP server that a CMD file has been downloaded from the FTP server confirm php...

Страница 40: ...ble in a configuration file FTP connection failed Error connecting to the FTP server GPRS signal RSSI Level of the GSM signal 1 to 31 Firmware version version Current version of the firmware Restart G...

Страница 41: ...send debug file failed filename Upload of debug trace file filename unsuccessful FTP send parameters file OK filename Upload of parameter file filename successful FTP send parameters file failed filen...

Страница 42: ...de o SIM PUK The SIM card is waiting for a PUK code after three unsuccessful attempts to enter a PIN code o SIM ERROR No SIM card has been inserted Signal level Quality of the GSM signal range 1 to 31...

Страница 43: ...n ACTIVITY Operational status of the gateway On continuously hardware version V2 Power on Flashing rapidly Initialization PULSE x3 Activity on Pulse inputs Off continuously No configuration On continu...

Страница 44: ...nable initial diagnosis of a problem with the WebdynPulse SMS Description connect Requests a connection to the remote server version Requests the current software version of the unit reboot Initiates...

Страница 45: ...ved for use by Webdyn in support mode 5 Log_RemoteIpAddr Syslog destination address Reserved for use by Webdyn in support mode up to 15 characters empty Log_Port Syslog destination port Reserved for u...

Страница 46: ...ow 1 Turn off the power supply to the unit 2 Open the casing of the WebdynPulse to gain access to the configuration DIP switch 3 Set DIP switch 2 to ON 4 Turn on the power supply to the unit 5 Wait fo...

Страница 47: ...ion 2 0 26 Rue des Gaudines 78100 Saint Germain en Laye France Tel 33 1 3904 2940 Fax 33 1 3904 2941 E mail support webdyn com Website http www webdyn com We shall require the following details Serial...

Отзывы: