7. pArAmEtEr liSt
1)
R/W = Read and write value, R = Read only value
parameter
type of value
1)
range
unit
default value Comments
5.7 frost protection
See section 5.3
Pump stop
R/W
Yes/No
–
Yes
No = Pumps always running
Pump Stop mode
R/W
Summer / Winter
Heating / Cooling
Heating /
Cooling
Heating/Cooling = Heating pump is running
when there is a heating demand. Cooling pump
is running when there is a cooling demand.
Summer/Winter = Heating pump is running
when the unit is in winter mode. Cooling pump
is running when the unit is in summer mode.
Exercise of pumps every day at 12.00-12.05.
Constant temp Hot Water Coil
R/W
0-50
° C
25
Low limit running temp, Set point
R/W
0-50
° C
12
Frost Protection Alarm, Set Point
R/W
0-50
° C
7
6. Air quality
6.1 Co
2
Control
Not for VEKA
7. Alarm Configuration
7.1 Alarm Settings
Dirty Filter alarm time
R/W
0-600
days
0
Set to 0 to deactivate the filter alarm
A and B on first Relay
R/W
Yes / No
–
Yes
Enable temperature alarm
R/W
Yes / No
–
Yes
Temperature alarm
R/W
-10 - +10
° C
5
Activate test of RHE belt
R/W
Yes / No
–
No
Not for VEKA
7.2 Alarm cathegorys
Fire Alarm
R/W
A/B
–
A
External function
Sensor Error Supply air
R/W
A/B
–
A
Sensor Error Outdoor air
R/W
A/B
–
A
Sensor Error Extract air
R/W
A/B
–
A
Sensor Error Frost Protection
R/W
A/B
–
A
For unit with Hot Water coil
Sensor Error Defrost
R/W
A/B
–
B
Not for VEKA
Sensor Error AI10
R/W
A/B
–
B
Not for VEKA
Supply Fan Error
R/W
A/B
–
A
Not for VEKA
Extract Fan Error
R/W
A/B
–
A
Not for VEKA
Dirty Filter Alarm
R/W
A/B
–
B
Not for VEKA
Preesure switch RHE
R/W
A/B
–
B
Not for VEKA
RHE Failure
R/W
A/B
–
B
Not for VEKA
Filter Alarm Supply
R/W
A/B
–
B
Filter Alarm Extract
R/W
A/B
–
B
Not for VEKA
Electrical Heater Error
R/W
A/B
–
B
Pump Heater Malfunction
R/W
A/B
–
B
Frost Protection
R/W
A/B
–
B
Alarm Cooling
R/W
A/B
–
B
Pump Cooling Malfunction
R/W
A/B
–
B
Temperature alarm
R/W
A/B
–
A
RHE belt alarm
R/W
A/B
–
A
Not for VEKA