Printed in U.S.A.
Page 6B
MODEL 6700 Downflow - V2.0
Option Setting Level #2
Softener Manufacturer Programming (Cont’d.)
9.
Timed Auxiliary Output Window #2 Setting (r)
Depress the Program Button. This option setting
consists of two displays. The first display is used to
set the turn on time of the output, referenced to the
start of Backwash. The second display is used to set
the output turn off time, referenced again to the start
of Backwash. An OFF setting cancels this setting. A
set on time with a set off time of S will turn the output
off at the start of Service. All settings are in minutes
and output timing is synchronized with regeneration
cycle timing.
Examples: Activate output 15 min. after the start of
Step #1/Deactivate when in Service -[r - - - 15.0]
[- - - - - - S]
Cancel setting - [r - - -OFF]
The UP and DOWN Set Buttons will adjust this
value.
10. Chemical Pump Output (n)
Depress the Program Button. This option setting
consists of two displays. The first display is used to
set the turn on time (in minutes) of the output. The
second display is used to set the volume of water flow
at which the output will turn on.
Examples: Activate output 1.0 min. after every 200
gallons -[n - - - - 1.0]
[ 200]
Activate output 1 second after every 200 gallons -[n -
- - - - P] (Pulse Mode)
[ 500]
Cancel setting -[n - - - OFF]
The UP and DOWN Set Buttons will adjust these
settings.
11. Regeneration Day Override (A)
Depress the Program Button. The next display is used
to set the Regeneration Day Override Option Setting.
The Regeneration Day Override Option Setting sets
the maximum amount of days that the conditioner can
be in service without a regeneration, regardless of
water usage or the lack of a sensor signal.
Regeneration begins at the set regeneration time or
at the previous regen time. An OFF setting will cancel
this option with all regeneration types except Time
Clock Regeneration. A day override setting is
required for time clock regeneration valves.
Examples:
Override every 7 days -
[A - - -
- - 7]
Cancel Setting -
[A - - -
OFF]
The UP and DOWN Set Buttons will adjust this
value.
12. Volume Override (b)
Depress the Program Button. The next display viewed
is used to set the maximum amount of water that can
be used before a regeneration cycle is called for.
When this feature is used with delayed regeneration
systems, it will be up to the programmer to determine
a reserve capacity. The control will no longer keep
track of the reserve capacity. This option is typically
used to bypass standard reserve or capacity
calculations made by the control.
Examples:
Override every 700 gallons -
[b - - -
700]
Override cancelled -
[b - - -
OFF]
The UP and DOWN Set Buttons adjust this value.