STRA-07 Room Controller. Installation and maintenance manual.
STRA-07 for Fancoils
Fläkt Woods
8713 GB 2014.04
3
Specifications are subject of alteration without further notice.
Wiring
STRA-07 has been constructed to be as compact as
possible. Therefore, the controller’s communication input
is not galvanically separated from the supply voltage.
This means that it is important to keep G and G0 in order,
as well as the communication input’s A and B.
All units that share the same transformer and
communication loop must use the same transformer-
pole for G (terminal 10) and G0 (terminal 11). On the
communication loop the A-terminal (terminal 42) should
only be connected to another A-terminal and the B-
terminal (terminal 43) to another B-terminal. Otherwise,
there is great danger of short-circuit with damaged
components as a result.
Inputs
AI
PT1000-sensor, 0...50°C, ac/- 0.1°C
UI
AI: PT1000-sensor, 0...100°C, ac/- 0.2°C or
DI: see DI below
CI
Fläkt Woods’s condensation detector, STRZ-16
DI
Closing potential-free contact connected to +C in
one end
Outputs
DO
24 V AC, max 0,5 A
UO
DO:24 V AC, max 2.0 A or AO:0.5...10 V DC, max
5 mA +C, power output for DI only...24 V DC,
max 10mA, short circuit protected