STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils

Fläkt Woods

8713 GB 2014.04

9

Specifications are subject of alteration without further notice.

Shutdown

When the Occupancy button is held depressed for more

than 5 seconds, the controller changes operating mode to

”Shutdown” (Off/Unoccupied), regardless of the current

operating mode. Via the display , you can configure

which operating mode, Off or Unoccupied, should be

activated on ”Shutdown”. The factory setting is that

Unoccupied is activated.
If you press the Occupancy button for less than 5 seconds

when the controller is in operating mode Shutdown

or the preset operating mode, the controller changes

to operating mode Bypass. If you press the button for

less than 5 seconds when the controller is in Bypass, it

changes operating mode to the Preset operating mode.
After a configurable time in Bypass (FS=2 hours), the

controller returns to the preset operating mode.
For handling of the Occupancy button in combination

with central control, see the section Central control below.

Occupancy detector

 

 

For local control of the operating mode between the

preset operating mode and Bypass, an occupancy detector

is connected.
When occupancy is indicated, the controller changes

operating mode to Bypass. If you want to be able to

enter the room temporarily without activating Bypass,

for example to pick something up, you can configure a

powerup delay. This means that Bypass is not activated

until the power-up delay has expired. The Bypass delay

can be set to a value between 0 and 60 minutes (FS=0

min).
In Bypass on presence, there is a switch-off timer, which

means that if there is no occupancy indication during this

time (FS=10 min), the controller will return to the preset

operating mode.

Control states

The controllers can be configured for different control

states/control sequences:
• Heating
• Heating or cooling via the change-over function
• Heating/Heating
• Heating/Cooling
• Heating/Cooling with VAV-control and forced supply

air function
• Heating/Cooling with VAV-control
• Cooling

• Cooling/Cooling
For the control states, UO1 is used for the left control

function and UO2 is used for the right control function.

For control states where only one control function is

active (Heating, Heating or cooling via the change-over

function, and Cooling), only UO1 is used.

Heating

In control state Heating, the unit is always a heating

controller and controls according to the heating setpoint

plus/minus the setpoint displacement. The setpoint can be

adjusted in the display.

Heating or cooling via the change-over function

Like control state Heating but with change-over function,

i. e. when the change-over input is active, the controller

becomes a cooling controller and regulates according

to the basic cooling setpoint plus/minus the setpoint

displacement. See more in the section Change-over.

Heating/Heating

Split output signal

In control state Heating/Heating, the controller is always

a heating controller and controls according to the basic

heating setpoint plus the setpoint displacement. When

the controller output signal reaches 50%, it is divided

between two actuators. 0…48% of the signal is sent to

actuator 1 and 52…100% of the signal is sent to actuator 2.

See the figure below.

 

 

Heating/Cooling

In control state Heating/Cooling, the controller functions

as a heating controller when the room temperature

is lower than the basic heating setpoint plus half the

neutral zone. The neutral zone is the difference in

temperature between the heating setpoint and the cooling

setpoint. When the room temperature exceeds this limit,

the controller becomes a cooling controller. There is a

hysteresis of 0.1°C when the controller changes from

heating to cooling controller and vice versa. When the

controller is heating, it regulates according to the basic

heating setpoint plus the setpoint displacement, and

when it is cooling according to the basic cooling setpoint

plus the setpoint adjustment.

 

Содержание STRA-07 R

Страница 1: ... without further notice Content STRA 07 for Fancoils Installation preparations 2 Controller Display handling 5 Technical data 5 Installation 6 Configuration 6 Operating modes 7 Activation operating modes 7 Control states 8 Actuators 9 Fan control 9 Forced ventilation Condensation detector Frost protection 10 Parameter settings 10 ...

Страница 2: ...ation without further notice STRA 07 for Fancoils Installation instruction Ensure that the installation complies with local safety regulations Information about commissioning of the product can be found in the manual STRA Manual which is available for download from www flaktwoods com 1 2 3 alt 4 5 Dimensions Dimensions in mm ...

Страница 3: ...communication loop must use the same transformer pole for G terminal 10 and G0 terminal 11 On the communication loop the A terminal terminal 42 should only be connected to another A terminal and the B terminal terminal 43 to another B terminal Otherwise there is great danger of short circuit with damaged components as a result Inputs AI PT1000 sensor 0 50 C accuracy 0 1 C UI AI PT1000 sensor 0 100...

Страница 4: ...enu and change parameter 20 to thermal actuator 24 UO2 Control output heating or cooling FS For 0 10 V DC valve actuator max 5 mA FS The valve actuator s 0 10 V control signal terminal is connected to terminal 24 and its supply terminals to terminals 10 and 11 Make sure that the reference pole G0 is connected to the correct terminal on the actuator alternative For 24 V AC thermal actuator max 2 0 ...

Страница 5: ...l STRA 07 for Fancoils Fläkt Woods 8713 GB 2014 04 5 Specifications are subject of alteration without further notice Plug in of relay box STRZ 14 to fan coil unit QFDK mounted in ceiling Plug in of condensation detector Plug in of relay box STRZ 14 to STRA 07 ...

Страница 6: ...ses the current setpoint by 0 5 C with each press up to the max limit FS 3 C Pressing on DECREASE decreases the current setpoint by 0 5 C with each press down to the min limit FS 3 C Switching between heating and cooling setpoints is done automatically in the controller depending on the heating and cooling requirement Fan control Fan control STRA 07 has a fan button When you press the button a sym...

Страница 7: ... CENELEC EN 61000 6 1 and EN 61000 6 3 and the requirements of European LVD standard IEC 60 730 1 It carries the CE mark Inputs External room sensor PT1000 sensor 0 50 C Suitable sensor is Fläkt Woods STRZ 05 Occupancy detector Closing potential free contact Suitable occupancy detector is Fläkt Woods STRZ 09 Condensation detector alt window contact Fläkt Woods condensation detector STRZ 16 alt win...

Страница 8: ...n 19 C and 27 C The setpoints can also be adjusted 3 C via the display Display the background lighting is lit dimmed STANDBY and the current room temperature or setpoint depending on the configuration are shown in the display Occupied Operating mode Occupied means that the room is in use and is therefore in a comfort mode The controller regulates the room temperature around a heating setpoint and ...

Страница 9: ...r cooling via the change over function Heating Heating Heating Cooling Heating Cooling with VAV control and forced supply air function Heating Cooling with VAV control Cooling Cooling Cooling For the control states UO1 is used for the left control function and UO2 is used for the right control function For control states where only one control function is active Heating Heating or cooling via the ...

Страница 10: ...two types of actuators Analogue 0 10 V actuators Thermal actuators The actuator type is set via the parameter menu in the display Analogue actuators The following output signals can be set for analogue actuators 0 10 V FS 2 10 V 10 2 V 10 0 V Thermal actuators When thermal actuator control has been selected this is controlled digitally with time proportional pulses via output UO By pulsing the ope...

Страница 11: ...osition with high speed Manual setting of speed I III means that the speed of the fan in operating modes Stand by Occupied and Bypass is always the set speed In the other operating modes the fan is demand controlled Auto control In auto mode you can configure if the fan should be controlled by the heating output the cooling output or both the heating and cooling outputs When the selected output ex...

Страница 12: ...heating and cooling outputs are set to 0 V and the frost protection function is activated Frost protection STRA has built in frost protection which is activated when the controller is not in use The frost protection prevents the temperature from dropping below 8 C Return to normal fan speed and control occurs automatically when the room temperature exceeds 8 C Parameter Settings STRA 07 is deliver...

Страница 13: ...ndby Neutral Zone C 3 4 Unoccupied Heating Setpoint C 15 5 Unoccupied Cooling Setpoint C 30 6 Frost protection Setpoint C 8 7 P Band C 10 8 I Time sec 300 9 Cooling Changeover difference temperature Room and media C 3 10 Heating Changeover difference temperature Room and media C 4 11 Heating Cooling Functions 0 Heat 1 Heat Heat 2 Heat or Cool via changeover 3 Heat Cool 4 Heat Cool with VAV and for...

Страница 14: ... hours 23 37 Cooling Valve Periodic Exercise Interval 0 inactive hours 23 38 Hysteresis for the heating thermostat function C 2 39 Hysteresis for the cooling thermostat function C 2 40 The minimum heat output in heating mode 0 41 Fan runs on low speed Not in use 0 0 42 Display View 0 Actual Temp Value 1 Heating Setpoint 2 Cooling Setpoint 3 Average of Heating Cooling 4 Only Setpoint Displacement 5...

Страница 15: ... Even 2 71 Modbus Timeout millisecond 3 72 Modbus Response Delay Millisecond 5 73 Heating output 0 For N C actuator 1 For N O actuator 0 74 HMI Displacement View 0 The offset 1 The active setpoint offset 2 The heating setpoint offset 3 The cooling setpoint offset 4 Occupied Heating Setpoint Offset 5 Occupied Cooling setpoint Offset 6 Occupied Average Offset 0 0 75 Free Cooling 0 ON 1 OFF N A 0 76 ...

Страница 16: ...t PPM 0 114 Port Mode 0 EXOline Modbus 1 BACnet 0 115 BACnet address Above 127 Slave 116 BACnet device ID low 4 figures 117 BACnet device ID high 3 figures 118 BACnet Max Master 127 119 Com Speed 0 9600 1 19200 2 38400 3 76800 BACnet 0 120 Reset com to factory default Modbus 9K6 8 N 1 0 121 The lowest output the fan will need to start Not in use 0 V 10 122 The highest speed of the fan Not in use 0...

Отзывы: