background image

 

 

 

84 | 

P a g e

 

 

HOME AUTOMATION 

The Flare Fireplace can be operated through an external source such as a smart home (home automation) system by using the 5-
pin connector on the receiver. 

The Flare Home Automation Cable (below) must be used between the Flare receiver and the home automation system. Position 

the home automation system so that the Flare Home Automation Cable can be connected directly. 

DO NOT EXTEND OR SPLICE. 

The millivolt system will not work properly if the cable is extended or spliced.

 

 

 

 

 

 

 

Signal relays (gold contacts) or opto-couplers are recommended but not supplied. The Flare Home Automation Cable must be 

connected to the three smart home system contacts as shown below.  

Please contact Flare Support for additional information 

on appropriate relays to be used.

 

Operation  

 

To start ignition, close contacts 1 and 3 simultaneously for 2 
seconds. 

 

To set the valve to High Fire, close contact 1. 

 

To set the valve to Pilot, close contact 3. In each case, the 
contacts need to be closed for 12 seconds to turn the motor from 
one end-stop to the other end stop. 

 

To set the valve to the Off position, close contacts 1, 2, and 3 
simultaneously for 1 second.  
 

Modes of operation

 

Mode 1

 - the external s

ource provides “

ON 

“and

 

“OFF “operation

 only. The remote-control handset provides all other functions. 

Note: Even if the fire is switched on by the external source, the handset, in the thermostatic mode, controls the room 
temperature. The room temperature setting of the handset will remain the same for the next ON-cycle of the external source if 
the temperature setting in the handset has not been changed. If the handset is in manual mode, it will go to High Fire in the next 
cycle of external operation. 

Mode 2

 - The handset must be set to the manual mode if the external source is to control the room temperature. If the handset is 

placed in the thermostatic mode, it will override the external source. 

 

 

CAUTION 

DO NOT CONTROL FIREPLACE FROM OUTSIDE OF HOME USING EXTERNALLY CONNECTED DEVICE 

ONLY OPERATE 3

RD

 PARTY APPLICATION OR HOME AUTOMATION WHEN YOU CAN PHYSICALLY SEE THE FIREPLACE TURNING ON & OFF.  

IT IS NOT MEANT TO OPERATE WITHOUT LINE OF SIGHT TO FIREPLACE 

Содержание Flare Corner Right & Left 30-100"

Страница 1: ...by qualified certified NFI personnel Massachusetts The piping and final gas connection must be performed by a licensed plumber or gas fitter in the State of Massachusetts Also see Carbon Monoxide dete...

Страница 2: ...LACE 18 INTERNAL GLASS REMOVAL 19 SIDE GLASS TRIM REMOVAL INSTALLATION FLARE H EH 21 REFLECTIVE BACK INSTALL 22 INSTALLATION STEPS 23 INSTALLATION PREPARATION 24 ACCESS PANEL 24 FIREPLACE UNPACKING 25...

Страница 3: ...STRUCTIONS 59 Power requirements 59 TELEVISION MOUNTING ABOVE FIREPLACE 60 TV INSTALL FLAT EXAMPLE 61 TV INSTALL L TYPE EXAMPLE 62 TV INSTALL RECESS 45 DEGREE ELBOW ON TOP OF THE UNIT 63 TV INSTALL WI...

Страница 4: ...DOUBLE GLASS AND POWER VENT 86 DOUBLE GLASS BOARD LED LIGHT GUIDE 87 ELECTRIC DIAGRAM PV SYSTEM 88 REPLACEMENT PARTS 89 MAINTENANCE 90 APPENDIX 92 MAINTENANCE LOG 92 MAXITROL TROUBLESHOOTING GUIDE FOR...

Страница 5: ...5 P a g e SAFETY INFO AND WARNINGS...

Страница 6: ...Fuels used in gas wood burning or oil fired appliances and the products of combustion of such fuels contain chemicals known to the State of California to cause cancer birth defects and other reproduc...

Страница 7: ...ve been certified and tested to work with Natural Gas or Propane Certification Information ANSI Z21 88 CSA 2 33 2014 Vented Gas Fireplace Heaters CSA CLASSES CLASS 2901 84 CLASS 2901 04 All fireplaces...

Страница 8: ...DuraVent direct vent installation manual http www duravent com For details on ICC direct vent installation please use the ICC installation guide http icc chimney com en exceldirect support This produc...

Страница 9: ...9 P a g e FIREPLACE OPERATION REMOTE CONTROL INSTRUCTIONS...

Страница 10: ...10 P a g e...

Страница 11: ...11 P a g e...

Страница 12: ...12 P a g e...

Страница 13: ...move the batteries from the battery box This could cause a short circuit to the system PAIRING REMOTE WITH FIREPLACE RECEIVER Your remote will come paired with the fireplace receiver to allow for oper...

Страница 14: ...ncrease the flame height Decrease the flame height Note that the thermostat and programming functions are not available with the wall switch The fireplace receiver will respond to both the wall switch...

Страница 15: ...t cover view open to be able to view the pilot spark and flame from outside Fireglass a or Fire Glass may be used b When the fireplace viewing window is open and media is placed make sure Fire Glass d...

Страница 16: ...oxes 5 Pcs 9 Bags 4 Small 3 Large 1 Bag 45 10 Lbs 13 Lbs 3 Boxes 7 Pcs 12 Bags 6 Small 3 Large 1 5 Bags 50 11 Lbs 18 Lbs 4 Boxes 9 Pcs 15 Bags 7 Small 5 Large 2 Bags 60 14 Lbs 20 Lbs 5 Boxes 11 Pcs 17...

Страница 17: ...ot viewing glass and is provided with this appliance It must remain installed for the protection of children and other at risk individuals Do NOT operate the fireplace without the safety screen barrie...

Страница 18: ...be done once during install only Attach glass suction cups to the glass Use more than one suction cup if needed any unit above 45 Using suction cups slightly push in the external glass top edge Once g...

Страница 19: ...licensed or qualified service person Step 1 Attach glass suction cups to the glass Remove the glass lower magnetic trim Place the trim in a secure place Any unit above 45 requires 2 suction cups to ho...

Страница 20: ...4 1 Step 4 2 When putting back the glass DO NOT overtighten the bolts or glass may break Use step 4 1 for putting the glass back Glass trim screws should be closed hand tight DO NOT overtighten the bo...

Страница 21: ...done with a cold fireplace fireplace appliance turned off and manual gas valve shutoff Unplug the fireplace from any electric power Double Glass Units The below picture shows the right side glass tri...

Страница 22: ...y to clean The reflective back is shipped outside the unit inside a sleeve with the other glass panes It should be mounted at the back of the fireplace placed in the gap between the fire bed shown yel...

Страница 23: ...Put the Fireplace in the desired location Verify clearance to non combustible and combustible materials Follow the clearance instruction and example in the manual 5 For LED units connect LED system an...

Страница 24: ...he necessary parts that may need servicing over time While Flare also offers access to these components by going inside the fireplace with instructions HERE you will find having a dedicated area where...

Страница 25: ...and confirm there is no external damage If damage exists please notify Flare Fireplaces immediately Remove the top wood studs and pull the external carton box up Please do not remove the blue wrap com...

Страница 26: ...LC DC RD front legs will need to be assembled Fireplace must NOT be installed without telescopic legs extracted to a minimum of 3 Installing fireplace without telescopic legs is a fire hazard Install...

Страница 27: ...three screws to secure the telescopic leg in position Note that the top pin inserts into the holes only for alignment The two bottom screws tighten down on the legs Step 5 Repeat Steps 1 4 for each on...

Страница 28: ...the 4 screws so that the fireplace will stand at the desired height after the foot for fine tuning is also screwed in Insert the 4 screws into the holes and Rivnuts beneath and tighten Screw in the fo...

Страница 29: ...test of unit Place accessories white bag in a secure location The control unit gas valve and receiver is attached to the fireplace on an umbilical cord Once fireplace is moved to its final location t...

Страница 30: ...aming Use the manual clearance guide for more details Attach the fireplace top brackets to the metal stud in the back to secure the fireplace in place The bracket length can be adjusted by releasing t...

Страница 31: ...Double Glass unit LED power is connected to the Flare control system Labeled in picture above as LED Power Outlet and below as Connection C LED will turn On and Off with the fireplace controlled by t...

Страница 32: ...re connected prior to shipping Connect LED connectors points A to the fireplace using the quick connect connectors 3 Connect LED control system to the power supply point B 4 Connect LED Power supply t...

Страница 33: ...owning 64 thousand colors 20 automatic changing modes to choose from RBG Strip is using 24V DC power adapter REMOTE MATERIAL 110x52x20mm POWER AAA Battery 2pcs MATERIAL ABS FABRICATION PROCESSING Mult...

Страница 34: ...ITTERS ADJUSTABLE ADJUSTABLE 16 BLUE COLOR FREQUENTLY BLINKS ADJUSTABLE ADJUSTABLE 17 BLUE COLOR GLITTERS ADJUSTABLE ADJUSTABLE 18 YELLOW COLOR FREQUENTLY BLINKS ADJUSTABLE ADJUSTABLE 19 YELLOW COLOR...

Страница 35: ...operation of the blowers is controlled with a power ON Off to the outlet they are connected to The customer has the option to Install a smart outlet to control the blowers Use a wall switch to start...

Страница 36: ...ease use the ICC direct vent installation manual http icc chimney com en exceldirect Instructions Where a vent pipe passes through a floor or ceiling a ceiling firestop MUST be used to retain insulati...

Страница 37: ...e on all horizontal runs to combustibles is required VERTICAL VENT CLEARANCES A minimum of 1 inches 25mm all around the vent pipe on all vertical runs to combustibles is required except for clearances...

Страница 38: ...vent part used Note size of vents depends upon specific fireplace and cutout sizes vary according to the DuraVent or ICC part number used Minimum height from roof to lowest discharge opening Vertical...

Страница 39: ...tiple horizontal terminations See the table on page 32 for minimum cutout dimensions or frame openings around wall venting Make sure clearances to combustible material are maintained based on vent par...

Страница 40: ...aces require 24 inches 61 cm min Clearance to unventilated soffit F 6 15 cm min Clearance to outside corner G 6 15 cm min Clearance to inside corner H 3 90 cm min Not to be installed above a meter reg...

Страница 41: ...r Clearance in accordance with local installation codes and the requirements of the gas supplier As specified in CGA B149 Installation Codes note local Codes or Regulation may require different cleara...

Страница 42: ...The vent restrictor setting is from 1 minimum restriction to 6 maximum restriction The installer will document the restrictor setting in the end of the installation Use the vent planning guide and tab...

Страница 43: ...ers in the table represent the restrictor setting to be set Document the restrictor setting configuration prior to leaving the installation site The tables apply to both NG Natural Gas and Propane Min...

Страница 44: ...44 P a g e FLARE 30 30H Suitable for all Flare 30 Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run may need to be Power Vented...

Страница 45: ...45 P a g e FLARE 45 45H 45EH Suitable for all Flare 45 45H 45EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run may need to be Power Vented...

Страница 46: ...46 P a g e FLARE 50 50H 50EH Suitable for all Flare 50 50H 50EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run may need to be Power Vented...

Страница 47: ...47 P a g e FLARE 60 60H 60EH Suitable for all Flare 60 60H 60EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented...

Страница 48: ...48 P a g e FLARE 70 70H 70EH Suitable for all Flare 70 70H 70EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented...

Страница 49: ...49 P a g e FLARE 80 80H 80EH Suitable for all Flare 80 80H 80EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented...

Страница 50: ...50 P a g e FLARE 100 100H 100EH Suitable for all Flare 100 100H 100EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented...

Страница 51: ...t vent pipes It is critical for the safety and operation of the system to use the DuraVent 3x5 gasket system INLET OPTION 1 Open heat release must not be blocked 10 1 4 259 5 15 1 8 384 3 5 3 5 9 1 2...

Страница 52: ...s less than 20 feet Refer to the Flare Power Vent Installation Manual for more specific instructions Clearance Clearances between the vent pipe and combustible materials must be maintained at 3 inches...

Страница 53: ...w voltage 6V 3 wire cable labeled below as connection Fan Exhust Optional Cable to be used is 16 AWG 3 copper wire not solid wire Cable is not included with the PV kit Connect low voltage cable from t...

Страница 54: ...to or less than 1 2 psig 3 5 kPa Move the appliance into position and secure it to the wall using the back or side mount Install a manual gas valve before the connection to the fireplace appliance au...

Страница 55: ...local codes if any If not available follow ANSI 223 1 Installation should be done by a qualified installer approved and or licensed as required by the locality in the Commonwealth of Massachusetts in...

Страница 56: ...code latest edition GAS VALVE ACCESS DOOR The Flare Fireplace gas valve and control system is on an umbilical cord that can be stretched up to 50 from the middle of the fireplace and be put next to th...

Страница 57: ...n line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY B...

Страница 58: ...lass The design allows cool air to flow between the two layers with the help of built in blowers which significantly lowers the temperature of the external glass making it safe for a brief touch Doubl...

Страница 59: ...Intake are measured for open air space NOTE On all See Through and Room Definer units the air intake must be doubled To reduce you chase and double glass heat increase your heat release air intake abo...

Страница 60: ...to allow cables and other related material to be installed with less concern of blocking hot air flow Use non combustible material for double wall All wires MUST be secured and anchored to the frame t...

Страница 61: ...61 P a g e TV INSTALL FLAT EXAMPLE Warning Maintain open Air flow between the fireplace and wall covers Make sure cables or any other materials are not blocking hot air flow...

Страница 62: ...62 P a g e TV INSTALL L TYPE EXAMPLE Warning Maintain Open Air flow between the fireplace and drywall Make sure cables or any other materials are not blocking hot air flow...

Страница 63: ...a recess up to 4 inches at the top of the glass which will bring the front wall out and allow for space to recess also the TV See an example of this on the previous page 2 Install two 45 elbows direct...

Страница 64: ...below the TV increase the size of the heat release above the minimum required for your unit All measurements shown are minimum requirements Please note that most television manufactures and manuals w...

Страница 65: ...eely at the top of the chase All measurements shown are minimum requirements Please note that most television manufactures and manuals will instruct the owner not to install television above or near a...

Страница 66: ...g e CLEARANCES GENERAL INFORMATION AND STEPS All materials inside the chase and above the Fireplace must be non combustible or covered combustible only See more clearance information in the following...

Страница 67: ...t pipe on all horizontal runs to combustibles is required VERTICAL VENT PIPE CLEARANCES A minimum of 1 inch 25mm around the vent pipe on all vertical runs to combustibles is required Except for cleara...

Страница 68: ...sides and back Covered combustible Combustible material at the back or sides of the fireplace MUST be covered with non combustible material that is at least inch thick Covered wood can be placed a min...

Страница 69: ...e 18 must be covered Zone B There should be no combustible materials left uncovered above the fireplace inside the chase Fireplace chase should be designed and built to allow hot air to release from t...

Страница 70: ...l fireplace frame This can result in excessive heat transfer and or damage to the fireplace and surrounding materials 15 Hearth Clearance Clearance to an uncovered combustible hearth below the glass i...

Страница 71: ...metal fireplace frame This can result in excessive heat transfer and or damage to the fireplace and surrounding materials All joints between the finished wall sheathing and the appliance must be seal...

Страница 72: ...el size and location Use chart and provided table for information on mantel install Do not anchor any mantel or shelf to the fireplace Only use metal studs above the fireplace as anchor points Mantel...

Страница 73: ...e when the room heats up from the fireplace being operated normally Please follow local building code to determine what temperature setting is relevant for your installation WARNING VAULTED CEILINGS C...

Страница 74: ...on combustible fire stop is placed atop the inside of the chase and is framed in a way that does not allow any pockets of heat to be formed All rising heat should be able rise to the fire stop and fre...

Страница 75: ...75 P a g e EXAMPLES OF HEAT RELEASES...

Страница 76: ...E FRONT SEE THROUGH AND CORNER FIREPLACE CLEARANCE FLAT SIDE AND ISOMETRIC VIEW Warning Maintain open Air flow between the fireplace and drywall Make sure cables or any other materials are not blockin...

Страница 77: ...ening to be released back to the room from the top To increase heating the enclosure should prevent hot air from being released to the attic by venting it back to the room using the static vent system...

Страница 78: ...ING Maintain open air between the fireplace and drywall Make sure cables or any other materials are not blocking hot air flow ain open Air flow between the fireplace and drywall Make sure cables or an...

Страница 79: ...f the fireplace glass from lower vent opening to be released back to the room from the top To increase heating the enclosure should prevent hot air from being released to the attic by venting it back...

Страница 80: ...outdoor kit will tolerate moderate amounts of water on an occasional basis but is not waterproof The fireplace must be enclosed in a weatherproof enclosure covered in typical weatherproof material su...

Страница 81: ...place is fully turned off when attempting to clean the front of the fireplace including pilot Use the Flare architectural guide for information on the window size and opening http flarefireplaces com...

Страница 82: ...g e All studs and surrounding should follow the fireplace clearances and non combustible requirements The outdoor window kit should be sealed with non combustible tape prior to covering with brick or...

Страница 83: ...ll to four tabbed charts click DOWNLOAD CENTER BURNER TYPE SIZE cm SIZE in FIREPLACE SIZE OF BURNERS A 55 cm 21 11 16 30 1 B 80 cm 31 12 16 45 1 C 105 cm 40 1 16 50 1 D 125 cm 35 cm 55 cm 35 cm 50 1 1...

Страница 84: ...to be closed for 12 seconds to turn the motor from one end stop to the other end stop To set the valve to the Off position close contacts 1 2 and 3 simultaneously for 1 second Modes of operation Mode...

Страница 85: ...85 P a g e ELECTRIC AND CONTROL ELECTRIC DIAGRAM SCREEN Optional 6V power supply and remote...

Страница 86: ...86 P a g e DIAGRAM DOUBLE GLASS AND POWER VENT BLUE RECEIVER RELAY GREEN RECEIVER AUX...

Страница 87: ...ill bypass the need to verify fan activity The switches are numbered to correlate with the LED lights they are associated with above The final switch is the Master Bypass option Turning this on bypass...

Страница 88: ...88 P a g e ELECTRIC DIAGRAM PV SYSTEM Ports 49 47 are connected to J6 on fireplace main board...

Страница 89: ...le Cable That Creates Spark Spark Cable Spark Ignitor Electrode Ignitor Spark Ignitor Electrode Thermocouple Includes fitting to Thermocouple Valve Housing Thermocouple Pilot Gas Line Includes fitting...

Страница 90: ...ation to the product that causes soot or carbon to form and results in damage is not the responsibility of the manufacturer Do not modify or substitute any part of this appliance Inspect the external...

Страница 91: ...pilot operation and burner ignition Burner Maintenance The flames from the burner should be visually checked The flame should have a blue base and yellow tops and be candle like in appearance If exce...

Страница 92: ...ny Name_________________________________________________________ Technician NPI ________________________________________________________ Service Information ___________________________________________...

Страница 93: ...eiver is surrounded by metal reducing the transmission range Bring remote closer to unit for troubleshooting Limited range of the remote due to local RF transmission Change the position of the antenna...

Страница 94: ...cation along cable Check spark on the receiver by disconnecting the spark cable from the receiver Inappropriate inlet pressure confirm gas pressure is correct rating for NG LPG Air seal issue around p...

Страница 95: ...be Relay cable between the board and the GV 60 Receiver Check wiring diagram for information on relay cable Ensure fan harness is connected to the board If partial double glass fans are not working V...

Страница 96: ...96 P a g e Figure 1 Figure 2 Figure 3 Figure 4 Figure 5...

Страница 97: ...97 P a g e Figure 6 Figure 7...

Страница 98: ...set and back of the receiver are both blue or remote sticker is black and the receiver sticker is green Dead batteries no batteries Bent pins on 8 wire connectors Inspect and straighten pins as needed...

Страница 99: ...gram code Pilot is lit and control continues to spark Valve shuts after 10 30 seconds Over tightened thermocouple interrupter Bad thermocouple Receiver Pilot is lit and sparking stops Valve shuts afte...

Страница 100: ...are low Pilot flame lights but there is no main gas flow Low inlet pressure Valve turned down to pilot flow Turn flame to high fire by pressing up button on remote handset Mail burner line is crimped...

Страница 101: ...ecified in the manual is contrary to the manufacturer s instructions and may void this warranty All installations must be performed by a qualified technician in accordance with applicable local and na...

Страница 102: ...proper chimney or venting installation Holes have been drilled in to the fireplace for any reason Exclusions This warranty does not apply to any component that shows evidence of misuse abuse improper...

Отзывы: