| 15
4.3.4. REGULATION T-box - ELIS B-E WIRING DIAGRAMS
Power supply 3x400V/50Hz
•
ELiS B-E-100 (min. 5x2,5 mm
2
) (Overcurrent B16)
•
ELiS B-E-150 (min. 5x4,0 mm
2
) (Overcurrent B20)
•
ELiS B-E-200 (min. 5x4,0 mm
2
) (Overcurrent B25)
T-box (LIYCY-P 2x2x0,5 mm
2
)
Door contact DCe/DCm (door closed
– contacts opened; door
opened
– contacts closed) (OMY 2x0,5 mm
2
)
ATTENTION:
Switch 4 on SW3 to the position “E” and then restart the system
switching it off for 5 seconds. Each time the device is switched off the
heaters are being cooled for next 30 seconds.
NOTE :
In last DRV in line, dipswitch SW2 has to be switched to the
right
– T120.