Supply air unit VEKA
Integrated Control Equipment Curo
6
Fläkt Woods
9965 GB 2016.09.27
Specifications are subject to alteration without notice
2. ConnECtion of ExtErnAl ComponEntS
2.7 ExtEndEd / forCEd VEntilAtion
For external electronic timer, push button, PIR or other volt free
contact. Electronic timer and/or PIR if ordered is supplied
separately. When using a push button the time has to be set in
the control panel.
Component
designation Connection remark
Timer 1
TMR1
13 - 14
1)
Timer 2
TMR2
15 - 16
1)
1)
Connects directly to the control board.
Function of aux. inputs Timer 1 (T1) and Timer 2 (T2) can be
selected according to the following tables.
timEr funCtion 1 (dEfAult)
timer 1
timer 2
Manual/Automatic Mode
0
0
Trickle
1
0
Normal
0
1
Boost
1
1
timEr funCtion 2
timer 1
timer 2
Manual/Automatic Mode
0
0
Trickle
1
0
Boost
0
1
Stop
1
1
timEr funCtion 3
timer 1
timer 2
Manual/Automatic Mode
0
0
Normal
1
0
Boost
0
1
Stop
1
1
timEr funCtion 4
timer 1
timer 2
Stop
0
0
Manual/Automatic Mode
1
0
Stop
0
1
Boost
1
1
timEr funCtion 5
timer 1
timer 2
Stop
0
0
Manual/Automatic Mode
1
0
Stop
0
1
Normal
1
1
2.8 firE protECtion funCtion
External fire alarm to stop the unit can be connected to terminals
in the control box. Smoke detectors and fire dampers cannot be
connected directly to the air handling unit, a separate fire system
is needed.
Component
designation Connection remark
Fire protection
funcion
FIRE
35 - 36
1)
Voltfree contact (NC)
Looped at delivery
1)
Connects directly to the control board.
2.9 SummAry AlArm
The alarm output can be configured to indicate A-alarms or both
A- and B-alarms.
Component designation Connection remark
Summary
alarm
ALM
11 - 12
1)
Voltfree contact
Maximum load 24 V, 200 mA
1)
Connects directly to the control board.
2.10 ExtErnAl ExhAuSt fAn
External exhaust fan (FF) with frequency converter connects
according to the following table.
Component designation
Connection remark
External
exhaust
fan
Control signal
64 - 65
1)
Y - M
Alarm
23 - 24
1)
Voltfree contact,
(NO, configurable)
1)
Connects directly to the control board.
2.11 filtEr guArd
Filter guard (GP1) connects according to the following table.
Component designation Connection remark
Filter guard GP1
17 - 18
1)
Voltfree contact (NO)
1)
Connects directly to the control board.