Control parameters
(e.g. can be set via the app):
for thermal disinfection
Value
Adjustment
range
Factory
setting
Notes
Parameter
Mode
1-active
0-inactive
Value = 0
Only achievable in service mode
Thermal
disinfection
setpoint
value
70…80 °C
(return line)
70 °C
Setting of disinfection temperature
(ensures that 70 °C is achieved
throughout the entire system)
Disinfection
hold time
3…60 min
15 min
Mode off once hold time reached
Max. run
time
3…60 min
60 min
Error mode, failed attempts =>3
for domestic hot water circulation
Domestic water circulation
setpoint value (circulation)
20…65 °C
60 °C
Domestic hot water
temperature setting:
set to T5 to T4 > 5K setpoint
value or
set to T4 and T5 must not < 5K
T4 -> error message (see DVGW
AB W-551)
T5 or T4
Time programme with time
windows
3 switch-on and 3 switch-off
times per day, values can be
set separately for each day
Shut-off delay (pulse/
monitoring)
0…60 min 3 min
Can be set on the controller
(preset to 3 min in app)
External switch input
1-active
0-inactive
Value = 0
In addition: Sanitary circulation
with DVGW-compliant design
1-active
0-inactive
Value = 0
Info:
The setpoint value for the domestic hot water temperature is also the setpoint value of the
sanitary circulation temperature.
Warning:
Once domestic hot water has been drawn off, the sanitary circulation is switched off for
20 seconds!
If the maximum hot water temperature of 75 °C is exceeded, an alert is issued and the sanitary
circulation pump switched off.
The sanitary circulation settings must comply with the DVGW guidelines of the country
in question (e.g. in Germany, the DVGW worksheets)!
Содержание LogoTronic HIU V2
Страница 172: ...171 RUS 1 Flamco Meibes 1 1 CE HIU RED 2014 53 EU LVD 2014 35 EU EMCD 2014 30 EU ROHS 2011 65 EU 1 1 1 DIN EN...
Страница 173: ...LogoTronic HIU Controller f r LogoMatic G2 172 1 1 2 1 2 DIN EN 12828 LogoTronic HIU IEC60730 1 1 3 1 4 RoHS 2011 65 EU...
Страница 178: ...177 RUS 7 7 1 230 50 USB 1 2 3 4 5...
Страница 179: ...LogoTronic HIU Controller f r LogoMatic G2 178 7 1 1 A B USB USB USB 1 4 4...
Страница 182: ...181 RUS UPM3 Hybrid 8 MUT 1 MUT 2 VTY10 Molex Mini Fit 3 9x NTC 10K T5 T2 T3 T4 T7 T1 Honeywell AF10 B54 NTC 10K RS485...
Страница 185: ...LogoTronic HIU Controller f r LogoMatic G2 184 LogoMatic G2 1 2 Flamconnect 3 QR A QR 4 B A QR B QR Flamconnect...
Страница 186: ...185 RUS 1 2 Flamco 3 QR LogoMatic G2 4 5 LM G2 Bluetooth 6...
Страница 187: ...LogoTronic HIU Controller f r LogoMatic G2 186 7 8 LogoMatic G2 9...
Страница 188: ...187 RUS 10 CSV 10 1 0 1 0 10 2 5 50 K 5 K...
Страница 191: ...LogoTronic HIU Controller f r LogoMatic G2 190 CSV DIN EN 1264 4 1 21 7 DIN EN 1264 4 3 25 C 4 55 C 1 1 C 55 C 45 C...
Страница 192: ...191 RUS 10 5 TWZ TWZ TWZ TWZ TWZ DVGW DVGW W 551 DIN VDE TWZ 60 8 TWZ 10...
Страница 193: ...LogoTronic HIU Controller f r LogoMatic G2 192 TWZ 3 60 1 TW 80 C TWZ...
Страница 196: ...195 RUS...