TRANSPORT, MOUNTING INSTRUCTIONS
Beware of damaging the fan while lifting. Always adjust chains/
beams long enough not to get in touch with motor, frequency con-
verter or impeller.
4.4.2 SIZES
≥
080
The fan is to be lifted with four lifting chains/beams, two attached
to the front plate supports and two to the motor bracket. Lifting
points are shown in the picture below.
5 MOUNTING INSTRUCTIONS
5.1 INSTALLATION OF THE FAN
The fan is to be installed to a base frame using anti-vibration
mountings. Alternatively the base could be mounted on anti-
vibration mountings.
The base must be level and stable. The fan must only be mounted
in a horizontal plane.
5.2 BUILT-ON FREQUENCY CONVERTER
If needed, the frequency converter can be removed to the other
side of the fan with the following instructions. Otherwise please
use the cable tie (delivered with the fan) to attach the motor cable
to the motor bracket and mounting plate, see point 5.2.4.
5.2.1 Loosen the upper bolts and remove lower fixing bolts (M6) of
the frequency converter mounting plate. You might need a
10 mm wrench with the upper front bolt.
Upper bolt
Lower bolt
Centriflow 3D GMPM, GMEB - Installation and Maintenance
5
FläktGroup DC_9853GB_20180425_R0