9.2  Adjustment with CI600 

9.2.1 Adjustment 

Only stage 2 (NORMAL) needs to be adjusted. 

Note that it is also possible to adjusted stages 1 and 3 
with a CI600 control panel. This should only be done if a 
special need arises, however. This is because it is extremely 
important to have adequate air flow rates.

The function of the different stages:

MIN

Must not be used when the home is in use. Must 
not be used in the first two heating seasons.

NORMAL

Used under normal conditions. On this setting 
the air supply must be adjusted according to 
current regulations. 

MAX

Used if there is a need for increased air supply 
on account of higher occupancy or a raised 
humidity level, for example during showering 
or when clothes are being dried. This setting is 
normally used for limited periods.

First go to the "Advanced user" menu, enter the PIN and 
press OK:

PIN CODE

OK?

1  0  0  0

Then go to the "Fan control" menu. The fans are selected and 
configured in this menu screen.  Then go to adjustment of 
the extract air fan and supply air fan.

FAN REGULATION

SUPPLY AIR
EXTRACT AIR
TIMER
AIR VOLUME COMP

 

>
>
>
OK?

This dialog is identical for the supply air and extract air fans. 
The fans are adjusted individually to the desired capacity for 
the respective speed.

SUPPLY AIR

MIN SPEED
NORMAL SPEED
MAX SPEED

OK?

50%
75%
100%

Factory settings for supply air/extract air:

MIN

50% (variable)

NORMAL

75% (variable)

MAX

100% (variable)

9.2.2 Temperature 

regulation

In this menu screen (located under "Advanced user") you 
configure the temperature regulation and cooling functions.

TEMPERATURE REGULATION

REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL

>
>
OK?
>

Regulation type

If supply air regulation is selected, no further settings can 
be set here. If extract air regulation is selected, the max. and 
min. supply air temperatures can also be specified.

REGULATION TYPE

REGULATION
MAX SUPPLY AIR  TEMP
MIN SUPPLY AIR TEMP

 

EXTR OK?
35°
15°

UNI 4 Installation Instructions

The unit's air supply MUST be adjusted before 
the unit is used for the first time. This should 
be done in accordance with the projection 

documents. Adjust the values based on the projected 
values.

Содержание SPIRIT UNI 4

Страница 1: ...110674E 12 2016 11 Installation Instructions Air Handling Unit Automatic Control Spirit UNI 4 A...

Страница 2: ...g off CI600 16 9 Adjusting the unit 17 9 1 Adjustment with CI60 17 9 2 Adjustment with CI600 18 9 2 2 Temperature regulation 18 10 Installation of external kitchen hood 19 10 1 Kitchen hoods without a...

Страница 3: ...o label the product itself and in the installation and user documentation Important Safety Instructions UNI 4 Installation Instructions This appliance can be used by children aged from 8 years and abo...

Страница 4: ...yout and placement of the water battery channel battery must be planned These must be kept warm to avoid frost damage See separate instructions that accompany the water battery 1 3 Electrician Power s...

Страница 5: ...ll that has no room on the other side that is sensitive to noise The wall should be soundproofed with for example rock wool to reduce the transfer of sound Double plasterboard in the wall cut off stud...

Страница 6: ...UNI 4 Installation Instructions 2 3 Loft installation If needed the rear door of the ventilation unit can be removed temporarily leaving the depth of the unit at 484mm in compliance with minimum trapd...

Страница 7: ...ections for outdoor air can be moved to the bottom of the unit if desired by exchanging the ducts and covers See chapter 4 and chapter 12 3 for information about moving ducts as well as duct placement...

Страница 8: ...ail Fig 7 Hold the unit at an angle when hooking it onto the wall The upper edge of the wall bracket should be mounted 65 mm higher than the top of the unit If one desires for example that the top of...

Страница 9: ...ith the enclosed screws when the door is closed see Fig 8 and 9 The strap is attached to the inside of the door and the inside of the unit see Fig 10 There are attachment points both in the left and r...

Страница 10: ...h suitable space for servicing and maintenance such as filter replacement and cleaning of fans and recovery system see Fig 12 Control cable with plug for automatic control must be easily accessible Th...

Страница 11: ...with two end studs and a strap The end studs are screwed on with the enclosed screws when the door is closed see Fig 13 and 14 The strap is attached to the inside of the door and the inside of the uni...

Страница 12: ...sation it is particularly important for the outdoor and exhaust air ducts to have insulation and a plastic sleeve pulled right down to the unit Seal the plastic sleeve to the unit with ties All ducts...

Страница 13: ...e cable in place on the outside of the duct so that it stays in place See wiring diagram enclosed with the unit 6 Plumbing work If the unit shall have heating with water battery All plumbing work must...

Страница 14: ...adiated noise from the unit specified in the sound data does not include possible noise from ducting The cover should therefore be soundproofed too 7 2 Flexit duct cover The Flexit duct cover is avail...

Страница 15: ...0 panels and one CI600 panel to each unit If several CI60 panels are used each panel must have its own identity This is selected with the switch on the panel s printed circuit board se Fig 20 Use the...

Страница 16: ...itable for installation Screw the back piece to the wall with suitable screws Click the cable into the control panel from below where there is a socket in the printed circuit board se Fig 29 Fig 22 Fi...

Страница 17: ...b 9 is used for supply air level and knob 8 for extract air level see Fig 26 The adjustment range is 20 100 of the maximum level according to the scale on the knob Factory settings for supply air extr...

Страница 18: ...Then go to adjustment of the extract air fan and supply air fan FAN REGULATION SUPPLY AIR EXTRACT AIR TIMER AIR VOLUME COMP OK This dialog is identical for the supply air and extract air fans The fan...

Страница 19: ...hood is regulated according to the planned air flow rate Flexit s kitchen hoods handle odour absorption up to 150 m h It is not necessary to compensate for the supply air fan to achieve a balanced ai...

Страница 20: ...mostat manual reset F20 Overheating thermostat automatic reset FI1 Supply air filter FI2 Extract air filter M1 Supply air fan M2 Extract air fan HR R Heat recovery system M4 Rotor motor K Kitchen hood...

Страница 21: ...m 9 M4 Rotor motor 10 Control unit 11 Connection for external kitchen hood 12 Temperature sensor supply air 13 Temperature sensor outdoor air 12 4 General picture without heating element left model 1...

Страница 22: ...5 W Rated power electric battery 1300W Rated power fans 175W x 2 175W x 2 Rated preheating power Fan type Backward curved fans Backward curved fans Fan motor control 0 10V 0 10V Fan speed max rpm 2930...

Страница 23: ...23 UNI 4 Installation Instructions 14 Physical dimensions 700mm 505mm 484mm 540mm 120mm 125mm 160mm 141mm 211mm 381mm 780mm 450mm 900mm Fig 24...

Страница 24: ...80 60 40 SFP 0 75 112670 112671 0 7 12 18 25 0 13 20 28 37 0 20 40 60 80 100 120 140 160 180 200 0 20 40 60 80 100 120 140 160 180 200 0 100 200 300 400 500 600 700 800 0 100 200 300 400 500 600 700...

Страница 25: ...lue LwA 70 dBA 21 dBA 49 dBA which is then speci ed in LwA sound effect level adapted to the ear s A band EXAMPLE 2 Radiated sound in Lw per octave If at the working point you read off 70 dBA in the s...

Страница 26: ...ts have been tested in accordance with parts of 2006 42 EC Machinery Directive Safety Producer FLEXIT AS Televeien 15 1870 rje Type UNI 4 R Ventilation unit Compliance with valid versions of the follo...

Страница 27: ...27 UNI 4 Installation Instructions...

Страница 28: ...Flexit AS Televeien 15 N 1870 rje www exit no...

Отзывы: