UNI 4 Installation Instructions
8 Installation of control panel CI 60/600
8.1 Content
8.2 Installation of CI60/600
CAUTION!
The control panel must be connect-
ed to the ventilation unit before the ventilation
unit is connected to mains.
!
Lay the cable for the control panel between the ventilation
unit and the control panel. The control panel is adapted for
concealed installation over a single connection box (use low
back piece, item no. 2) or surface installation on the wall (use
high back piece, item no. 3).
Click the cable into the contact at the back of the control
panel and into the contact on the top of the ventilation unit.
It is possible to connect two CI60 panels and one CI600
panel to each unit. If several CI60 panels are used, each
panel must have its own identity. This is selected with the
switch on the panel’s printed circuit board (se Fig. 20). Use
the appropriate table settings. The panels can be connected
serially, in arbitrary order.
OFF = MASTER
ON = SLAVE
ontent
1
2
3
4
5
NB!
The low-voltage cable must be placed at
least 30 cm from cables carrying mains voltage
or higher. With concealed installation, the cable
is laid in 20 mm conduit pipes. The cable length must
not exceed 24 meters.
1.
Control panel
2.
Back piece for concealed installation
3.
Back piece for surface installation
4. Installation
instructions
5.
Cable for control panel
Fig. 19
Fig. 20
ON OFF
Configuration
Setting
CI 600 (MASTER)
CI60 1 (SLAVE)
CI60 2 (SLAVE)
Automatic
OFF
ON
CI60 1 (MASTER)
CI60 2 (SLAVE)
OFF
ON
CI 600 (MASTER)
CI60 (SLAVE)
Automatic
Irrelevant