GENERAL INSTALLATION STEPS  

(Collar Mount) (see Fig. 2) 
(Inlet collars are available as a kit from your 
distributor)

 

1.  Before installing, remove any packaging. Open 

the door and remove the filters. Remove the 
lower panel on the front of the unit to remove 
PCO and VOC filters and the lamps and gloves 
which were packed at the bottom of the unit. 
See Maintenance for instructions to remove the 
filters. 

2. This unit can be installed with collars and 

aluminum flexible ducting if desired. 

DO NOT 

use plastic duct. 

Openings are pre-punched 

on the top and bottom of the unit for this 
purpose. Remove the plastic film covering the 
holes and snip out the joints to open the hole. 

Do not open the holes on the back of the 
unit if you are collar mounting the Air 
Cleaner.

 

3.  The collar is installed with the flange on the 

inside of the cabinet with only the collar ring on 
the outside of the cabinet. Compress the collar 
until you can insert the flange into the opening 
in the enclosure. Enlarge the collar to its 
maximum and install two screws into the ring to 
hold it to the proper diameter. Turn the collar in 
the hole until the holes in the enclosure line up 
to the holes on the collar flange. Secure with 
the screws provided. 

4.  The intake collar on the return duct must be 

installed after the last return branch connection 
on the plenum. If outside air is introduced into 
the return air duct, either through a HRV (Heat 
Recovery Ventilator) or direct, it should be 
added to the system before the intake inlet to 
the Air Cleaner. 

5.  The 8 inch intake collar (top) must draw air from 

the return duct at a location that will be ahead of 
the clean exhaust air, that will be returned to the 
duct from the Air Cleaner. 
An 8 inch collar will be installed on the return 
duct and a length of 8 inch flexible hose or duct 
is required to attach between the 8 inch intake 
collar and the collar on the return duct. When 
running the hose, make sure that there are no 
kinks or sharp bends that will impede the air 
flow to the unit. Secure and seal the hose and 
connections to prevent air leakage. 

6.  The 8 inch exhaust collar can be mounted in the 

same manner to the bottom of the unit. An 8 
inch collar will be installed on the return duct 
close to the furnace and a length of 8 inch 
flexible hose or duct is required to attach 
between the exhaust collar and the collar on the 
return duct. 

Do Not use plastic duct. 

The ideal 

location is low on the return air boot pointing at 
the furnace. To prevent air shear inside the 
duct, it is recommended that you install a 
deflector inside the boot, so the discharged air 
is deflected down into the boot. When running 
the hose, make sure that there are no kinks or 
sharp bends that will impede the air flow from 
the unit. Secure and seal the hose and 
connections to prevent air and UV light leakage. 

Fig. 2 – Collar Mount Installation 

WARNING  

If the top and bottom openings are being used to 
install this Air Cleaner, ducting 

MUST

 be installed to 

ensure no light escapes from the unit. 

Fig. 3 – Self-Contained Basement Installation 

Alternate Installations 

 

Содержание DM900UV-VO-A

Страница 1: ...traviolet Germicidal Lamps CinQuartz Photo Catalytic Oxidation Filter removes unpleasant odors and Volatile Organic Compounds Carbon Potassium Permanganate Final Filter removes non organic gases Kills or inhibits bacteria viruses mold fungi and microbial growth Easy to change Filters and Lamps Powerful motor delivers 250 CFM of clean sterilized air Heavy gauge galvanized steel cabinet and external...

Страница 2: ...time and redecorating costs Provides a healthier more comfortable environment year round HOW IT WORKS Millions of airborne pollutants are carried through the return air ducts of the heating cooling system The Air Cleaner has been designed to be installed on the return air duct A portion of this return air is by passed through an opening on the rear or top of the unit and passes through a 5 stage f...

Страница 3: ... the holes on the top or bottom of the unit if you are duct mounting the Air Cleaner Bend all the flaps outward slightly less than 90 degrees except for the upper bottom flap which is only bent up 45 degrees This bottom flap will act as a deflector for the exhaust air entering back into the plenum 5 Place the gasket material around the two openings on the back of the air cleaner 6 Place the unit o...

Страница 4: ...r direct it should be added to the system before the intake inlet to the Air Cleaner 5 The 8 inch intake collar top must draw air from the return duct at a location that will be ahead of the clean exhaust air that will be returned to the duct from the Air Cleaner An 8 inch collar will be installed on the return duct and a length of 8 inch flexible hose or duct is required to attach between the 8 i...

Страница 5: ... cord to be placed where it may be walked on or allow anything to roll over it MAINTENANCE For efficient operation the filters must be changed on a regular basis If you notice a reduction in air flow from the system check the filters WARNING Never use the Air Cleaner without all of the filters in place and all cover panels and doors closed Make sure all the screws are in place CAUTION Make sure to...

Страница 6: ...tancy of the HEPA filter Note Handle the HEPA filter by the frame only The paper is fragile and a puncture or tear will reduce efficiency Replacing the UV Lamps PCO Filter and Final Filter 1 To change the PCO filter Final filter and UV lamps turn the Air Cleaner OFF and UNPLUG it Remove the screws from the lamp access panel and remove the panel DO NOT misplace the parts 2 Carefully remove the filt...

Страница 7: ... may still light after 2 years but the intensity of the germicidal wavelength will be reduced UV Lamp PCO Filter Kit DM900 1002 Kit contains 2 UV lamps 2 lamp support clips 1 PCO filter and gloves Dimensions Height Width Depth 29 5 in 16 25 in 12 75 in 74 9 cm 41 3 cm 32 4 cm Intake 14 5 x 3 75 in or 8 in dia 36 8 x 9 5 cm or 20 3 cm dia Outflow 14 5 x 4 37 in or 8 in dia 36 8 x 11 1 cm or 20 3 cm...

Страница 8: ...emoving installing shipping servicing or handling of either defective parts or replacement parts LIMITATIONS OF WARRANTY All implied warranties including implied warranties of merchantability are hereby limited in duration to the period for which the limited warranty is given The expressed warranties made in this warranty are exclusive and may not be altered enlarged or changed by any distributor ...

Отзывы: