Supply air unit VEKA
Integrated Control Equipment Curo
20
Fläkt Woods
9965 GB 2016.09.27
Specifications are subject to alteration without notice
4.7 SChEdulES, Cont.
ExAmplE 2
Below is an example of a weekly schedule configured to run the
fans at normal speed from 08.00 to 18.00 Monday to Thursday,
from 08.00 to 17.00 on Friday and 10.00 to 14.00 on Saturday. At
all other times, the fans are turned off.
day
time
fan speed
Monday
8–1 8
Normal
Tuesday
8–18
Normal
Wednesday
8–18
Normal
Thursday
8–-18
Normal
Friday
8–-17
Normal
Saturday
10–14
Normal
Other time
Stop
4. Control pAnEl, opErAtionS, CommiSSioning
1 Weekly 1
Fan speed
Normal
Temp set point Rel 0°C
From
To
Mon
Fri
Daily
08:00
18:00
2 Weekly 2
Fan speed
Stop
Tem Setpoint Rel 0°C
From
To
Fri
Fri
Daily
17:00
18:00
ExAmplE 3
Below is an example of a weekly schedule configured to run the
fans at normal speed from 08.00 to 18.00 Monday to Friday.
At all other times, the fans are configured to run at trickle speed.
At trickle speed the temperature set point will be decreased by
two degrees.
day
time
fan speed
temperature set point
Monday
8–18
Normal
0 ° C
Tuesday
8–18
Normal
0 ° C
Wednesday
8–18
Normal
0 ° C
Thursday
8–18
Normal
0 ° C
Friday
8–18
Normal
0 ° C
Other time
Trickle (Low)
–2 ° C
3 Weekly 3
Fan speed
Normal
Temp Setpoint Rel 0°C
From
To
Sat
Sat
Daily
10:00
14:00
1 Weekly 1
Fan speed
Trickle
Temp Setpoint Rel -2°C
From
To
Mon
Sun
Daily
00:00
23:59
2 Weekly 2
Fan speed
Normal
Temp Setpoint Rel 0°C
From
To
Mon
Fri
Daily
08:00
18:00
Only Weekly 1–2 should be activated.
Only Weekly 1–3 should be activated.