m)  Evenly tighten the tensioning nuts to tension both cables and pull the fire snugly against the  

wall.  Do not overtighten, it is only necessary to pull the seal up against the sealing face of the 
wall, it does not need to be compressed.  Check that there are no gaps behind the seal. 

 
n)  With the fire securely in place, if a concealed gas connection has been made through either of 

the access holes in the sides of the fire, the holes should be closed around the pipe to prevent 
leakage of air through the gap around the pipe. 

 
o)  Refit the burner in the reverse order using the four M4x 6mm pozi pan screws. 

 

p)  Refit Top Infill Panel, Pilot Heat Shield and Glass Frame as shown in section 4 

 

q)  Before making the final gas connection, thoroughly purge the gas supply pipework to 

remove all foreign matter, otherwise serious damage may be caused to the gas control 
valve on the fire

 
 
2.3  GAS TIGHTNESS AND BURNER PRESSURE  
 
a)  Remove the pressure test point screw from the inlet elbow and fit a manometer. 
 
b)  Turn on the main gas supply and carry out a gas tightness test. 
 
c)  Depress the control knob and turn anti-clockwise to the position marked pilot.  Hold in the 

control knob for a few seconds to purge the pipe work then press the igniter button.  The 
burner should light, continue to hold the control knob for a few seconds then turn to the full-on 
position. 

 
d)  Check that the gas pressure is 20 mbar (+/- 1.0mbar) 8 in w.g.(+/- 0.3 in w.g.). 
 
e)  Turn off the fire, remove the manometer and refit the pressure test point screw.  Check the 
 

pressure test point screw for gas tightness with the appliance turned on using a suitable  

 

leak detection fluid or detector.  

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание Atlanta FAVRU0MN

Страница 1: ...0161 620 6677 ATLANTA DECORATIVE RADIANT NATURAL VENT GAS FIRE Installation and Maintenance Instructions Hand these instructions to the user Model No FAVRU0MN is only for use on Natural Gas G20 at a...

Страница 2: ...re fabricated twin wall metal flue boxes 7 1 10 Hearths 7 1 11 Spillage Monitoring system 7 Section 2 Installation of Fire 2 1 Unpacking the fire 8 2 2 Installing the fire box 8 11 2 3 Gas tightness a...

Страница 3: ...mbar 8 0 0 4 in w g Ignition Push button Piezo Electrode Spark Gap 4 0mm Weight without fender 16 0kg Fire box dimensions without trim Width 470mm Height 583mm Overall Depth 165mm Trim dimensions Over...

Страница 4: ...ally required for this appliance For use in I E this appliance must be installed in accordance with the rules in force and used only in a sufficiently ventilated space Please consult document I S 813...

Страница 5: ...inside of the chimney flue is in good condition along it s length and check that there is no leakage of smoke through the structure of the chimney during and after the smoke pellet test With pre cast...

Страница 6: ...ee fig 2 below Fig 2 1 7 FITTING TO FIREPLACES WITH EXISTING CHAIRBRICKS AND CONVENTIONAL BRICKBUILT CHIMNEYS This appliance is suitable for use in fireplaces fitted with an existing chairbrick withou...

Страница 7: ...e box must have a minimum flue diameter of 125mm internal and minimum internal dimensions of 380mm deep by 650mm high by 480mm wide There are no maximum dimensional requirements for the box The top fa...

Страница 8: ...E FIRE BOX a Remove the Top Infill Panel Pilot Heat Shield and Glass Frame as shown in section 4 to allow access to the burner b Ensure that the hearth is protected from damage and carefully lift the...

Страница 9: ...ller to deal with any type of installation The preferred method of fixing which is suitable for almost all situations is the cable fixing method which is described in the following section in detail T...

Страница 10: ...e protected surface of the hearth and reach into the fire opening Thread each of the cables vertically downwards through the pair of fixing eyes on the same side of the fire Thread the free end of the...

Страница 11: ...efore making the final gas connection thoroughly purge the gas supply pipework to remove all foreign matter otherwise serious damage may be caused to the gas control valve on the fire 2 3 GAS TIGHTNES...

Страница 12: ...igh position and the main burner will light e Turn the control knob clockwise to the low position and the gas input will be reduced to the minimum setting f Slightly depress the control knob and turn...

Страница 13: ...ected from the gas supply and expert advice obtained e If there is an extractor fan fitted anywhere in the vicinity of the appliance the spillage test should be repeated with the fan running on maximu...

Страница 14: ...g screws which hold the pilot shield in place d Unscrew and remove the four screws which retain the burner Carefully pull forwards the burner control assembly and remove from fire box e Refit in the r...

Страница 15: ...ion 4 1 b Unscrew and remove the thermocouple retaining nut from the end of the control tap and disconnect the ignition lead from the pilot electrode c Unscrew pilot tube nut and disconnect pilot pipe...

Страница 16: ...mp cloth Black painted metal parts should be gently cleaned with a damp cloth Abrasive cleaners chemical cleaning agents or any type of polish must never be used as damage to the paint may result CLEA...

Страница 17: ...www heating spares co Tel 0161 620 6677 17 REPLACEABLE PARTS Replacement of any parts must be carried out by a competent person such as a CORGI registered gas installer Replacement Pilot Assembly Part...

Страница 18: ...provement and development the exact accuracy of illustrations and descriptions contained in this book cannot be guaranteed Part no 84 38080 Issue 7 CFM Europe Ltd Trentham Lakes Stoke on Trent Staffor...

Отзывы: