STRA-07 Room Controller. Installation and maintenance manual.
Fläkt Woods
8713 GB 2014.04
15
Specifications are subject of alteration without further notice.
Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter number
Description
Values
Unit
FS STRA-07
53
Fan Speed 3 Limit
0
%
100
54
Fan Start/Stop Hyst
0
5
55
Fan Speeds
0
3
56
External Temperature Sensor Calibration Gain AI1
°C
0
57
Sensor Calibration Gain UI1
°C
0
58
Internal Temperature Sensor Calibration Gain
°C
0
59
Filter factor for AI temperature
°C
0.2
60
Normally open/Normally closed DI1
0 = For N/C-actuator,
1=For N/O-actuator
0
61
Normally open/Normally closed DI2
0=N/O,
1=N/C
1
62
Normally open/Normally closed UI1
0=N/O,
1=N/C
0
63
Heating Manual Override
0=,
1=Manual,
2=Auto
2
64
Cooling Manual Override
0=,
1=Manual,
2=Auto
2
65
Forced ventilation Manual Override
0=,
1=Manual,
2=Auto
2
66
Changeover Manual Override
0=Heating,
1=Cooling,
2=Auto
2
67
Manual Mode Heating Output
%
0
68
Manual Mode Cooling Output
%
0
69
Modbus Address
70
Modbus Parity
0=None,
1=Odd,
2=Even
2
71
Modbus Timeout
millisecond
3
72
Modbus Response Delay
Millisecond
5
73
Heating output
0 = For N/C-actuator,
1=For N/O-actuator
0
74
HMI Displacement View
0=The offset,
1=The active se offset,
2=The heating se offset,
3=The cooling se offset,
4=Occupied Heating Se Offset,
5=Occupied Cooling se Offset,
6=Occupied A Offset
0
0
75
Free Cooling
0=ON, 1=OFF
N/A
0
76
Forced Ventilation control mode
0=No Action,
1=Forced on Heat/Cool output at 100%,
2=Forced on Cool output at 100%
0
77
P.I.R Activated Operation Mode
3=Occupied,
4=Bypass
4
78
The Controller PLA Address. Used in EXOline
0
79
The Controller ELA Address. Used in EXOline
0
80
Cool output
0=N/O, 1=N/C
0
81
AI2 Input
0=Disable,
5=CO2,
7=0-100% ,
8=Flow calculation,
9=0-10V
0
82
Flow at 0 volt on AI2 (Not in use)
0
l/s
0
83
Flow at 10 volt at AI2 (Not in use)
0
l/s
100
84
The minimum time the valve is open when the
calculation of change over is made
sec
60
86
Alarm triggers when temperature falls below
°C
40
87
Alarm triggers when temperature raise above
°C
15
97
CO2 Level to Change to Boost Mode
PPM
0
98
CO2 Level below "Boost Mode CO2 Start" value to
start Boost Mode Timer countdown
PPM
0
100
AI CO2 Filter
0
104
CO2 Sensor PPM for 0v
PPM
104
105
CO2 Sensor PPM for 10v
PPM
0