18
9.2 Adjustment with CI600
9.2.1 Adjustment
Only stage 2 (NORMAL) needs to be adjusted.
Note that it is also possible to adjusted stages 1 and 3
with a CI600 control panel. This should only be done if a
special need arises, however. This is because it is extremely
important to have adequate air flow rates.
The function of the different stages:
MIN
Must not be used when the home is in use. Must
not be used in the first two heating seasons.
NORMAL
Used under normal conditions. On this setting
the air supply must be adjusted according to
current regulations.
MAX
Used if there is a need for increased air supply
on account of higher occupancy or a raised
humidity level, for example during showering
or when clothes are being dried. This setting is
normally used for limited periods.
First go to the "Advanced user" menu, enter the PIN and
press OK:
PIN CODE
OK?
1 0 0 0
Then go to the "Fan control" menu. The fans are selected and
configured in this menu screen. Then go to adjustment of
the extract air fan and supply air fan.
FAN REGULATION
SUPPLY AIR
EXTRACT AIR
TIMER
AIR VOLUME COMP
>
>
>
OK?
This dialog is identical for the supply air and extract air fans.
The fans are adjusted individually to the desired capacity for
the respective speed.
SUPPLY AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
OK?
50%
75%
100%
Factory settings for supply air/extract air:
MIN
50% (variable)
NORMAL
75% (variable)
MAX
100% (variable)
9.2.2 Temperature
regulation
In this menu screen (located under "Advanced user") you
configure the temperature regulation and cooling functions.
TEMPERATURE REGULATION
REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL
>
>
OK?
>
Regulation type
If supply air regulation is selected, no further settings can
be set here. If extract air regulation is selected, the max. and
min. supply air temperatures can also be specified.
REGULATION TYPE
REGULATION
MAX SUPPLY AIR TEMP
MIN SUPPLY AIR TEMP
EXTR OK?
35°
15°
UNI 4 Installation Instructions
The unit's air supply MUST be adjusted before
the unit is used for the first time. This should
be done in accordance with the projection
documents. Adjust the values based on the projected
values.