Page 18
Procedure 4-2 Connecting the Power Cables
WARNING:
WHEN PERFORMING ANY TASKS INVOLVING THE POWER SYSTEMS,
MAKE SURE THAT THE POWER IS NOT LIVE. ALL POWER OPERATIONS
SHOULD BE PERFORMED BY QUALIFIED PERSONNEL ONLY.
1.
Locate the DC power connection point and the DC return connection point. See
Figure
4.7 Power Connections Viewed from inside the Cabinet
and
Figure 4.8 Schematic View of
Power Connections
.
2.
Connect the power cable to the connectors with 6 AWG wire with a 2–hole lug for a 1/4”
diameter stud.
3.
Fasten the lug on to the stud with the nuts provided. Tighten nuts to 40–50 in-lb torque.
4.
Connect the other end of the cable to the DC power source.
RadioRouter
®
BaseStation Installation Guide — Draft
Version 0.5 - © 2003