3.2.  Parameter menu

Item

Factory setting

Duration of turbo

- Remaining fast run time up to automatic change to normal mode

10 hours

Pause normal degaz

- Duration of pause between end of evacuation time and beginning of 

pump run

15 minutes

- Pause ON (beginning of night pause)

06:00 pm

- Pause OFF (end of night pause)

08:00 am

Degassing

- Pump run time

Pressure dependent [s]

- De-aeration time

60 seconds 

System pressure

- pON: depending on the system type

ENA 7 -> 1.5 bar  

ENA 10 -> 1.5 bar 

ENA 20 -> 3.0 bar  

ENA 30 -> 5.0 bar

- pOFF: depending on the system type

ENA 7 -> 2.0 bar  

ENA 10 -> 2.0 bar  

ENA 20 -> 4.0 bar  

ENA 30 -> 6.0 bar

- Lower pressure limit (lower working pressure limit)

Depending on the 

system type

- Upper pressure limit (upper working pressure limit)

Depending on the 

system type

- Special system pressure (irrelevant for the operator)

 Factory setting

Litres counter

- Litre/pulse: pulse water meter (can be set only by service personnel)

10 litre/pulse

- Error litres counter: monitoring of delay of cycle of litres counter

40 minutes

Water treatment

100 litres

- Treatment capacity in case of integrated water softening module

100 litres

Filling quantity: 

 

Based on a continually referenced preceding period of time (time window), the unit allows using a 

certain number of filling cycles that are separated by pauses from one another. Cycles, pauses and 

time windows (time spending) can be freely parameterised.

Example: (default setting) 

 

In the last 480 minutes (time spending) the make-up water quantity per cycle must not exceed 50 litres. 

Moreover, it is not permissible to supply this quantity during this time more than three times, and the 

pauses between the cycles must be 5 minutes at a minimum.

Item

Factory setting

Max quantity/filling
-  Maximum allowable quantity per cycle (also per cycle) with integrated 

and  

configured pulse water meter. See section Monitoring: make-up quantity

150 litres

Max time/filling

-  Maximum allowable make-up time per cycle (also per cycle). See section  

Monitoring: monitoring of run time

20 minutes

Min. interval betw. 2 cycles

- Minimum interval between two cycles (pause)

5.0 minutes

Max cycles/time spend

- Maximum number of cycles per time window

3

Time spending

- Size of time window

480 minutes

Item

Factory setting

Time and date

Operator task

-  Summer time on: starting month  (summer time ON is 00 for regions 

without change between times)

03

-  Summer time off: ending month (summer time OFF=00 for regions 

without change between times)

10

- Maintenance gap: maintenance interval 0 .. 800 days

365 days

- Pressure sensor min.value

0.0 bar

- Pressure sensor max.value

10.0 bar

Note that the values in the filling quantity menu are interdependent. Therefore, it may be necessary 

to first parameterise another value before the actual value becomes accessible within the intended 

limits. Similarly, setting ranges may be limited by the dependencies. It is advisable, for instance, to 

first parameterise a sufficiently sized time window before defining the pauses and the number and 

length of cycles

3.3. Service menu

Project number

 

Factory settings; not be programmed by the operator.

Software version

 

Readable entry made by manufacturer.

Start

 

Enter the time and date of the start (traceability) by pressing Start. Before pressing, the date and time 

must have been correctly set.

Maintenance

 

The date of the next maintenance is indicated in parentheses. When this time is reached, the 

centralised fault alarm is optionally tripped, and a fault message is displayed to remind the operator. 

If it is acknowledged, it will be displayed again after seven days unless ‘Maintenance done’ has been 

pressed, thus indicating that the maintenance has already been carried out. The time and date of the 

last maintenance as well as the code level are indicated in the upper two lines.

Содержание 17070

Страница 1: ...www flamcogroup com manuals Ena 7 30 ENG Installation and operating manual ...

Страница 2: ...Menu symbols 15 6 3 Working principle controller 16 6 4 Controller inputs 17 7 Maintenance and troubleshooting 18 7 1 Before maintenance 18 7 2 After a power failure 18 7 3 Maintenance interval 18 7 4 Change the automat for water treatment 18 7 5 Error message 19 8 Disposal 21 9 Technical specification 21 9 1 Additional accessories 22 Appendix 1 Commissioning 23 1 1 Commissioning ENA 7 30 23 1 2 P...

Страница 3: ...llation be carried out by qualified personnel Comply with local legislation and guidelines Do not make modifications to the automat without prior written permission of Flamco Make sure that all automat covers and doors are closed when operating the automat Do not touch live voltage The sensor units and the capacity pressure sensors operate with extra low safety voltage Flamco shall not be liable f...

Страница 4: ...evices and check them regular on proper working 2 6 Signs on the automat The signs on the automat are part of the safety provisions Do not cover or remove the signs Inspect regularly if the signs are present and legible Replace or repair signs that are illegible or damaged A B C D On the type plate the following product information can be found A Automat type ENA 10 20 or 30 B Automat serial numbe...

Страница 5: ...ing which the pump is running vacuum is forming alternates with an interval during which the air is discharged pump is stopped Normal deaeration mode An additional pause is added between the end of the evacuation interval and the starting of the pump This additional interval can be selected via a parameter within fixed limits Upon expiry of the deaeration interval the system changes to the normal ...

Страница 6: ...e can support the maximum weight of the automat including the water Refer to chapter 9 Technical specifications The automat may not be affected by external forces No dirt may get into the automat and its accessories Install shut off devices to the drinking water net on site Plan enough free space around the automat for maintenance work Note the effective regulations regarding the use and the insta...

Страница 7: ...ntroller SCU Unscrew the protective cover of the terminal box Pull the power plug or switch off external separators and secure these against a restart The descriptions of the terminal bars are on the inside of the protective cover 5 5 Basic electrical connection ENA 7 ENA 10 Nominal voltage 230 V 6 10 50 Hz 1 1 Nominal current 2 77 A 5 3 A 7 2 A 10 6 A Nominal power 0 62 kW 1 1 kW 1 51 kW 2 2 kW S...

Страница 8: ...ware version 3 Start 4 Maintenance 5 Error list Passive 6 Value statistics 7 Operating hours 8 Refill statistics 9 Change entry code 10 Change access code 11 Data transfer 12 Back Parameter menu F 1 Duration of turbo 2 Pause normal degas 3 Degassing 4 Automatic degassing 5 System pressure 6 Special system press 7 Litres counter 8 Water treatment 9 Re filling quantity 10 Time Date 11 Other 12 Other...

Страница 9: ...ater treatment Level controlled Back G2 1 Deutch Nederlands English Français F 5 System pressure Special syst press Litre pulse Water treatment G 2 19 Dansk Suomi Maggar Back G2 7 Polski Dansk Suomi Maggar F 10 Water treatment Filling quantity Time date Other G 5 Language Liters counter Water treatment Control mode F5 Fillcommand on D 2 Hardware Parameter Service Back X x bar Fillcommand on Save B...

Страница 10: ...oo high Check control Check admission pressure use larger diaphragm expansion vessel Lower filling pressure to working pressure range 3 Entrycap too low Litres counter does not supply water after make up request A No pulses sent from litres counter because litres counter defective cable not co Replace litres counter Connect cable Use higher setting value for response time 5 Cycle interval Make up ...

Страница 11: ...h B Hardware software problem Get in contact with service department 25 Gas sensor defective Gas sensor defective A Malfunctions in measuring signal possible faulty cable connection to SCU Check connection to controller Exchange sensor if necessary 26 Gas sensor undervoltage Signal during Measurement 4mA A Sensor not connected cable damage 27 Gas sensor overvoltage Signal during Measurement 20mA A...

Страница 12: ...ly at the place of erection and in respect of the field of application The party erection and operating the unit will be responsible for making the checks and for carrying out commissioning For commissioning the hydraulic and electric connections must be in place and the shut off devices open 1 2 Parameterisation for commissioning The ENA 7 30 comes with a pre parameterized control As this control...

Страница 13: ...expansion vessel is used When the signal is applied the pump switches on The filling operation takes place until the level set on the control of the expansion vessel is reached 2 2 2 Pressure controlled P Control takes place via the pressure sensor that is integrated in the module When the system pressure has dropped to the activation pressure Fill command on the pump switches on and operates unti...

Страница 14: ...ntity that can be read in litres in the process menu When a quantity of zero litres is reached the centralised fault alarm is tripped and an error message will be displayed Negative values mean that the allowable treatment quantity capacity has been exceeded The make up unit continues to operate even if the centralised fault alarm has been tripped The operator must activate the water treatment fun...

Страница 15: ...mum allowable quantity per cycle also per cycle with integrated and configured pulse water meter See section Monitoring make up quantity 150 litres Max time filling Maximum allowable make up time per cycle also per cycle See section Monitoring monitoring of run time 20 minutes Min interval betw 2 cycles Minimum interval between two cycles pause 5 0 minutes Max cycles time spend Maximum number of cyc...

Страница 16: ... Change entry code Change to another access code For the operator only code 000001 is possible and required Appendix 4 Examples 4 1 ENA 7 30 with NFE1 1 and a diaphragm expansion vessel in a heating system Donotusenominalboressmaller thanindicatedforthelenghts ofthelinesconcerned Thelines shouldbeasshortaspossible DN20 10 m DN25 20 m DN32 30 m 4 2 ENA 7 30 with NFE1 2 and a compressor controlled p...

Страница 17: ...ion may be reproduced or published in any way without explicit permission and mention of the source The data listed are solely applicable to Flamco products Flamco Limited shall accept no liability whatsoever for incorrect use application or interpretation of the technical information Flamco Limited reserves the right to make technical alterations Man_Ena7 30_art nr_17070_eng_2022 08 ...

Отзывы: